Plan Review Details - Permit 10080211
Plan Review Stops For Permit 10080211
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-17 Cont ID  
Sent By mcarsill Date 2010-08-17 Time 09:58 Rev Time 0.00
Received By mcarsill Date 2010-08-17 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-11 Cont ID  
Sent By mcarsill Date 2010-08-11 Time 11:53 Rev Time 0.00
Received By mcarsill Date 2010-08-11 Time 11:46 Sent To  
Notes
2010-08-11 11:53:26900 SOUTH OLIVE AVENUE
 ADD FIRE ALARM DEVICES TO THE EXISTING FIRE ALARM
 SYSTEM AS DEPICTED ON THE DRAWING.
  
  
 1. VALUE APPEARS TOO LOW FOR THE SCOPE OF WORK. THE
 GENERAL CONTRACTOR ADVISED THAT THE PERMIT VALUE SHOULD
 HAVE BEEN AROUND $ 7,000.00 DOLLARS. IF CORRECT, THE
 PLANS SHOULD HAVE BEEN SIGNED AND SEALED AND THE PERMIT
 APPLICATION SHOULD REFLECT THIS VALUE.
  
 2. NEW FIRE ALARM EQUIPMENT DISPLAYED HOWEVER EXISTING
 EQUIPMENT NOT DISPLAYED. PLANS SHOULD REFLECT ENTIRE
 FIRE ALARM SYSTEM BOTH NEW AND OLD EQUIPMENT.
  
 3. ARE THERE ANY EXISTING OR NEW DUCT DETECTORS
 PROVIDED IN THE BUILDING.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-17 Cont ID  
Sent By mcarsill Date 2010-08-17 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2010-08-17 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2010-08-11 Cont ID  
Sent By mcarsill Date 2010-08-11 Time 11:53 Rev Time 0.00
Received By mcarsill Date 2010-08-10 Time 14:49 Sent To  
Notes
2010-08-10 14:49:18TO FIRE
  