Plan Review Details - Permit 10070752
Plan Review Stops For Permit 10070752
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-11 Cont ID  
Sent By shill Date 2010-08-11 Time 11:06 Rev Time 0.00
Received By shill Date 2010-08-11 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-02 Cont ID  
Sent By shill Date 2010-08-02 Time 16:55 Rev Time 0.00
Received By shill Date 2010-08-02 Time 16:55 Sent To  
Notes
2010-08-02 16:56:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. WHEN RESUBMITTING, PLEASE PROVIDE TWO SETS OF THE
 INSTALLATION SCHEDULE.
  
 2. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 4. REVISE EXPOSURE CATEGORY OR PROVIDE ENGINEERING
 RATIONALE FOR EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE
 THAT THE CODE CHANGED EFFECTIVE MARCH 1, 2009.
  
 5. CONNECTION TYPE A REQUIRES CONCRETE SUBSTRATE, SEE
 PRODUCT APPROVAL.
  
 NOTE THAT IN THE FUTURE PERMITS MAY BE ISSUED WITH
 PROVISO FOR A REVISION PROVIDING INFORMATION WHICH WAS
 INCORRECT OR INCOMPLETE AT TIME OF FIRST REVIEW.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-29 Cont ID  
Sent By rmcdouga Date 2010-07-29 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2010-07-29 Time 08:11 Sent To  
Notes
2010-07-29 08:11:27SENT TO MISC 1