Plan Review Details - Permit 10070772
Plan Review Stops For Permit 10070772
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By jgomez Date 2010-08-10 Time 13:25 Rev Time 0.00
Received By jgomez Date 2010-08-10 Time 13:25 Sent To  
Notes
2010-08-10 13:25:34BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE RAS 117 CALCULATIONS SUBMITTED: ENGINEER TO
 USE THE BASE SHEET FASTENER SPACING LISTED ON THE
 PRODUCT APPROVAL FOR ROOF ZONE #1 AS REQUIRED BY SEC.
 8.1 OF RAS 117.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-02 Cont ID  
Sent By jgomez Date 2010-08-02 Time 09:22 Rev Time 0.00
Received By jgomez Date 2010-08-02 Time 09:21 Sent To  
Notes
2010-08-02 09:23:01RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE WEBSITE FLAT ROOF NOA
 07-0730.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
  
 2- RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER TO REVISE ALL CALCULATIONS USING ASCE 7-05
 NOT ASCE 7-02. ASCE 7-05 IS THE CODE ADOPTED BY THE
 2007 FBC.
  
 B) ENGINEER TO REVISE THE FASTENER SPACING FOR ROOF
 ZONE #3. 3 1/2" SPACING IS NOT ALLOWED BY SEC. 8.1 OF
 RAS 117 CALCULATIONS. THE MINIMUM FASTENER SEPARATION
 SHALL NOT BE LESS THAN 4" O.C.
  
 C) ENGINEER TO REVISE FASTENER SPACING. ALL FRACTIONS
 SHALL BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER AS
 REQUIRED BY SEC. 10.4.5 OF RAS 117 CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-02 Cont ID  
Sent By jgomez Date 2010-08-02 Time 09:21 Rev Time 0.00
Received By jgomez Date 2010-08-02 Time 09:21 Sent To  
Notes
***NONE***