Plan Review Stops For Permit 10080218 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2011-02-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-02-10 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-02-10 |
Time |
07:09 |
Sent To |
|
|
Notes |
2011-02-10 11:05:07 | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVAL FOR THE PGT FRENCH DOORS IS FOR | | THE 2004 EDITION OF THE FBC. PLEASE SUBMIT TWO COPIES | | OF FL253-R9 WHICH IS THE CURRENT PRODUCT APPROVAL FOR | | THESE DOORS. | | | | 2) THE PLANS NEED TO BE TAKEN TO PALM BEACH COUNTY FOR | | IMPACT FEE REVIEW. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-08-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-31 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-31 |
Time |
14:35 |
Sent To |
|
|
Notes |
2010-08-31 15:15:14 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) ON SHEET SP-1 THE 2004 EDITION OF THE EXISTING | | BUILDING CODE IS SPECIFIED. PLEASE UPDATE TO THE 2007 | | EXISTING BUILDING CODE. | | | | 2) BASED ON THE 2009 REVISIONS TO THE FLORIDA BUILDING | | CODE RESIDENTIAL BECAUSE THE STRUCTURE IS LOCATED | | WITHIN 1500 FT OF EXPOSURE C TERRAIN, IT IS REQUIRED TO | | BE DESIGNED FOR EXPOSURE C. FBC R301.2.1.4.3. PLEASE | | REVISE SHEETS SP1, S1 AND S2. | | | | 3) PLEASE INCREASE THE WINDOW AND DOOR PRESSURES ON S2 | | TO REFLECT EXPOSURE C. FBCR301.2.1 | | | | 4) PLEASE UPDATE THE STRUCTURAL NOTES ON SHEET S-3 TO | | REFERENCE THE 2007 FBC AND ASCE7-05. | | | | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE PGT | | IMPACT WINDOWS, THERMA-TRU IMPACT DOORS AND THE METAL | | ROOF SPECIFIED ON THE PLANS. DCA RULE 9B-72 | | | | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS AND EVALUATION REPORTS FOR THE ICYNENE | | SPRAY FOAM INSULATION. FBC R314 | | | | 7) THE PLANS INDICATE THAT THERE IS 3'-11" BETWEEN THIS | | STRUCTURE AND ANOTHER DWELLING UNIT LOCATED ON THE SAME | | PROPERTY. THE FIRE SEPARATION DISTANCE IS DEFINED AS | | THE DISTANCE FROM THE BUILDING FACE TO AN IMAGINARY | | LINE BETWEEN TWO BUILDINGS ON THE LOT. THEREFORE, THE | | FIRE SEPARATION DISTANCE IS 1' - 11 & 1/2" . SECTION | | 302.1 OF THE EXISTING BUILDING CODE REQUIRES PORTIONS | | OF A STRUCTURE THAT ARE BEING ALTERED TO COMPLY WITH | | THE FLORIDA BUILDING CODE. THE PLANS INDICATE THAT THE | | PORTION OF THE WALL WITH A FIRE SEPARATION DISTANCE OF | | LESS THAN 3 FEET IS BEING ALTERED TO ADD SOME WINDOWS. | | BASED ON FBCR TABLE R302.1, NO OPENINGS ARE ALLOWED IN | | THIS SECTION OF WALL. ALSO THE ALTERED WALL, NEW GABLE | | END AND UNDERSIDE OF THE OVER-HANG PROJECTION WILL | | REQUIRE A MINIMUM ONE HOUR FIRE-RESISTANCE RATING. | | PLEASE ADDRESS. | | | | 8) THE PLANS INDICATE THAT AN EXISTING STORAGE AREA | | WILL BE CONVERTED TO LIVING SPACE AT THE NEW BATHROOM. | | THIS WILL REQUIRE THE PLANS TO BE REVIEWED BY PALM | | BEACH COUNTY FOR IMPACT FEES. PLEASE INDICATE UNDER THE | | AREA CALCULATIONS ON THE PLANS THE SQUARE FOOTAGE OF | | THE STORAGE AREA THAT IS BEING CONVERTED TO LIVING | | SPACE. | | | | 9) SHOW COMPLIANCE WITH FBC R313.2.1 FOR REQUIRED SMOKE | | ALARMS. | | | | 10) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW | | EACH OF THE COMMENTS IS BEING ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2011-01-24 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-01-24 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-01-24 |
Time |
15:38 |
Sent To |
|
|
Notes |
2011-01-24 15:40:03 | REQUIRES ELECTRICAL PLANS TO BE SUBMITTED FOR REVIEW. | | REQUIRES AN ELECTRIC PERMIT. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
dwise |
Date |
2010-08-25 |
Time |
19:22 |
Rev Time |
0.00 |
Received By |
dwise |
Date |
2010-08-25 |
Time |
19:22 |
Sent To |
|
|
Notes |
2010-08-25 19:25:59 | MISSING ELECTRICAL PLAN AND OR NOTES | | JOHN DICKINSON CONTRACT PLAN REVIEWER CELL PHONE 561 | | -718-3230 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2011-02-08 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2011-02-08 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2010-08-09 16:47:53 | OK PER J PAPA NO FEE 8-9-10 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2011-01-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-01-21 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-01-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-01-24 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-11 |
Time |
13:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2011-03-02 15:05:09 | IMPACT FEE REVIEW IS REQUIRED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2010-08-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-31 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-31 |
Time |
11:56 |
Sent To |
|
|
Notes |
2010-08-31 11:57:23 | NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL | | PERMIT APPLIED FOR. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2011-02-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-02-10 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-02-10 |
Time |
11:07 |
Sent To |
|
|
Notes |
2011-02-10 11:08:24 | DENIED BY PLUMBING | | | | 1) COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT BEEN | | ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2010-08-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-31 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-31 |
Time |
11:57 |
Sent To |
|
|
Notes |
2010-08-31 13:54:06 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) SUBMIT TWO SETS OF A SANITARY RISER DIAGRAM. SPECIFY | | PIPE SIZES, VENT LOCATIONS, CLEAN-OUTS, ETC. FBC | | 106.3.5 | | | | 2) INDICATE THE SIZE, TYPE AND LOCATION OF THE WATER | | HEATER. FBCR M2005.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2011-02-09 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2011-02-09 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2011-02-09 |
Time |
14:34 |
Sent To |
|
|
Notes |
2011-02-09 14:35:02 | ZONING PLAN REVIEW | | | | PERMIT NO.: 10080218 | | ADDRESS: 714 NEW JERSEY STREET | | CONTRACTOR/CONTACT: PENE LATHAM | | TELEPHONE NO.: 561.832.1500 | | SCOPE OF REVIEW: REMODEL OF ACCESSORY DWELLING UNIT. | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1) PURSUANT TO SECTION 94-513(B)(1)(D) OF THE CITY???S | | ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), | | NONCONFORMING USES WITH NO ADVERSE IMPACTS MAY ONLY BE | | ALTERED OR REPAIRED PROVIDED THE COSTS INCURRED WITHIN | | A 12-MONTH PERIOD DOES NOT EXCEED 50 PERCENT OF THE | | VALUE OF THE STRUCTURE OR BUILDING. PLEASE PROVIDE A | | CURRENT AND ACCURATE APPRAISAL INDICATING THE VALUE OF | | THE STRUCTURE TO BE REMODELED (NOT THE ENTIRE | | PROPERTY). AS THE PERMIT VALUE INDICATES $20,000 WORTH | | OF CONSTRUCTION, THE VALUE OF THE STRUCTURE MUST EXCEED | | $40,000 IN ORDER TO BE EXEMPT FROM THE ABOVE-REFERENCED | | PROVISION. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN ROACH, SENIOR PLANNER | | CITY OF WEST PALM BEACH | | PLANNING AND ZONING DEPARTMENT | | 401 CLEMATIS STREET - P.O. BOX 3366 | | WEST PALM BEACH, FLORIDA 33402 | | | | PHONE: 561.822.1435 | | FAX: 561.822.1460 | | | | EMAIL: [email protected] | | | | WWW.CITYOFWPB.COM | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-09-01 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2010-09-01 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2010-09-01 |
Time |
11:35 |
Sent To |
|
|
Notes |
2010-09-01 11:53:46 | ZONING PLAN REVIEW | | | | PERMIT NO.: 10080218 | | ADDRESS: 714 NEW JERSEY STREET | | CONTRACTOR/CONTACT: PENE LATHAM | | TELEPHONE NO.: 561.832.1500 | | SCOPE OF REVIEW: REMODEL OF ACCESSORY DWELLING UNIT. | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1) PURSUANT TO SECTION 94-513(B)(1)(D) OF THE CITY???S | | ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), | | NONCONFORMING USES WITH NO ADVERSE IMPACTS MAY ONLY BE | | ALTERED OR REPAIRED PROVIDED THE COSTS INCURRED WITHIN | | A 12-MONTH PERIOD DOES NOT EXCEED 50 PERCENT OF THE | | VALUE OF THE STRUCTURE OR BUILDING. PLEASE PROVIDE A | | CURRENT AND ACCURATE APPRAISAL INDICATING THE VALUE OF | | THE STRUCTURE TO BE REMODELED (NOT THE ENTIRE | | PROPERTY). AS THE PERMIT VALUE INDICATES $20,000 WORTH | | OF CONSTRUCTION, THE VALUE OF THE STRUCTURE MUST EXCEED | | $40,000 IN ORDER TO BE EXEMPT FROM THE ABOVE-REFERENCED | | PROVISION. | | | | 2) PURSUANT TO SECTION 94-305(B)(2) OF THE CITY'S | | ZLDRS, STRUCTURAL INTRUSIONS SHALL NOT ENCROACH MORE | | THAN THREE (3) FEET INTO ANY REQUIRED SETBACK. | | THEREFORE, THE NEW ROOF EAVE SHOWN ON THE SOUTH | | PROPERTY LINE SHALL BE AT LEAST TWO (2) FEET FROM THE | | SOUTH PROPERTY LINE. | | | | IMPORTANT ??? AS THE PROPOSED STRUCTURE DOES NOT MEET | | THE CURRENT SETBACK REQUIREMENTS, A NOTE WILL BE ADDED | | TO THE PERMIT INDICATING THAT IF ANY REBUILDING OF THE | | EXTERIOR WALLS, ETC. IS DEEMED NECESSARY, A REVISION TO | | THE PERMIT WILL BE REQUIRED, AND MAY REQUIRE THE | | APPROVAL OF A VARIANCE FROM THE ZONING BOARD OF | | APPEALS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN ROACH, SENIOR PLANNER | | CITY OF WEST PALM BEACH | | PLANNING AND ZONING DEPARTMENT | | 401 CLEMATIS STREET - P.O. BOX 3366 | | WEST PALM BEACH, FLORIDA 33402 | | | | PHONE: 561.822.1435 | | FAX: 561.822.1460 | | | | EMAIL: [email protected] | | | | WWW.CITYOFWPB.COM | | |
|
|