Plan Review Details - Permit 10080065
Plan Review Stops For Permit 10080065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-09-30 Cont ID  
Sent By rmcdouga Date 2010-09-30 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2010-09-30 Time 15:53 Sent To  
Notes
2010-09-30 15:54:27DENIED BY BUILDING
  
 1) FS 471 REQUIRES DRAWINGS FROM A FLORIDA LICENSED
 ENGINEER ARE REQUIRED TO HAVE THEIR ORIGINAL SIGNATURE
 AND SEAL ON THE DRAWINGS.
  
 2) THE SURVEY DOES NOT INDICATE THAT THERE IS AN
 APPROVED EXISTING BARRIER AT THE SIDES BETWEEN THE
 PROPOSED REAR FENCE AND THE PRIVACY WALL OR BETWEEN THE
 PROPOSED FENCES. PLEASE CLARIFY.
  
 NOTE: THE POOL IS REQUIRED TO BE PROTECTED FROM ENTRY
 FROM THE DWELLING UNIT SEE FBC R4101.17.1.9.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-24 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2010-08-23 Time 16:50 Sent To Z
Notes
2010-08-24 11:06:36DENIED BY BUILDING
  
 1) FS 471 REQUIRES DRAWINGS FROM A FLORIDA LICENSED
 ENGINEER ARE REQUIRED TO HAVE THEIR ORIGINAL SIGNATURE
 AND SEAL ON THE DRAWINGS.
  
 2) THE SURVEY DOES NOT INDICATE THAT THERE IS AN
 APPROVED EXISTING BARRIER AT THE SIDES BETWEEN THE
 PROPOSED REAR FENCE AND THE PRIVACY WALL OR BETWEEN THE
 PROPOSED FENCES. PLEASE CLARIFY.
  
 NOTE: THE POOL IS REQUIRED TO BE PROTECTED FROM ENTRY
 FROM THE DWELLING UNIT SEE FBC R4101.17.1.9.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date   Cont ID  
Sent By BRM Date 2010-09-21 Time   Rev Time 0.00
Received By   Date 2010-09-21 Time   Sent To Z
Notes
2010-09-21 16:42:41PLEASE PROVIDE INFORMATION DETAILED IN COMMENTS BY
 ENGINEERING REVIEWER ON AUGUST 16.
 PROVIDE DETAILED LAYOUT OF SITE WITHIN SURVEY.
  
 BRIAN R. MOREE
 ENGINEERING CONSTRUCTION SUPERVISOR
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 561-494-1098
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-08-16 Cont ID  
Sent By efabian Date 2010-08-16 Time 15:49 Rev Time 0.50
Received By efabian Date 2010-08-16 Time 15:49 Sent To  
Notes
2010-08-17 08:27:44FAILED
  
 PLEASE RESPOND TO PLANNING & ZONING SENIOR PLANNER,
 LINDA MIA FRANCO'S COMMENTS CONCERNING FENCE AND
 FENCE-GATE LATCHING HARDWARE DETAILS.
  
 ALSO, PLEASE INCLUDE POOL PLAN AND LAY-OUT, LOCATION,
 SIZE, ETC., TO COMPLETE THIS APPLICATION.
  
 EMERY P. FABIAN
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-822-1200
 FAX: 561-494-1116
 MOBILE: 561-662-2269
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2010-08-23 Time 16:50 Sent To  
Notes
2010-08-23 16:50:32TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2010-08-04 Time 18:41 Sent To  
Notes
2010-08-04 18:41:14IN ZONING

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-09-27 Cont ID  
Sent By lfranco Date 2010-09-27 Time 18:52 Rev Time 0.00
Received By lfranco Date 2010-08-24 Time 16:51 Sent To B
Notes
2010-09-27 18:52:39PLANNING AND ZONING: *** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)
 AND (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 PROVIDE HEIGHT OF THE FENCE AND SELF-LATCHING
 INFORMATION ON PLANS. ALSO PROVIDE PERMIT NUMBER OF
 POOL PERMIT AND VICE VERSA TO ALLOW EASY REFERENCE TO
 BOTH PERMITS.
  
 RESUBMITTAL: THE SURVEY SUBMITTED SHOWS NEW FENCING
 ONLY ON THE SIDE OF THE HOME (APPROXIMATELY 10 LINEAR
 FEET - NORTH TO SOUTH) AND AT THE REAR. WHAT ABOUT THE
 NORTH AND SOUTH SIDE PROPERTY? THE ENCLOSURE SHALL BE
 FROM ALL SIDES SURROUNDING THE POOL) A SMALL 8-1/2" X
 11" PAGE OF THE SURVEY WITH THE POOL IS INCLUDED FOR
 REFERENCE ONLY (THIS SURVEY WAS PART OF THE POOL PERMIT
 1005045.)
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-13 Cont ID  
Sent By lfranco Date 2010-08-13 Time 19:27 Rev Time 0.00
Received By lfranco Date 2010-08-06 Time 15:31 Sent To ENG
Notes
2010-08-13 19:32:33PLANNING AND ZONING: *** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)
 AND (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 PROVIDE HEIGHT OF THE FENCE AND SELF-LATCHING
 INFORMATION ON PLANS. ALSO PROVIDE PERMIT NUMBER OF
 POOL PERMIT AND VICE VERSA TO ALLOW EASY REFERENCE TO
 BOTH PERMITS.
  
 3. AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (4TH
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  