Plan Review Details - Permit 10070748
Plan Review Stops For Permit 10070748
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-01 Cont ID  
Sent By shill Date 2011-06-01 Time 08:43 Rev Time 0.00
Received By shill Date 2011-06-01 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-05-06 Cont ID  
Sent By shill Date 2011-05-06 Time 16:23 Rev Time 0.00
Received By shill Date 2011-05-06 Time 16:23 Sent To  
Notes
2011-05-06 16:53:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 2ND REVIEW
  
 1. OK.
  
 2. OPENING 10, 139" SPAN, REQUIRES USE OF 12' ROW, 10"
 SPACING DOES NOT COMPLY. CHECK ALL.
  
 3. SUBSTRATE SPECIFIED ON INSTALLATION SCHEDULE IS
 CONCRETE BLOCK, BUT CONNECTION TYPE A REQUIRES A
 CONCRETE SUBSTRATE. PLEASE REVISE INSTALLATION SCHEDULE
  
 2ND REVIEW, INSTALLATION SCHEDULE SUBSTRATE STATES:
 "CONC BLOCK." DOES THIS MEAN THAT ALL OPENINGS HAVE A
 CONCRETE BLOCK SUBSTRATE, OR THAT THIS IS CONCRETE AT
 THE TOP, BLOCK ON THE BOTTOM?
  
 4. THE REVISED INSTALLATION SCHEDULE HAS CHANGED EDGE
 DISTANCE FROM 3" TO 2". ANCHOR SPACING, 10", NO LONGER
 COMPLIES. PLEASE APPLY FACTOR .35 PER CHART ON SHEET
 14.
  
 ALSO PLEASE NOTE, I RECEIVED CLARIFICATION FROM WALTER
 TILLET, PE. A 3" EDGE DISTANCE ALSO REQUIRES A .35
 FACTOR. ONLY 3 1/2" EDGE DISTANCE FOR TAPCONS CAN
 UTILIZE THE SPACING IN THE CHARTS WITHOUT A .35 FACTOR.
  
  
 5. SEE ANCHOR CHART FOR CONNECTION TYPE D. SOMEONE
 CIRCLED 10" ON THE PRODUCCT APPROVAL, BUT THAT IS THE
 ROW FOR ALL POINTS SOLID SET. THE TAPCON ROW REQUIRES
 4" SPACING. PLEASE SEE THE LEGEND AT TOP LEFT CORNER OF
 SHEET 13.
  
 6. AS DISCUSSED, I PULLED TWO PLANS AT RANDOM TO
 RE-REVIEW INSTALLATION SCHEDULES ON ISSUED PERMITS IN
 ORDER TO DETERMINE WHY CONTRACTOR WAS ABLE TO OBTAIN
 PERMITS IN THE PAST BUT IS HAVING DIFFICULTIES AT THIS
 TIME. I FOUND THE FOLLOWING:
  
 10050282 WAS SUBMITTED INCORRECTLY BY CONTRACTOR. I HAD
 A DISCUSSION WITH THE CONTRACTOR, EXPLAINED ERRORS, AND
 REDLINED.
  
 08030066 WAS SUBMITTED WITHOUT AN INSTALLATION
 SCHEDULE, BUT ALL INFORMATION WAS PROVIDED IN AN
 ALTERNATE FORMAT. THE WOMAN WHO DID THE PAPERWORK AT
 THAT TIME DEVELOPED A FORM WHICH SHE TITLED "DRILLING
 REQUIREMENT" AFTER SHE AND I HAD NUMEROUS DISCUSSIONS
 REGARDING THE INFORMATION REQUIRED FOR PERMITTING.
  
 PLEASE BE ADVISED THAT IN THE FUTURE PERMITS WITH
 INCORRECT INFORMATION SUBMITTED MAY BE ISSUED WITH
 PROVISO THAT CORRECTED (CODE COMPLIANT) PLANS BE
 SUBMITTED AS A REVISION (WITH REVISION FEES).
  
 WHEN RESUBMITTING, PLEASE PAY PLAN REVIEW FEE. THIS
 PROJECT WAS PULLED FROM REVIEW BECAUSE PLAN REVIEW FEES
 WERE NOT PAID AT TIME OF SUBMITTAL AS REQUIRED. DUE TO
 THE EXTENUATING CIRCUMSTANCES WITH THE PERMIT RUNNER,
 REVIEW HAS BEEN PERFORMED (CONTRARY TO DEPARTMENT
 POLICY) AS A COURTESY TO THE CONTRACTOR WHO APPEARS TO
 BE A VICTIM. HOWEVER, PLEASE PAY PLAN REVIEW FEE WHEN
 RESUBMITTING PLAN IN ORDER TO BE IN COMPLIANCE WITH
 DEPARTMENT REQUIREMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-13 Cont ID  
Sent By shill Date 2010-08-13 Time 13:33 Rev Time 0.00
Received By shill Date 2010-08-13 Time 13:33 Sent To  
Notes
2010-08-13 14:17:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE TWO COMPLETE SETS OF PLANS, ONLY ONE
 INSTALLATION SCHEDULE PROVIDED.
  
 2. OPENING 10, 139" SPAN, REQUIRES USE OF 12' ROW, 10"
 SPACING DOES NOT COMPLY. CHECK ALL.
  
 3. SUBSTRATE SPECIFIED ON INSTALLATION SCHEDULE IS
 CONCRETE BLOCK, BUT CONNECTION TYPE A REQUIRES A
 CONCRETE SUBSTRATE. PLEASE REVISE INSTALLATION SCHEDULE
  
 PLEASE BE ADVISED THAT IN THE FUTURE PERMITS WITH
 INCORRECT INFORMATION SUBMITTED MAY BE ISSUED WITH
 PROVISO THAT CORRECTED (CODE COMPLIANT) PLANS BE
 SUBMITTED AS A REVISION
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-06 Cont ID  
Sent By shill Date 2011-05-06 Time 16:53 Rev Time 0.00
Received By shill Date 2011-03-28 Time 14:34 Sent To  
Notes
2011-03-28 14:34:37SENT TO SAMANTHA'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-13 Cont ID  
Sent By shill Date 2010-08-13 Time 14:17 Rev Time 0.00
Received By shill Date 2010-07-28 Time 11:20 Sent To  
Notes
2010-07-28 11:21:11SENT TO MISC. 1 BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved