Plan Review Details - Permit 10080100
Plan Review Stops For Permit 10080100
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-02 Cont ID  
Sent By wjolin Date 2010-09-02 Time 15:17 Rev Time 0.00
Received By wjolin Date 2010-09-02 Time 15:16 Sent To M
Notes
2010-09-02 15:17:14*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-13 Cont ID  
Sent By wjolin Date 2010-08-13 Time 15:34 Rev Time 0.00
Received By wjolin Date 2010-08-13 Time 10:46 Sent To M
Notes
2010-08-13 15:34:23*****REVIEW COMMENTS - FIRE*****
  
 1) PLANS AND HYDRAULIC CALCULATIONS NOT SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER. SPRINKLER DESIGN IS
 LESS THAN 50 SPRINKLERS, BUT PLANS WERE SUBMITTED FOR A
 SPRINKLER PERMIT; HOWEVER, SHEET 2 OF 3 (NOTE #4)
 STATES, "FIRE EXTINGUISHING CONTRACTOR SHALL ENGINEER,
 DESIGN..ALL COMPONENTS." PLEASE EXPLAIN.
  
 2) PROVIDE JOB ADDRESS IN TITLEBLOCK.
  
 3) PROVIDE LOCKABLE KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 4) WHAT IS THE CHURN PRESSURE OF THE 147 PSI RATED FIRE
 PUMP? WHAT IS THE STATIC PRESSURE OF THE WATER STORAGE
 TANK? SYSTEM PRESSURES MAY BE EXCEEDING 175 PSI.
  
 5) HYDRAULIC PLACARD INFORMATION: CALCULATED AREA IS
 NOT 3000 SQ.FT.
  
 6) PROVIDE NOTE ON THE DRAWING INDICATING IF EXPOSED
 STRUCTURE IS OBSTRUCTED CONSTRUCTION OR UNOBSTRUCTED
 CONSTRUCTION, AND INDICATE MIN/MAX SPRINKLER DISTANCE
 ALLOWED BELOW ROOF DECK.
  
 7) SPRINKLER INFORMATION (TEMPERATURE, K-FACTOR ETC.)
 FROM HYDRAULIC CALCULATIONS NOT SHOWN ON THE PLANS.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-25 Cont ID  
Sent By lmartine Date 2010-08-25 Time 17:35 Rev Time 0.00
Received By lmartine Date 2010-08-25 Time 17:35 Sent To  
Notes
2010-08-25 17:35:41IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-16 Cont ID  
Sent By hmoser Date 2010-08-16 Time 13:13 Rev Time 0.00
Received By hmoser Date 2010-08-05 Time 12:00 Sent To  
Notes
2010-08-05 12:00:22SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-15 Cont ID  
Sent By hmoser Date 2010-09-15 Time 09:48 Rev Time 0.00
Received By hmoser Date 2010-09-15 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-16 Cont ID  
Sent By hmoser Date 2010-08-16 Time 13:07 Rev Time 0.00
Received By hmoser Date 2010-08-16 Time 13:07 Sent To  
Notes
2010-08-16 13:10:12PLAN DENIED
 REFER TO FIRE DEPARTMENT COMMENTS #1 AND #2 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732