Plan Review Details - Permit 10080004
Plan Review Stops For Permit 10080004
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-08-04 Cont ID  
Sent By jwitmer Date 2010-08-04 Time 16:30 Rev Time 0.77
Received By jwitmer Date 2010-08-04 Time 16:20 Sent To  
Notes
2010-08-04 16:43:26BUILDING PLAN REVIEW
 PERMIT: 10080004
 ADD: 124 N DIXIE HWY
 CONT: COLORS GROUP INC
 TEL: (561)371-2509
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 1) PROVIDE REPORT FOR TENANT/ OCCUPANCY SEPARATION WALL
 AND (2) HOUR FIRE RATING
 PER FBC-B TABLE 508.3.3 AND PENETRATIONS PER FBC-B
 712.3.1.2.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-24 Cont ID  
Sent By shill Date 2010-08-24 Time 17:58 Rev Time 0.00
Received By shill Date 2010-08-24 Time 17:58 Sent To  
Notes
2010-08-24 18:00:42OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By mcarsill Date 2010-08-10 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2010-08-10 Time 10:56 Sent To  
Notes
2010-08-10 10:58:16SPOKE TO ROBERT BROWN, ASSISTANT BUILDING OFFICIAL AND
 JIM WITMER REGARDING THESE PLANS. SOME INFORMATION
 PROVIDED BY THIS DEPARTMENT IS FOR FUTURE USE AND
 DEVELOPMENT.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-04 Cont ID  
Sent By mcarsill Date 2010-08-04 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2010-08-04 Time 15:00 Sent To  
Notes
2010-08-04 15:28:42124 NORTH OLIVE AVENUE
 PERMIT NUMBER 10080004
 INTERIOR RENOVATION
  
  
 1. PLEASE DECLARE PROPOSED OCCUPANCY TYPE.
  
 2. PLANS INDICATE INSTALLATION OF EXIT SIGNS AND
 EMERGENCY LIGHTS BUT THE DRAWINGS DO NOT SPECIFY ANY
 LOCATIONS FOR THESE DEVICES.
  
 3. NO WALL INSTALLATION DETAIL TO REPAIR THE TWO HOUR
 FIRE WALL.
  
 4. NO INTERIOR FINISH INFORMATION PROVIDED FOR WALLS
 AND CEILINGS.
  
 5. IT IS BELIEVED THAT PREVIOUSLY THE SPACE WAS USED AS
 A NIGHTCLUB. PLEASE BE ADVISED THAT CERTAIN OCCUPANCY
 TYPES THAT INCLUDE NIGHTCLUBS WITH OCCUPANT LOADS OF
 100 OR MORE PERSONS ARE NOW REQUIRED TO BE FIRE
 SPRINKLER PROTECTED.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-09 Cont ID  
Sent By lmartine Date 2010-09-09 Time 16:19 Rev Time 0.00
Received By lmartine Date 2010-09-09 Time 16:19 Sent To  
Notes
2010-09-09 16:20:39SEE REVISON #10090210

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By shill Date 2010-08-25 Time 06:12 Rev Time 0.00
Received By shill Date 2010-08-02 Time 13:37 Sent To  
Notes
2010-08-02 13:50:52NOT IN ELECTRIC BOX
 LOOK AT B--6
2010-08-02 13:38:20****************EXPEDITED*****************
 PUT IN ELECTRIC BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-19 Cont ID  
Sent By ajones Date 2010-08-19 Time 09:07 Rev Time 0.00
Received By ajones Date 2010-08-19 Time 09:07 Sent To  
Notes
***NONE***