Plan Review Details - Permit 10070569
Plan Review Stops For Permit 10070569
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-01 Cont ID  
Sent By hmoser Date 2011-03-01 Time 10:03 Rev Time 0.00
Received By hmoser Date 2011-02-24 Time 09:28 Sent To  
Notes
2011-02-24 09:28:43INCOMING SENT TO H. M. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-03-01 Cont ID  
Sent By hmoser Date 2011-03-01 Time 10:03 Rev Time 0.00
Received By hmoser Date 2010-07-28 Time 10:09 Sent To  
Notes
2010-07-28 10:10:21UNDER 5 K MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-03-01 Cont ID  
Sent By hmoser Date 2011-03-01 Time 09:22 Rev Time 0.00
Received By hmoser Date 2011-03-01 Time 09:22 Sent To  
Notes
2011-03-01 10:03:05PASS PROVISO
 NEED A REVISER PLAN WITH FRESH AIR CALCULATIONS BY THE
 ENGINEER .PER TABLE 403.3 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-02-11 Cont ID  
Sent By hmoser Date 2011-02-11 Time 09:14 Rev Time 0.00
Received By hmoser Date 2011-02-11 Time 09:13 Sent To  
Notes
2011-02-11 09:20:49PLANS DENIED
 PLEASE PROVIDE A COMPLETE SET OF MECHANICAL PLANS FOR
 REVIEW.
 REFER TO SECTION 606.2.1 SUPPLY AIR AND 606.3
 INSTALLATION 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-04 Cont ID  
Sent By hmoser Date 2010-08-04 Time 11:31 Rev Time 0.00
Received By hmoser Date 2010-08-04 Time 11:31 Sent To  
Notes
2010-08-04 11:37:16PLAN DENIED
 PLEASE REFER TO TABLE 403.3 NAIL SALON 2007 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732