Plan Review Details - Permit 10080166
Plan Review Stops For Permit 10080166
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2010-09-27 Cont ID  
Sent By lmartine Date 2010-09-27 Time 09:45 Rev Time 0.00
Received By lmartine Date 2010-09-27 Time 09:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2010-08-19 Cont ID  
Sent By efabian Date 2010-08-19 Time 08:53 Rev Time 1.00
Received By efabian Date 2010-08-19 Time 08:53 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-01 Cont ID  
Sent By mcarsill Date 2010-09-01 Time 12:39 Rev Time 0.00
Received By mcarsill Date 2010-09-01 Time 12:37 Sent To  
Notes
2010-09-01 12:39:104175 BROADWAY AVENUE
 PERMIT NUMBER 10080166
  
  
 1. ACCESS SHALL BE PROVIDED TO THE FIRE HYDRANT AND ANY
 OTHER FIRE PROTECTION SYSTEM DEVICES.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-27 Cont ID  
Sent By lmartine Date 2010-09-27 Time 09:45 Rev Time 0.00
Received By lmartine Date 2010-08-19 Time 09:55 Sent To  
Notes
2010-08-10 11:32:55SENT TO C-7.

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-16 Cont ID  
Sent By eschneid Date 2010-08-16 Time 16:08 Rev Time 0.50
Received By eschneid Date 2010-08-11 Time 10:52 Sent To ENG
Notes
2010-08-16 16:08:33PASSED W/PROVISO (REDLINED ON PLANS)
  
 1) NOTE ALL PLAN REDLINES.
  
 2) THE EXISTING SIDEWALK SHALL HAVE RAMPS ADHERING TO
 CITY STANDARDS, NOT CURBING.
  
 3) THE PVC FENCE SHALL BE SOLID OPAQUE.
  
 4) THE DUMPSTER ENCLOSURE DOORS SHALL SWING OUTWARD.
  
 5) THE DUMPSTER SHALL BE ROLLED TO A LOCATION APPROVED
 BY SANITATION FOR PICK-UP AND THEN ROLLED BACK TO THE
 ENCLOSURE BY THE OWNER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.