Plan Review Details - Permit 10070788
Plan Review Stops For Permit 10070788
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-08 Cont ID  
Sent By shill Date 2010-10-08 Time 16:44 Rev Time 0.00
Received By shill Date 2010-10-07 Time 12:30 Sent To  
Notes
2010-10-08 16:45:15****PROVISOS****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 1. LS 0.00, TRAINING AREA (B) OCCUPANCY PER ARCHITECT,
 PLEASE REVISE.
  
 2. A2.01 AND OTHER AFFECTED SHEETS, 18" MIN MANEUVERING
 CLEARANCE REQUIRED FOR DOOR 118A, REVISE TO SHOW
 COMPLIANCE, SEE FBC FIGURE 11-25.
  
 3. DOOR PRODUCT APPROVAL, REVIEWED BY DESIGNER OF
 RECORD, TO BE SUBMITTED PRIOR TO INSTALLATION.
  
 4. ALL WORK OUTISDE THE BUILDING FOOTPRINT NOT INCLUDED
 IN THIS PERMIT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-30 Cont ID  
Sent By shill Date 2010-08-30 Time 14:13 Rev Time 0.00
Received By shill Date 2010-08-25 Time 07:04 Sent To  
Notes
2010-08-26 12:08:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE NOTIFY OWNER; THERE ARE EXPIRED PERMITS FOR
 THIS ADDRESS. PLEASE REQUEST TO EITHER VOID OR REAPPLY
 FOR THESE PERMITS.
  
 2. BUSINESS TAX RECEIPTS ON RECORD SHOW SUITE 102 IS
 OCCUPIED, BUT FLOOR PLAN SHOWS 102 AS STAIR 1. TENANT
 123 IS SHOWN. PLEASE ADVISE AS TO CORRECT SUITE NUMBERS
 CURRENTLY OCCUPIED OR REVISE PLAN TO CORRELATE WITH OUR
 RECORDS.
  
 3. SEE FBC1008.1.9. LS0.0 STATES THAT OCCUPANCY
 CLASSIFICATION IS B, BUT (A) IS SHOWN FOR TRAINING /
 BREAK AREA. DOORS 111A AND 112A HAVE PANIC HARDWARE AND
 CLOSER SPECIFIED ON SHEET A0.30, BUT THIS IS NOT SHOWN
 FOR DOOR 110A WHICH IS ALSO LOCATED IN THE MEANS OF
 EGRESS FOR THIS AREA. PLEASE REVISE OR CLARIFY DESIGN
 INTENT.
  
 4. DOOR 111B AND 112B, SHEET A2.01, PROVIDE INFORMATION
 REGARDING THE DOOR. SHEET A0.30 SHOWS THIS AS A 24IN
 DOOR, PLAN DOES NOT SHOW A SIDE HINGED DOOR. PLEASE SEE
 FBC1003.6, FBC 1008.1.2, 1008.1.1.
  
 5. SEE FBC1014.2, BREAK AREA ACCESS TO EXIT DOOR 112A
 IS THROUGH AN UNMARKED ROOM. PLEASE REVISE.
  
 6. PARTITION TYPE B IS NOT A RATED WALL, SHOWN AT
 STORAGE 114, BUT DOOR 114A IS SHOWN AS A 45 MINUTE
 DOOR. PLEASE CLARIFY DESIGN INTENT; SHOULD THE STORAGE
 AREA BE FIRE RESISTANCE RATED? SEE ALSO DOOR 117A. FBC
 508.
 7. DOORS 312 A AND B, DOORS TO BE FIRE RATED IN
 ACCORDANCE WITH FBC TABLE 715.4.
  
 8. SEE FBC1008.1.3.4, ACCESS CONTROLLED EGRESS DOORS,
 SHOW COMPLIANCE ON PLAN. THERE IS A NOTE REGARDING
 POWER ON THE PLAN, BUT PLEASE SHOW COMPLIANCE FOR ALL
 REQUIREMENTS.
  
 9. EXIT SIGN IN CORRIDOR 213 IS SHOWN DIRECTS OCCUPANTS
 THROUGH CORRIDOR 214 WHICH LEADS TO WORKSTATION 218.
 SEE FBC 1008.1.2, CANNOT USE THE SLIDING DOOR IN THE
 MEANS OF EGRESS EXCEPT AS PERMITTED IN EXCEPTIONS.
  
 10. FBC 1008.1.2, SHEETS LS2.01, LS2.02, LS2.03,
 CONFERENCE ROOMS MUST HAVE A SIDE HINGED DOOR FOR MEANS
 OF EGRESS. THE EXCEPTION (PRIVATE GARAGES, OFFICE
 AREAS, FACTORY AND STORAGE AREAS) DOES NOT APPLY TO
 THIS TYPE OF AREA. FOR EXAMPLE, SEE CONFERENCE ROOMS
 228, 248, 315, AND 340. PLEASE CHECK ALL.
  
 11. FBC11 4.24, SEE DETAIL 3 A8.03. A TOE KICK IS SHOWN
 FASTENED TO THE CABINET BASE, PLEASE SHOW HOW THIS
 COMPLIES WITH ACCESSIBILITY REQUIREMENTS. PLEASE CHECK
 ALL.
  
 12. FBC11 4.24, PLEASE SHOW ALL REQUIRED DIMENSIONS.
 NOTE THAT SINK DEPTH DOES NOT APPEAR TO COMPLY, 3
 A8.03, CHECK ALL.
  
 13. FLORIDA STATE OR LOCAL PRODUCT APPROVAL (REVIEWED
 BY DESIGNER OF RECORD) REQUIRED FOR EXTERIOR DOOR,
 FAC9B72.
  
 14. D2.03 NOTE 13 REFERS TO DETAILS ON STRUCTURAL
 SHEETS, PLEASE PROVIDE.
  
 15. PLANS STATE TO SEE CIVIL DRAWINGS FOR DETAIL FOR
 NEW RAMP ON EAST SIDE OF BUILDING 1ST FLOOR, NO CIVILS
 SUBMITTED. PLEASE PROVIDE A DETAIL FBC11 4.8.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-10-08 Cont ID  
Sent By dwise Date 2010-10-08 Time 16:00 Rev Time 0.00
Received By dwise Date 2010-10-08 Time 15:53 Sent To  
Notes
2010-10-08 16:00:15APPROVED WITH THE FOLLOWING PROVISOS:
 1. MUST OBTAIN SEPARATE PERMITS FOR EXTERNAL SITE
 ELECTRICAL WORK.
 2. MUST OBTAIN SEPARATE PERMITS FOR SERVICE UPGRADES
 RELATED TO THE INSTALLATION OF AN OPTIONAL STANDBY
 GENERATOR.
 3. MUST OBTAIN SEPARATE PERMITS FOR FIRE ALARM SYSTEMS.
 4. MUST PROVIDE REVISED POWER DENSITY TABULATIONS WHICH
 DEFINE FLOOR AREAS BY SF AND POWER UTILIZATION ON EACH
 FLOOR.
 5. MUST PROVIDE REVISED VOLTAGE DROP DATA FOR 3/0
 FEEDER CONDUCTORS SERVING DISTRIBUTION PANELBOARDS.
 6. OTHER PROVISOS AS NOTED ON THE APPROVED DRAWINGS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-09-22 Cont ID  
Sent By dwise Date 2010-09-22 Time 18:25 Rev Time 0.00
Received By dwise Date 2010-09-22 Time 18:25 Sent To  
Notes
2010-09-22 19:18:34ELECTRICAL PLAN REVIEW COMMENTS - 10070788
 9/21/2010
 DOUG WISE, 805-6650, [email protected]
  
 1. SHEET E0.02 NOTES 20 AND 21 - PLEASE NOTE THE DESIGN
 MUST SATISFY THE FOLLOWING CRITERIA:
 13-413.ABC.1.1 FEEDERS AND CUSTOMER-OWNED SERVICE
 CONDUCTORS. FEEDER AND CUSTOMER-OWNED SERVICE
 CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF
 2 PERCENT AT DESIGN LOAD.
 13-413.ABC.1.2 BRANCH CIRCUITS. BRANCH CIRCUIT
 CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF
 3 PERCENT AT DESIGN LOAD.
 THIS DESIGN RESPONSIBILITY CANNOT BE TRANSFERRED TO THE
 ELECTRICAL CONTRACTOR. THE DESIGN PROFESSIONAL SHALL
 PROVIDE A TABLE WITH WIRE SIZES AND MAXIMUM WIRE
 LENGTHS OR OTHER MEANS TO ENSURE THE DESIGN ITSELF
 SATISFIES THIS CRITERIA.
  
 2. SHEET E0.02 NOTE 39 - MULTIWIRE BRANCH CIRCUITS MAY
 BE PERMITTED IF THEY SHARE A COMMON BREAKER OR HANDLE
 TIE, FURTHER ALL CONDUCTORS SHALL BE "TIED" THAT SERVE
 SUCH A MULTI-WIRE BRANCH CIRCUIT WITHIN THE PANELBOARD
 PURSUANT TO SECTION 210.4(D).
  
 3. SHEET E2.01 - PROVIDE A PLAN WHICH DEMONSTRATES THE
 REQUIRED OPENING(S) AND RELATED ELECTRICAL FIXTURES FOR
 THE BREAK ROOM
  
 4. SHEET E2.01 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 5. SHEET E2.02 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 6. SHEET E2.03 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 7. SHEET E3.01 - VENDING EQUIPMENT OR RECEPTACLES MUST
 COMPLY WITH NEC 422.51
  
 8. SHEET E3.02 - SERVER ROOM MUST COMPLY WITH NEC 645.4
 AND 645.10 INCLUDING FIRE RATED SEPARATION,
 ELECTRICALLY CONTROLLED DAMPERS, AND DISCONNECTING
 MEANS FOR SEPARATE HVAC AND EQUIPMENT. PLEASE
 DEMONSTRATE COMPLIANCE AND COORDINATE DESIGN WITH OTHER
 RELATED PLAN PAGES.
  
 9. SHEET E3.02 - DRINKING FOUNTAIN CIRCUIT MUST BE GFI
 PROTECTED PURSUANT TO NEC 422.52. PLEASE COORDINATE
 WITH E7.03 PANEL SCHEDULE 2TB
  
 10. SHEET E3.02 - ONLY TWO "SMALL APPLIANCE" BRANCH
 CIRCUITS ARE SHOWN FEEDING THE BREAK ROOM COUNTER. IF A
 MICROWAVE OVEN AND A COFFEE MACHINE ARE DESIRED,
 ADDITIONAL DEDICATED CIRCUITS MAY BE REQUIRED TO
 ADEQUATELY SERVICE THIS LOCATION. PLEASE VERIFY THESE
 REQUIREMENTS WITH THE CUSTOMER.
  
 11. SHEET E3.03 - PLEASE REVIEW RECEPTACLE LOCATIONS IN
 THE BREAK ROOM. IT APPEARS INSUFFICIENT RECEPTACLES
 HAVE BEEN SHOWN AND ARE BEING SHOWN IN THE WRONG
 LOCATIONS. PLEASE REVIEW CUSTOMER NEEDS IN
 CONSIDERATION OF COMMENT #10 ABOVE. ENSURE ADEQUATE
 CIRCUITS ARE PROVIDED TO SATISFY CUSTOMER'S NEEDS.
  
 12. SHEET E5.01 - RISER INDICATES TENANT SPACE IS TO BE
 SERVED BY SEPARATE 15 ELECTRICAL METERS AND SERVICES.
 PLEASE VERIFY THAT THIS IS THE ACTUAL DESIGN INTENT.
 SHEET A2.01, NOTE 2 INDICATES THE CONTRACTOR IS TO
 PERMIT AND INSTALL AN EMERGENCY GENERATOR. ALTHOUGH AN
 EMERGENCY GENERATOR WILL BE PERMITTED SEPARATELY,
 ADEQUATE PROVISION IN THE ELECTRICAL SERVICE DESIGN IS
 NECESSARY TO FACITILATE THIS INTENT. PLEASE RECONCILE
 THESE INTENTIONS OR CLARIFY.
  
 13. SHEET E5.01 - IT APPEARS THAT PANEL 2SR IS BEING
 FED FROM METER 2ST. PLEASE CLARIFY OR RECONCILE.
  
 14. SHEET E5.02 - PLEASE NOTE THAT SEPARATE
 APPLICATION, REVIEW AND PERMITTING IS REQUIRED FOR FIRE
 ALARM AND ACCESS CONTROL SYSTEMS PROPOSED WITHIN THIS
 STRUCTURE. A SEPARATE "SUB-PERMIT" SHALL BE REQUIRED
 FOR ALL CATV / TELECOM / LOW VOLTAGE SYSTEMS NOT
 PERFORMED DIRECTLY BY THE "PRIME" ELECTRICAL
 CONTRACTOR.
  
 15. SHEET E6.01 - PLEASE NOTE THAT PURSUANT TO NEC
 ARTICLE 285 AND SECTION 285.5 ALL SURGE PROTECTION
 DEVICES (SPDS) SHALL BE LISTED. DEVICES BEARING THE
 TVSS DESIGNATION MAY NOT BE LISTED. ALSO PLEASE REVIEW
 SECTION 285.12 WHICH GOVERNS THE ROUTING OF CONNECTIONS
 BETWEEN THE SPD AND THE BUS. DESIGN DOCUMENTS SHOULD
 DESIGNATE SPDS AS TYPE 1, TYPE 2, AND TYPE 3 TO
 FACILITATE COMPLIANCE WITH ARTICLE 285.
  
 16. SHEET E7.01 - PLEASE NOTE MY PREVIOUS COMMENT UNDER
 NOTE 1 (ABOVE) REGARDING VOLTAGE DROP AND
 RESPONSIBILITY FOR THE DESIGN TO SATISFY THE CODE
 CRITERIA.
  
 17. SHEET E7.01 - THE ELECTRICAL PLANS APPEAR TO BE
 LACKING A "SPECIAL PURPOSE RECEPTACLE SCHEDULE" TO
 INDICATE WHAT DEVICES WILL BE ATTACHED TO THE NUMBERED
 SPECIAL PURPOSE RECEPTACLES SHOWN ON THE THREE
 ELECTRICAL FLOOR PLANS. SHEET E7.01 MIGHT BE AN
 APPROPRIATE LOCATION FOR SUCH A SCHEDULE.
  
 18. SHEET ED2.04 NOTE 6 - NO EQUIPMENT IS TO BE
 ENERGIZED WITH THE WRITTEN CONSENT OF THE CITY
 ELECTRICAL INSPECTOR. NO WORK IS TO BE PERFORMED ON
 ENERGIZED EQUIPMENT. AFTER HOURS INSPECTIONS ARE
 AVAILABLE UPON REQUEST TO FACILITATE COORDINATION OF
 INSPECTION AND MINIMIZE ADVERSE IMPACTS.
  
 19. SHEET ED2.04 NOTE 9 - ALL TEMPORARY ELECTRICAL
 SYSTEMS ARE TO BE DOCUMENTED, REVIEWED, INSPECTED AND
 FOUND TO BE IN FULL COMPLIANCE WITH ARTICLE 590 OF THE
 NEC BEFORE UTILIZATION.
  
 PLEASE FEEL FREE TO CONTACT ME DIRECTLY WITH CONCERNS
 OR QUESTIONS ABOUT THIS REVIEW.
  
 I MAY BE REACHED DURING NORMAL BUSINESS HOURS AT THE
 NUMBER SHOWN AT TOP OR BY EMAIL.
  
 DOUG WISE
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-08 Cont ID  
Sent By mcarsill Date 2010-10-08 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2010-10-08 Time 13:55 Sent To  
Notes
2010-10-08 15:14:57ON OCTOBER 7, 2010, A MEETING WAS HELD AT THE
 CONSTRUCTION SERVICES DEPARTMENT TO DISCUSS COMMENTS.
 THE FOLLOWING ITEMS NEED TO BE FURTHER CLARIFIED FROM
 THE PREVIOUS COMMENTS PROVIDED BY THE FIRE RESCUE
 DEPARTMENT.
  
 1. ITEM # 4 ON COMMENTS DATED 9/21/10 - SEPARATE PLANS
 AND PERMITS REQUIRED FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEM REMODELING.
  
 2. ITEM # 5 ON COMMENTS DATED 9/21/10 - PROVIDE CORRECT
 CODES AND STANDARDS THAT WERE USED FOR DESIGN PURPOSES.
  
 3. ITEM # 7 ON COMMENTS DATED 9/21/10 - NO CARD READERS
 ARE TO BE INSTALLED WITHIN STAIRWELLS.
  
 4. ITEM # 17 ON COMMENTS DATED 9/21/10 - EXIT DISCHARGE
 LIGHTING TO A PUBLIC WAY.
  
 5. MARK-UP ITEM ON PLANS - NOTE # 7 "POWERING DOWN OF
 FIRE ALARM SYSTEM" ON SHEETS ED2-01, ED2-02, AND ED2-03
 NEEDS TO BE CORRECTED.
  
  
 APPROVED PROVISO:
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-21 Cont ID  
Sent By mcarsill Date 2010-09-21 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2010-09-07 Time 10:46 Sent To  
Notes
2010-09-07 11:18:561920 WEKIVA WAY
 PERMIT NUMBER 10070788
 CONSTRUCTION WORK FOR A POTION OF THE FIRST FLOOR,
 COMPLETE SECOND AND THIRD FLOORS
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION ACTIVITIES
 TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED DAILY FROM THE SITE OR AS
 OFTEN AS NECESSARY.
  
 3. ADEQUATE FIRE LANES AND SUITABLE FIRE AND
 PARAMEDICAL ACCESS SHALL BE PROVIDED DURING
 CONSTRUCTION ACTIVITIES.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM REMODELING.
  
 5. WRONG EDITIONS OF FIRE CODES LISTED ON SHEET LS.O.
 THE CORRECT CODES ARE THE FLORIDA FIRE PREVENTION CODE
 2007 EDITION WHICH IS COMPRISED ON NFPA 1, 2006 EDITION
 AND THE LIFE SAFETY CODE, 2006 EDITION. ALSO NFPA 88A
 AND NFPA 20 ARE NOT APPLICABLE TO THIS PROJECT.
  
 6. ON SHEET AO.30, CARD READERS ARE MENTIONED IN ITEM #
 1. ELECTRONIC LOCKING DEVICES SHALL NOT INTERFERE WITH
 ANY EXITING. ANY SPECIAL LOCKING DEVICES ON EXIT DOORS
 SHALL COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION. ARE THESE DOORS FAIL
 SAFE OR FAIL SECURE.
  
 7. ON SHEET A0.30 CARD READER DEVICES NOT PERMITTED IN
 THE RATED STAIR ENCLOSURE PER SECTION 7.1.3.2 (6) OF
 NFPA 101, THE LIFE SAFETY CODE 2006 EDITION.
  
 8. DOOR # 110 A AND 116A IS SHOWN AS A 45 MINUTE RATING
 IN A 2 HOUR RATED WALL. NO DOOR CLOSER PROVIDED. CARD
 READER LOCKING DEVICES DO NOT CONFORM TO THE
 REQUIREMENTS OF 7.2.1.5 THROUGH 7.2.1.6.2 OF NFPA 101.
  
 9. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH
 APPROVED SELF-CLOSING DEVICES.
  
 10. ON SHEET LS2.01 TWO MEANS OF EGRESS THROUGH THE
 MOVABLE PARTITION WALLS IN BREAK ROOM # 112 PER SECTION
 7.2.1.12 OF NFPA 101.
  
 11. ON SHEET LS2.01 TWO VESTIBULE / CORRIDOR DOORS ARE
 SHOWN AS 1 HOUR FIRE RATED IN TWO-HOUR FIRE RATED
 WALLS.
  
 12. ON SHEET LS2.01 DOOR SWING FROM FILE 118 BLOCKING
 EGRESS FROM STORAGE 119.
  
 13. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
  
 14. ON SHEET LS2.03 THE ORIENTATION OF THE EXIT SIGNS
 NEAR STAIR # 1 AND STAIR # 2 MAY BE DIFFICULT TO BE
 SEEN FROM CORRIDOR # 301.
  
 15. ON SHEET A2.02 CARD READERS ON DOOR 225A, 213A,
 247A, AND 250A DO NOT CONFORM TO THE LOCKING
 REQUIREMENTS OF SECTION 7.2.1.5 OF NFPA 101.
  
 16. ON SHEET E2.01 NO EXIT SIGN PROVIDED IN VESTIBULE #
 116.
  
 17. ON SHEET E2.01 PLEASE PROVIDE EXIT DISCHARGE
 LIGHTING LEADING TO A PUBLIC WAY PER SECTION 7.8.1.1 OF
 NFPA 101.
  
 18. ON SHEET E2.03 EXIT SIGN AT COLUMN INTERSECTION 2/B
 ONLY DIRECTS OCCUPANTS TO THE EAST EXIT (AWAY FROM THE
 CLOSEST EXIT).
  
 19. ON SHEET E3.02 PLEASE PROVIDE VISUAL NOTIFICATION
 APPLIANCE IN BREAK ROOM # 209.
  
 20. ON PAGE A2.01 REFERENCE IS MADE TO THE INSTALLATION
 OF A GENERATOR. SEPARATE PLANS AND PERMITS REQUIRED FOR
 THE INSTALLATION OF THE GENERATOR AND ALL APPURTENANT
 EQUIPMENT.
  
 21. ON PAGE LS2.02 IT APPEARS THAT AN ADDITIONAL EXIT
 SIGN IS NEEDED IN CORRIDOR (245). PLEASE EXAMINE BLIND
 CORNERS.
  
 22. NOTE 15 ON PAGE E5.02 IS INCORRECT. THE ACTIVATION
 OF DUCT SMOKE DETECTORS SHALL CAUSE A GENERAL ALARM AND
 NOT A SUPERVISORY SIGNAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-09-30 Time   Rev Time 0.00
Received By rregueir Date 2010-08-09 Time 11:17 Sent To  
Notes
2010-08-25 11:18:03**ELECTRONIC PLANS** SEE PROJECTDOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By shill Date 2010-08-25 Time 08:39 Rev Time 0.00
Received By shill Date 2010-08-25 Time 08:39 Sent To  
Notes
2010-08-25 08:39:57INTERIOR BUILDOUT, IMPACT FEES PAID ON SHELL
  
  

Review Stop L LANDSCAPING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-10-07 Time   Rev Time 0.00
Received By rkussner Date 2010-10-07 Time 16:50 Sent To  
Notes
2010-10-07 16:52:19***LANDSCAPE REVIEW NOT REQUIRED***
  
 A SEPARATE LANDSCAPE PERMIT IS REQUIRED AND IS EXPECTED
 TO BE SUBMITTED ON 10/8/10 PER AV.---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-09-22 Cont ID  
Sent By rkussner Date 2010-09-22 Time 16:46 Rev Time 0.00
Received By rkussner Date 2010-09-22 Time 16:46 Sent To  
Notes
2010-09-22 17:21:19***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A TREE ALTERATION PERMIT THROUGH
 THE PLANNING AND ZONING DEPARTMENT. THE APPLICATION IS
 AVAILABLE AT THE FRONT DESK OF THE PLANNING AND ZONING
 DEPARTMENT. TWO COPIES OF THE LANDSCAPE PLAN SHALL BE
 SUBMITTED WITH THE APPLICATION.
  
 2. PLEASE PROVIDE A CURRENT SURVEY AND A PROPOSED SITE
 PLAN. IT WAS DIFFICULT TO DETERMINE WHERE THE OUTSIDE
 WORK WOULD BE TAKING PLACE ON THE SITE AND HOW IT WILL
 IMPACT THE AREA.
  
 3. A SEPARATE LANDCAPE PERMIT WILL BE REQUIRED. PLEASE
 SUBMIT THE APPLICATION AND TWO SETS OF SIGNED AND
 SEALED LANDSCAPE PLANS TO THE CONSTRUCTION SERVICES
 DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-10-01 Cont ID  
Sent By rregueir Date 2010-10-01 Time 16:03 Rev Time 0.00
Received By rregueir Date 2010-10-01 Time 16:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-30 Cont ID  
Sent By rregueir Date 2010-08-30 Time 10:44 Rev Time 0.00
Received By rregueir Date 2010-08-24 Time 11:30 Sent To  
Notes
2010-08-24 17:11:20REVIEW #: 1ST
 ACTION: IN PROGRESS
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVIEW COMMENTS:
  
 1. PG M0.01: CODE COMPLIANCE NOTES INDICATE "MIAMI-DADE
 COUNTY AMENDMENTS." SUCH AMENDMENTS ARE NOT APPLICABLE
 WITHIN THIS JURISDICTION. SEE ABOVE FOR APPLICABLE
 CODES.
  
 2. PG M2.01: FLOOR PLAN AND KEY NOTE #2 CALL FOR A
 12X12 OUTDOOR LOUVER. NO PRODUCT APPROVAL FOR SUCH
 LOUVER HAS BEEN PROVIDED. SUBMIT PRODUCT APPROVAL
 APPROVED IN WRITING BY THE DESIGN PROFESSIONAL IN
 ACCORDANCE WITH FBC-B 106.3.3 AND FAC RULE 9N-3
 (FORMERLY 9B-72).
  
 3. PG M2.02: KEY NOTE #1 CALLS FOR FIRE DAMPER AT DUCT
 PENETRATION OF SHAFT. DUCT PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5.5.
  
 4. PG M2.02: KEY NOTE #12 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF THE FILE STORAGE ROOM. THIS
 TRANSFER OPENING SHALL ALSO BE PROTECTED WITH A SMOKE
 DAMPER IN ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B
 710.7.
  
 5. PG M2.02: SUPPLY REGISTER IN OFFICE 231 IS MISSING
 CFM AND GRILL DESIGNATION. THIS INFORMATION IS REQUIRED
 TO DETERMINE DUCT SIZE AND FACILITATE PROPER BALANCING
 OF AIRFLOWS. PROVIDE MISSING INFORMATION IN ACCORDANCE
 WITH FBC-M 603.1.
  
 6. PG M2.03: KEY NOTE #6 CALLS FOR FIRE DAMPER AT NEW
 DUCT PENETRATION OF SHAFT. DUCT PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5.5.
  
 7. PG M2.03: FLOOR PLAN SHOWS TWO DUCTS FROM
 UNIDENTIFIED RTU GOING THROUGH THE 3RD FLOOR ASSEMBLY
 DOWN TO THE SECOND FLOOR. THESE PENETRATIONS SHALL BE
 PROTECTED AT THE FLOOR ASSEMBLY IN ACCORDANCE WITH
 FBC-M 607.6.
  
 8. PG M2.03: FLOOR PLAN SHOWS TWO DUCTS FROM RTU-3-1
 GOING THROUGH THE 3RD FLOOR ASSEMBLY DOWN TO THE SECOND
 FLOOR. THESE PENETRATIONS SHALL BE PROTECTED AT THE
 FLOOR ASSEMBLY IN ACCORDANCE WITH FBC-M 607.6.
  
 9. PG M2.03: KEY NOTE #8 CALLS FOR A FIRE DAMPER AT THE
 TRANSFER OPENING OF STORAGE ROOM 344. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 10. PG M2.03: KEY NOTE #7 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF FILE ROOM 312. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 11. PG M2.03: KEY NOTE #8 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF STORAGE ROOM 355. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 12. 2ND AND 3RD FLOORS: IF RATED FILE AND STORAGE ROOMS
 ON 2ND AND 3RD FLOORS ARE CONSIDERED TO BE SEPARATE
 FIRE AREAS (SEE DEFINITION OF FIRE AREA IN FBC-B
 SECTION 702), THESE ROOMS MAY NOT SHARE A COMMON PLENUM
 WITH THE ADJACENT SPACES IN ACCORDANCE WITH FBC-M 602.1
  
 13. PG M5.01: DETAIL #3 SHOWS 12 GA. WIRE HANGERS FOR
 FLEXIBLE DUCT SUPPORT. FLEXIBLE DUCT SUPPORTS SHALL BE
 MIN. 1.5 INCHES WIDE PER FBC-M 63.5.6.6.
  
 14.PG M5.01: DETAIL #3 NOTE LIMITS FLEXIBLE DUCT LENGTH
 TO 3 FEET. FLOOR PLANS SHOW FLEXIBLE DUCT EXCEEDING
 THREE FEET IN LENGTH IN MULTIPLE LOCATIONS. COORDINATE
 FLOOR PLANS AND DETAILS IN ACCORDANCE WITH FBC-B
 106.1.1 AND 106.4.
  
 15. PG M5.02: DETAIL #3 SHOWS NEW CONDENSER STAND ON
 ROOF WHILE PAGE M2.04 CALLS FOR THE EXISTING, SITE
 FABRICATED STAND TO BE USED. PROVIDE ENGINEERING DETAIL
 SHOWING HOW THE NEW CONDENSERS ARE TO BE ATTACHED TO
 THE EXISTING STAND FOR WIND RESISTANCE IN ACCORDANCE
 WITH FBC-M 301.12.
  
 16. PG M5.03: DETAIL #6, IF GOOSENECK IS UTILIZED, THE
 OPEN END SHALL BE PROTECTED WITH CORROSION-RESISTANT
 SCREEN IN ACCORDANCE WITH FBC-M 401.5.
  
 17. PG M5.03: DETAIL #1, SHOW LOCATION OF DUCT SMOKE
 DETECTORS ON FLOOR PLAN PER FBC-M 606.2.1 AND FBC-B
 106.1.1.
  
 18. PG M5.03: DETAIL #2, PROVIDE MAXIMUM HANGER SPACING
 PER FBC-M 305.1.
  
 19. PG M5.04: DETAIL #2, THIS DETAIL DOES NOT
 CORRESPOND WITH STRUCTURAL DETAIL ON PAGE S3.00. PLEASE
 COORDINATE PLANS TO SHOW COMPLIANCE WITH FBC-M 301.12.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-10-06 Cont ID  
Sent By lwagner Date 2010-10-06 Time 14:04 Rev Time 0.00
Received By lwagner Date 2010-10-06 Time 14:04 Sent To  
Notes
2010-10-06 14:13:36*******PROVISO*********
  
 LAVITORRY CLEARANCE IS 29" ABOVE FINISH FLOOR

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-08-24 Cont ID  
Sent By lwagner Date 2010-08-24 Time 14:28 Rev Time 0.00
Received By lwagner Date 2010-08-10 Time 10:23 Sent To  
Notes
2010-08-10 10:24:20PLUMBING PLAN REVIEW #1
 DENIED
  
 1. FBC 11-4.19.2
 PAGE 10-A8 - LAV CLEARANCE TO BE 29" AFF
  
 2. FBC 11-4.24
 BREAKROOM SINKS REQUIRE KNEE CLEARANCE 27" HIGH, 30"
 WIDE, AND 19" DEEP UNDER SINKS.
 SINK TO BE A MAXIMUM OF 6 1/2" DEEP.
  
 3. FBC 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 PLUMBING RISER DIAGRAMS REQUIRED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2010-10-14 Cont ID  
Sent By rregueir Date 2010-10-08 Time 15:03 Rev Time 0.00
Received By rregueir Date 2010-10-08 Time 15:03 Sent To  
Notes
2010-10-14 15:04:19RECEIVED HARD-COPY PEDDS SIGNATURE DOCS FOR ALL DESIGN
 PROFESSIONALS.

Review Stop Z ZONING
Rev No 2 Status N Date 2010-10-08 Cont ID  
Sent By lfranco Date 2010-10-08 Time 14:44 Rev Time 0.00
Received By lfranco Date 2010-10-08 Time 14:44 Sent To  
Notes
2010-10-08 14:48:35PLANNING AND ZONING: *** PROVISO: THE SCOPE OF THIS
 PERMIT IS ONLY FOR INTERIOR BUILDOUT. ALL PROPOSED
 EXTERIOR WORK NEEDS TO BE PERMITTED AND APPROVED BY THE
 PLANNING AND ZONING DEPARTMENT. FINAL SIGN-OFF FOR C.O.
 IS CONTINGENT ON APPROVAL OF ALL WORK FROM ZONING. ****
  
 COMMENTS MADE FROM ORIGINAL SUBMITTAL ON 8/9/10.
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE A COPY OF THE APPROVED INFORMAL SITE PLAN
 REVIEW (ISPR 05-09) AND PROPOSED SITE PLAN (NOT A
 PORTION OF THE SITE). IT IS NOT CLEAR WHAT SCOPE OF
 WORK IS BEING PERFORMED FOR THE EXTERIOR. CLARIFY SCOPE
 OF WORK.
  
 3. THERE IS A PATIO AREA THAT SEEMS TO BE ENCROACHING
 INTO THE REQUIRED LANDSCAPE BUFFER. A 15-FOOT WIDE
 BUFFER IS REQUIRED THROUGHOUT THE PROPERTY. PROVIDE
 INFORMATION ON PLANS REGARDING THE PAVER'S
 INSTALLATION. ARE THEY ON CONCRETE OR SAND? THE
 PERVIOUS AREA/SITE DATA SHALL BE REVIEWED AND
 CONSIDERED TO VERIFY IF THE PROPOSED WORK WILL NOT
 EXCEED THE MAXIMUM ALLOWANCE FOR IMPERVIOUS AREA. ALL
 TREES PROPOSED TO BE REMOVED NEED TO BE COORDINATED
 WITH ROBERT KUSSNER, LANDSCAPE PLANNER PRIOR TO ANY
 REMOVAL.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO DO A THOROUGH
 REVIEW. RESUBMITTAL MAY GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-29 Cont ID  
Sent By lfranco Date 2010-09-29 Time 18:57 Rev Time 0.00
Received By lfranco Date 2010-09-29 Time 18:57 Sent To  
Notes
2010-09-29 19:11:24PLANNING AND ZONING: *** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE A COPY OF THE APPROVED INFORMAL SITE PLAN
 REVIEW (ISPR 05-09) AND PROPOSED SITE PLAN (NOT A
 PORTION OF THE SITE). IT IS NOT CLEAR WHAT SCOPE OF
 WORK IS BEING PERFORMED FOR THE EXTERIOR. CLARIFY SCOPE
 OF WORK.
  
 3. THERE IS A PATIO AREA THAT SEEMS TO BE ENCROACHING
 INTO THE REQUIRED LANDSCAPE BUFFER. A 15-FOOT WIDE
 BUFFER IS REQUIRED THROUGHOUT THE PROPERTY. PROVIDE
 INFORMATION ON PLANS REGARDING THE PAVER'S
 INSTALLATION. ARE THEY ON CONCRETE OR SAND? THE
 PERVIOUS AREA/SITE DATA SHALL BE REVIEWED AND
 CONSIDERED TO VERIFY IF THE PROPOSED WORK WILL NOT
 EXCEED THE MAXIMUM ALLOWANCE FOR IMPERVIOUS AREA. ALL
 TREES PROPOSED TO BE REMOVED NEED TO BE COORDINATED
 WITH ROBERT KUSSNER, LANDSCAPE PLANNER PRIOR TO ANY
 REMOVAL.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO DO A THOROUGH
 REVIEW. RESUBMITTAL MAY GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, CONTACT ME.
  