Plan Review Details - Permit 10080235
Plan Review Stops For Permit 10080235
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-09-28 Cont ID  
Sent By wjolin Date 2010-09-28 Time 14:21 Rev Time 0.00
Received By wjolin Date 2010-09-28 Time 14:15 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-08-31 Cont ID  
Sent By wjolin Date 2010-08-31 Time 10:35 Rev Time 0.00
Received By wjolin Date 2010-08-31 Time 10:19 Sent To M
Notes
2010-08-31 10:34:39*****REVIEW COMMENTS - FIRE*****
  
 1) FOR SPRINKLER SYSTEM TO THE WEST (SUPPLIED BY OTHER
 RISER), ADD CROSS MAIN TO TREE SYSTEM NEAR COLUMN LINES
 L/N TO CONVERT TREE SYSTEM TO A GRID SYSTEM OR PROVIDE
 HYDRAULIC CALCULATION SUPPORTING THAT THE EXISTING
 LAYOUT IS SUFFICIENT FOR THE HAZARD BEING PROTECTED.
  
 2) IN ADDITION TO THE SCOPE OF WORK NOTE #2, SHOW ALL
 ADDITIONAL SPRINKLERS REQUIRED IN THE TENANT SPACES TO
 REDUCE THE AREA OF COVERAGE PER SPRINKLER TO 130 SQUARE
 FEET OR LESS. THE SXL METHOD MUST BE USED TO DETERMINE
 THE AREA OF COVERAGE PER SPRINKLER. APPROXIMATELY 45
 TENANT SPACES APPEAR TO HAVE SPRINKLERS COVERING MORE
 THAN 130 SQ.FT.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By wjolin Date 2010-08-12 Time 11:37 Rev Time 0.00
Received By wjolin Date 2010-08-12 Time 10:44 Sent To M
Notes
2010-08-12 11:37:47TUESDAY AUGUST 17, MET WITH MIKE & CINDY OF SUMMERS
 FIRE PROTECTION TO DISCUSS SUBMITTED DESIGN DOCUMENTS.
 REVISED PLANS WILL BE RESUBMITTED.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-23 Cont ID  
Sent By jgomez Date 2010-09-23 Time 10:32 Rev Time 0.00
Received By jgomez Date 2010-09-23 Time 10:32 Sent To FIRE
Notes
2010-09-23 10:33:20SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-01 Cont ID  
Sent By hmoser Date 2010-09-01 Time 13:23 Rev Time 0.00
Received By hmoser Date 2010-08-24 Time 14:09 Sent To  
Notes
2010-08-24 14:09:59INCOMING SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-01 Cont ID  
Sent By hmoser Date 2010-09-01 Time 13:24 Rev Time 0.00
Received By hmoser Date 2010-08-10 Time 14:42 Sent To  
Notes
2010-08-10 14:42:53TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-10-01 Cont ID  
Sent By rmcdouga Date 2010-10-01 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2010-10-01 Time 13:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-09-01 Cont ID  
Sent By hmoser Date 2010-09-01 Time 13:20 Rev Time 0.00
Received By hmoser Date 2010-09-01 Time 13:20 Sent To  
Notes
2010-09-01 13:22:22PLANS DENIED
 CAN'T READ PIPE SIZE ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By hmoser Date 2010-08-25 Time 09:53 Rev Time 0.00
Received By hmoser Date 2010-08-25 Time 09:53 Sent To  
Notes
2010-08-25 09:54:33NEED REVISIONS