Plan Review Details - Permit 10070689
Plan Review Stops For Permit 10070689
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-13 Cont ID  
Sent By rmcdouga Date 2010-09-13 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2010-09-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-08 Cont ID  
Sent By astelly Date 2010-08-05 Time 21:28 Rev Time 0.00
Received By rmcdouga Date 2010-09-07 Time 16:46 Sent To  
Notes
2010-09-08 08:02:152007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED (FL11963)
 ARE NOT THE ONES SPECIFIED ON THE INSTALLATION SCHEDULE
 (FL11398). SUBMIT MATCHING INFORMATION. PER THE TABLE
 ON FL11398, THE ANCHOR SPACING OF 18" FOR MOUNT TYPE C1
 AND C4 IS ONLY GOOD FOR 33.0 PSF. THE OPENING PRESSURES
 ARE HIGHER THAN THAT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-08 Cont ID  
Sent By rmcdouga Date 2010-09-08 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2010-07-28 Time 11:22 Sent To  
Notes
2010-08-11 10:03:40TO MISC 2
  
2010-07-28 11:23:33SENT TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-05 Cont ID  
Sent By astelly Date 2010-08-05 Time 21:28 Rev Time 0.00
Received By astelly Date 2010-08-05 Time 21:28 Sent To B
Notes
***NONE***