Plan Review Stops For Permit 10080108 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-10-01 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-10-01 |
Time |
09:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-08-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-31 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-31 |
Time |
07:51 |
Sent To |
|
|
Notes |
2010-08-31 08:03:29 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE WINDOW SCHEDULE THAT WAS SUBMITTED INDICATES | | OPENINGS THAT ARE 108", 112" AND 204" WIDE. THESE ARE | | WIDER THAN THE WIDTH OF THE WINDOWS LISTED IN THE | | PRODUCT APPROVAL. ARE THESE MULTIPLE WINDOWS THAT ARE | | MULLED TOGETHER? PLEASE CLARIFY. | | | | 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | STRUCTURAL MULLIONS. | | | | 3) SHOW COMPLIANCE WITH FBCR 313.2.1 AND 313.4 FOR | | REQUIRED SMOKE ALARMS AND CARBON MONOXIDE PROTECTION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2010-10-01 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2010-10-01 |
Time |
12:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-08-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-24 |
Time |
19:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-24 |
Time |
19:11 |
Sent To |
|
|
Notes |
2010-08-24 19:17:22 | PERMIT PACKAGE SHOWS NO ELECTRICAL INFO AT ALL,NO PLAN | | OR ANY DISCREPTION OF WORK | | | | JOHN DICKINSON (CONTRACT REVIEWER PX3182) | | 561-718-3230 | | 561-805-6650 | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-09-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-09-28 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-09-28 |
Time |
15:23 |
Sent To |
|
|
Notes |
2010-09-28 15:24:36 | SENT TO R MCDOUGAL'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-08-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-31 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-05 |
Time |
11:50 |
Sent To |
|
|
Notes |
2010-08-05 11:50:28 | TO R15. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-10-01 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-10-01 |
Time |
10:56 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-30 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-30 |
Time |
15:54 |
Sent To |
|
|
Notes |
2010-08-30 16:33:34 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) THE NOTARIZED SIGNATURE OF THE MECHANICAL CONTRACTOR | | ON THE PERMIT APPLICATION IS REQUIRED. | | | | 2) ACCORDING TO ITEM NUMBER 53 IN THE SCOPE OF WORK, | | THE AIR-HANDLER IS TO BE RELOCATED. THIS WILL REQUIRE | | THE EXISTING DUCTWORK TO BE RE-CONFIGURED, THEREFORE, | | THIS IS NOT CONSIDERED AN EXACT CHANGE-OUT. SUBMIT TWO | | SETS OF HVAC DRAWINGS. PROVIDE FLOOR PLANS SHOWING THE | | LOCATION OF THE UNITS, SUPPLY AND RETURN DUCT LOCATIONS | | AND SIZES, GRILL SIZES, CFMS AT EACH DROP, TRANSFER | | DUCTS OR GRILLS. SPECIFY THE SIZE AND MODEL NUMBERS OF | | THE HVAC EQUIPMENT ON THE PLANS. | | | | 3) SUBMIT TWO COPIES OF MANUAL J CALCULATIONS OR OTHER | | APPROVED HEATING AND COOLING EQUIPMENT SIZING | | CALCULATIONS. | | | | 4) INDICATE THE LOCATION OF THE GAS DRYER (ITEM 21). | | SHOW COMPLIANCE WITH FBCR M1701.1 FOR COMBUSTION AIR. | | | | 5) THE DRAWINGS CAN BE DONE BY FLORIDA LICENSED DESIGN | | PROFESSIONALS OR A FLORIDA LICENSED HVAC CONTRACTOR. IF | | THEY ARE FROM A HVAC CONTRACTOR, THE NAME AND LICENSE | | NUMBER OF THE CONTRACTOR IS REQUIRED ON THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-10-01 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-10-01 |
Time |
09:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-30 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-30 |
Time |
16:34 |
Sent To |
|
|
Notes |
2010-08-30 16:47:24 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) SUBMIT TWO SETS OF AN ISOMETRIC DRAIN, WASTE AND | | VENT DRAWING. SHOW LOCATION OF THE NEW CLOTHES WASHER | | STANDPIPE. | | | | 2) THE DRAWINGS CAN BE DONE BY FLORIDA LICENSED DESIGN | | PROFESSIONALS OR A FLORIDA LICENSED PLUMBING | | CONTRACTOR. IF THEY ARE FROM A PLUMBING CONTRACTOR, THE | | NAME AND LICENSE NUMBER OF THE CONTRACTOR IS REQUIRED | | ON THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2010-08-09 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2010-08-09 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2010-08-09 |
Time |
13:37 |
Sent To |
|
|
Notes |
2010-08-09 13:37:30 | VALUE OF JOB DOES NOT EXCEED 50 PERCENT OF PAPA | | IMPROVEMENT VALUE. |
|
|