Plan Review Details - Permit 10070561
Plan Review Stops For Permit 10070561
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-06-28 Cont ID  
Sent By jwitmer Date 2011-06-28 Time 13:05 Rev Time 1.10
Received By jwitmer Date 2011-06-28 Time 12:34 Sent To  
Notes
2011-06-28 12:37:21 
 BUILDING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 1) CONTRACTOR TO SIGN ONTO PERMIT, FRONT COUNTER TO
 VERIFY LICENSURE.
  
 2) AT THIS TIME THE FUTURE CONTRACTOR HAS NOT SUBMITTED
 PRODUCT APPROVALS. IF PRODUCT TESTING APPROVALS ARE NOT
 SUBMITTED BEFORE ISSUANCE THEN THE
 SUBMISSION OF TESTING REPORTS WILL CONSTITUTE A
 REVISION AND ASSOCIATED REVIEWS AND FEES.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 2A) SINGLE HUNG WINDOWS
 2B) CASEMENT WINDOWS
 2C) EXTERIOR DOORS
 2D) ROOFING ASSEMBLIES
 2E) STORM SHUTTERS, IF GLAZED OPENINGS ARE NOT LARGE
 MISSILE RESISTANT TESTED
 2F) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) GAS PERMIT WILL BE REQUIRED FOR THE NEW GAS INSTANT
 HOT WATER HEATER, NOT PART OF THIS REVIEW.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-04-18 Cont ID  
Sent By jwitmer Date 2011-04-18 Time 09:38 Rev Time 0.55
Received By jwitmer Date 2011-04-18 Time 09:38 Sent To  
Notes
2011-04-18 09:46:17BUILDING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
  
 1-3) COMPLIED.
  
  
 4) 106.3.3 THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) COMPLIED.WINDOWS/ SINGLE HUNG - RULE 9B-72(31) (B)
 NOA 080820.14
 WINDOWS/ CASEMENT RULE 9B-72(31) (B) NO APPROVALS WERE
 SUBMITTED
  
 5B) COMPLIED.EXTERIOR DOORS RULE 9B-72(31) (A) NEW RULE
 9N-3 FL 4334.1
 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D) NEW RULE 9N-3 NO
 APPROVALS WERE SUBMITTEDCAN BE ISSUED UNDER A SEPERATE
 ROOFING PERMIT.
 5D) NOT REQUIRED
  
 PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE
 PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS
 CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT
 APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE
 CONSIDERED A REVISION WITH FURTHER REVIEW AND
 ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON
 SHEET 5.1 ARE CORRECT.
  
 6-8) COMPLIED.
  
 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 10) IMPACT FEES : COMPLIED.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-03-30 Cont ID  
Sent By jwitmer Date 2011-03-30 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2011-03-30 Time 08:35 Sent To  
Notes
2011-03-30 08:39:01BUILDING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
 1-3) COMPLIED.
  
  
 4) NO PRODUCT APPROVALS WERE SUBMITTED. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) WINDOWS RULE 9B-72(31) (B)
 SINGLE HUNG
 CASEMENT
 5B) EXTERIOR DOORS RULE 9B-72(31) (A) NEW RULE 9N-3
 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D) NEW RULE 9N-3
 5D) STORM SHUTTERS/ PANELS 9B-72(31)(E) NEW RULE 9N-3
  
 PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE
 PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS
 CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT
 APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE
 CONSIDERED A REVISION WITH FURTHER REVIEW AND
 ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON
 SHEET 5.1 ARE CORRECT.
  
 6-8) COMPLIED.
  
 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 10:50 Rev Time 1.00
Received By jwitmer Date 2011-02-03 Time 09:40 Sent To  
Notes
2011-02-03 11:03:12BUILDING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE SHEET 1.1 INDICATES A TWO STORY TO BE REMODELED
 THERE ARE NO OTHER REFERENCES IN EITHER THIS PLAN NOR
 PERMIT APPLICATION AND WILL NOT BE PART OF WORK TO BE
 COMPLETED UNDER THIS PERMIT .
  
 1) EITHER A CONTRACTOR OR OWNER/ BUILDER WILL BE
 REQUIRED TO SIGN ON TO THE PERMIT APPLICATION.
  
 2) COMPLIED, TWO SETS OF PLANS.
  
 3) SEMI-COMPLIED. THE PLANS ARE DESIGNED BY RICHARD
 BOYETTE A FL PE, PE# 42485, PLANS ARE NOT SIGNED NOR
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
  
  
 4) NO PRODUCT APPROVALS WERE SUBMITTED. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) WINDOWS RULE 9B-72(31) (B)
 SINGLE HUNG
 CASEMENT
 5B) EXTERIOR DOORS RULE 9B-72(31) (A) NEW RULE 9N-3
 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D) NEW RULE 9N-3
 5D) STORM SHUTTERS/ PANELS 9B-72(31)(E) NEW RULE 9N-3
  
 PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE
 PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS
 CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT
 APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE
 CONSIDERED A REVISION WITH FURTHER REVIEW AND
 ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON
 SHEET 5.1 ARE CORRECT.
  
 6) 2ND REQUEST, SHEET 3.1 IN THE DESIGN PARAMETERS AND
 CODE REFERENCES, BOTH MAKE REFERENCES TO THE 2004 FBC,
 PLEASE REVISE TO THE 2007 FBC WITH 2009 SUPPLEMENTS.
 PLEASE ALSO INCLUDE UNDER THE 2007 EXISTING BUILDING
 CODE COMPLIANCE WITH SECTION 401.4 A DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 7-8) COMPLIED.
  
 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By jwitmer Date 2010-08-12 Time 10:59 Rev Time 3.30
Received By jwitmer Date 2010-08-12 Time 10:59 Sent To  
Notes
2010-08-12 11:00:07 
 BUILDING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE SHEET 1.1 INDICATES A TWO STORY TO BE REMODELED
 THERE ARE NO OTHER REFERENCES IN EITHER THIS PLAN NOR
 PERMIT APPLICATION AND WILL NOT BE PART OF WORK TO BE
 COMPLETED UNDER THIS PERMIT .
  
 1) EITHER A CONTRACTOR OR OWNER/ BUILDER WILL BE
 REQUIRED TO SIGN ON TO THE PERMIT APPLICATION.
  
 2) NOTE, ONLY ONE SET OF PLANS WERE SUBMITTED TO REVIEW
 FOR CODE COMPLIANCE. BEFORE A PERMIT WILL BE ISSUED TWO
 SETS OF PLANS AND ASSOCIATED DOCUMENTS WILL NEED TO BE
 SUPPLIED FOR REVIEW AND APPROVAL STAMPING. ONE FOR THE
 FIELD INSPECTORS AND ONE FOR RECORD RETENTION. 106.3.1/
 2007 FBC-B ADMINISTRATIVE CODE.
  
 3) PLEASE PROVIDE ON THE PLANS WHO IS THE DESIGNER OF
 RECORD, SINCE THIS IS A SINGLE FAMILY RESIDENCE IT DOES
 NOT NEED TO BE A ARCHITECT OR ENGINEER WHO ARE COVERED
 UNDER FL S 481 AND 471. FBC-B 106.1* DESIGNERS NAME AND
 CONTACT NUMBER TO BE ABLE TO CONTACT THE DESIGNER IN
 CASE OF QUESTIONS.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) WINDOWS RULE 9B-72(31) (B)
 SINGLE HUNG
 CASEMENT
 5B) EXTERIOR DOORS RULE 9B-72(31) (A)
 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D)
  
 PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE
 PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS
 CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT
 APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE
 CONSIDERED A REVISION WITH FURTHER REVIEW AND
 ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON
 SHEET 5.1 ARE CORRECT.
  
 6) SHEET 3.1 IN THE DESIGN PARAMETERS AND CODE
 REFERENCES, BOTH MAKE REFERENCES TO THE 2004 FBC,
 PLEASE REVISE TO THE 2007 FBC WITH 2009 SUPPLEMENTS.
 PLEASE ALSO INCLUDE UNDER THE 2007 EXISTING BUILDING
 CODE COMPLIANCE WITH SECTION 401.4 A DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 7) THE FLOOR PLAN SHEET 3.1 INDICATES A NEWLY REMODELED
 RESTROOM WITH THE SHOWER NEXT TO A SINGLE HUNG WINDOW
 PLEASE REVIEW R308.4(9) HAZARDOUS LOCATIONS.
  
 8) THE PLANS INDICATE IN SECTION 3/6.1 A TYPICAL GABLE
 WALL PLEASE REVIEW R602.1.2(1.1) FOR REQUIRED FIRE
 BLOCKING SEPARATING VERTICALLY AT THE CEILING.
  
 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-23 Cont ID  
Sent By rlecky Date 2011-03-23 Time 09:00 Rev Time 0.00
Received By rlecky Date 2011-03-23 Time 09:00 Sent To  
Notes
2011-03-23 09:03:29PROVISO ON PLANS:
  
 A CARBON DIOXIDE ALARM IS REQUIRED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE SECTION R313.2.1 FOR
 RESIDENTIAL BUILDINGS UNDER GOING REPAIRS AND
 ALTERATIONS.
  
 NEW GENERAL PURPOSE RECEPTACLES MUST BE PROTECTED WITH
 AFCI'S. NEC 210.12(B)
  
 BATHROOM RECEPTACLES MUST HAVE GFCI PROTECTION. NEC
 210-8 (A)
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-10 Cont ID  
Sent By shill Date 2010-08-10 Time 09:43 Rev Time 0.00
Received By shill Date 2010-08-10 Time 09:43 Sent To  
Notes
2010-08-10 09:43:55OK PER JOHN DICKINSON (CONTRACT REVIEWER)
 PX3182
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2011-02-03 Time 11:07 Sent To  
Notes
2011-02-03 11:09:15A SEPERATE GAS PERMIT WILL BE REQUIRED NOT TO BE
 INCLUDED UNDER THE MASTER.
  
 REQUIRED INFORMATION FOR GAS PERMIT:
  
 1) PLEASE PROVIDE THE DEVELOPED LENGTH OF THE GAS
 PIPING FROM THE METER TO THE LAST APPLIANCE, BTU OF
 EACH APPLIANCE.
  
 1A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
 SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER),
 TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER FBC-2007 FUEL
 GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 1B) 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL TUBING FOR EACH
 PIPE SIZE IF BEING USED.
  
 1C) NEW GAS INSTA-HOT WATER HEATER PLEASE PROVIDE
 MANUFACTURERS SPEC FOR BTU, AND APPROVAL FOR EXTERIOR
 LOCATIONS. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2007 FUEL GAS CODE SEC 402.2 &
 RESIDENTIAL CODE SEC. G2413.2.
  
 1D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8 THRU 402.6.1 AND
 TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 1E) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2004
 FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By jwitmer Date 2010-08-12 Time 11:23 Rev Time 0.33
Received By jwitmer Date 2010-08-12 Time 11:23 Sent To  
Notes
2010-08-12 11:37:25GAS PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- GAS
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) PLEASE PROVIDE THE DEVELOPED LENGTH OF THE GAS
 PIPING FROM THE METER TO THE LAST APPLIANCE, BTU OF
 EACH APPLIANCE.
  
 1A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
 SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER),
 TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER FBC-2007 FUEL
 GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 1B) 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL TUBING FOR EACH
 PIPE SIZE IF BEING USED.
  
 1C) NEW GAS INSTA-HOT WATER HEATER PLEASE PROVIDE
 MANUFACTURERS SPEC FOR BTU, AND APPROVAL FOR EXTERIOR
 LOCATIONS. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2007 FUEL GAS CODE SEC 402.2 &
 RESIDENTIAL CODE SEC. G2413.2.
  
 1D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8 THRU 402.6.1 AND
 TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 1E) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2004
 FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
  
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2011-06-20 Cont ID  
Sent By fmittner Date 2011-06-20 Time 14:08 Rev Time 0.00
Received By fmittner Date 2011-06-20 Time 14:08 Sent To  
Notes
2011-06-20 14:09:08NO VINYL WINDOWS. MUST BE PGT AS SPEC'D ON PLANS OR
 APPROVED BY HISTORIC PRESERVATION DIVISION STAFF/BOARD.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2011-04-04 Cont ID  
Sent By fmittner Date 2011-04-04 Time 10:39 Rev Time 0.00
Received By fmittner Date 2011-04-04 Time 10:39 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-01-28 Cont ID  
Sent By fmittner Date 2011-01-28 Time 17:17 Rev Time 0.00
Received By fmittner Date 2011-01-28 Time 17:17 Sent To  
Notes
2011-01-28 17:18:03HISTORIC APPROVED 1-28-11. BROUGHT PLANS TO LUIS M.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2010-08-18 Cont ID  
Sent By fmittner Date 2010-08-18 Time 13:02 Rev Time 0.00
Received By fmittner Date 2010-08-18 Time 13:02 Sent To  
Notes
2010-08-18 13:08:45PLANS FAILED BECAUSE NORTH ELEVATION WINDOWS EXTEND
 BELOW LOCATION OF ORIGINAL WINDOW SIZE PER HISTORIC
 PRESERVATION BOARD APPROVAL ON 9/23/08 FOR CASE 08-40.
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2011-06-28 Cont ID  
Sent By jwitmer Date 2011-06-28 Time 12:36 Rev Time 0.00
Received By jwitmer Date 2011-06-07 Time 14:11 Sent To  
Notes
2011-06-07 14:12:02R24

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-06-28 Cont ID  
Sent By jwitmer Date 2011-04-18 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2011-04-14 Time 16:45 Sent To  
Notes
2011-04-14 16:45:24GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-04-14 Cont ID  
Sent By lmartine Date 2011-04-08 Time 16:44 Rev Time 0.00
Received By lmartine Date 2011-03-21 Time 11:42 Sent To  
Notes
2011-03-21 11:42:42SENT TO R21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-02 Cont ID  
Sent By lmartine Date 2010-12-21 Time 13:44 Rev Time 0.00
Received By lmartine Date 2010-12-21 Time 13:44 Sent To  
Notes
2011-02-02 13:48:59RESUBMITTAL WAS INCORRECTLY SUBMITTED AS A NEW
 APPLICATION #10120533. THAT # HAS SINCE BEEN VOIDED AND
 THE RESUBMIITAL WILL CONTINUE UNDER THIS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-02 Cont ID  
Sent By lmartine Date 2010-08-18 Time 13:43 Rev Time 0.00
Received By lmartine Date 2010-07-28 Time 11:43 Sent To  
Notes
2010-07-28 11:43:38R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-04-08 Cont ID  
Sent By rlecky Date 2011-04-08 Time 12:27 Rev Time 0.00
Received By rlecky Date 2011-04-08 Time 12:27 Sent To  
Notes
2011-04-08 12:31:43FEES PAID PBC RECEIPT # 2011-0408-99 NEED PLAN STAMPED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By jwitmer Date 2010-08-12 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2010-08-12 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2011-06-28 Cont ID  
Sent By jwitmer Date 2011-06-28 Time 12:32 Rev Time 0.35
Received By jwitmer Date 2011-06-28 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2011-03-30 Cont ID  
Sent By jwitmer Date 2011-03-30 Time 08:41 Rev Time 0.25
Received By jwitmer Date 2011-03-30 Time 08:41 Sent To  
Notes
2011-03-30 08:42:10MECHANICAL PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 2) SHEET 6.1 MECHANICAL SHEET IS MISSING THE A/C SYSTEM
 DESIGN DATA, BLANK!
  
  
 JAMES A. WITMER C.B.O.
 SFP-100
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 11:11 Rev Time 0.35
Received By jwitmer Date 2011-02-03 Time 11:11 Sent To  
Notes
2011-02-03 11:15:58MECHANICAL PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 2) SHEET 6.1 MECHANICAL SHEET IS MISSING THE A/C SYSTEM
 DESIGN DATA, BLANK!
  
  
 JAMES A. WITMER C.B.O.
 SFP-100
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By jwitmer Date 2010-08-12 Time 11:09 Rev Time 0.50
Received By jwitmer Date 2010-08-12 Time 11:09 Sent To  
Notes
2010-08-12 11:23:18 
  
  
  
  
 MECHANICAL PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 2) PROVISO: M1602.4 BALANCED RETURN AIR. RESTRICTED
 RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED
 IN CENTRAL ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR
 FLOW TO THE RETURN GRILL OR WHEN CEILING SPACES ARE
 USED AS RETURN PLENUMS AND FIRE WALLS RESTRICT AIR
 MOVEMENT FROM ONE PORTION OF THE RETURN PLENUM TO
 ANOTHER. PROVISIONS SHALL BE MADE IN RESIDENTIAL
 BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE
 DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PA) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE WALLS
 IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH
 WC (2.5 PA) BY PROVIDING AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE
 LOW ZONE.
  
 EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-03-30 Cont ID  
Sent By jwitmer Date 2011-03-30 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2011-03-30 Time 08:39 Sent To  
Notes
2011-03-30 08:40:34GAS WILL REQUIRE A SEPERATE PERMIT, REVIEW AND
 ASSOCIATED FEES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-03 Cont ID  
Sent By jwitmer Date 2011-02-03 Time 11:18 Rev Time 0.25
Received By jwitmer Date 2011-02-03 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-08-16 Cont ID  
Sent By jwitmer Date 2010-08-16 Time 10:56 Rev Time 0.88
Received By jwitmer Date 2010-08-12 Time 11:37 Sent To  
Notes
2010-08-16 11:00:32PLUMBING PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE PLUMBING= 2007 FLORIDA BUILDING CODE-
 PLUMBING
 W/ 2009 FBC SUPPLEMENTS * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 6.1 ISOMETRIC PLAN THE NEW BATHROOM INDICATES
 A WATERCLOSET AND SHOWER CONNECTED TO THE SAME STACK.
 PLEASE REVIEW P3107.3 CONNECTIONS AT DIFFERENT LEVEL.
 THE UPPER FIXTURE SHALL NOT BE A WATER CLOSET.
 CURRENTLY SHOWN THE SHOWER IS NOT VENTED.
  
 2) THE KITCHEN THE PLANS INDICATE WINDOWS REQUIRING THE
 VENT TO BE ROUTED PAST THE FRAMED WINDOW OPENING.
 R602.2.7 DRILLING AND NOTCHING???STUDS. DRILLING AND
 NOTCHING OF STUDS SHALL BE IN ACCORDANCE WITH THE
 FOLLOWING:
  
 1.NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING
 PARTITION MAY BE CUT OR NOTCHED TO A DEPTH NOT
 EXCEEDING 25 PERCENT OF ITS WIDTH. STUDS IN NONBEARING
 PARTITIONS MAY BE NOTCHED
 TO A DEPTH NOT TO EXCEED 40 PERCENT OF A SINGLE STUD
 WIDTH.
  
 2. DRILLING. ANY STUD MAY BE BORED OR DRILLED, PROVIDED
 THAT THE DIAMETER OF THE RESULTING HOLE IS NO MORE THAN
 60 PERCENT OF THE STUD WIDTH, THE EDGE OF THE HOLE IS
 NO MORE THAN 5/8
 INCH (16 MM) TO THE EDGE OF THE STUD, AND THE HOLE IS
 NOT LOCATED IN THE SAME SECTION AS A CUT OR NOTCH.
 STUDS LOCATED IN EXTERIOR WALLS OR BEARING PARTITIONS
 DRILLED OVER 40 PERCENT
 AND UP TO 60 PERCENT SHALL ALSO BE DOUBLED WITH NO MORE
 THAN TWO SUCCESSIVE DOUBLED STUDS BORED. SEE FIGURES
 R602.2.7(1) AND R602.2.7(2).
  
 PLEASE NOTE AN AIR ADMITTANCE DEVICE MAY BE USED
 INSTEAD OF THE 2 INCH VENT.
  
 3) WITHIN THE NEW HALF BATH THE SANITARY VENT WILL
 EITHER CUT OR NOTCH THE TOP AND BOTTOM PLATE PLEASE
 REVIEW SECTION: R602.2.7.1 DRILLING AND NOTCHING OF TOP
 PLATE. WHEN PIPING OR DUCTWORK IS PLACED IN OR PARTLY
 IN AN EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL,
 NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP
 PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A
 GALVANIZED METAL TIE OF NOT LESS THAN 0.054 INCHES
 THICK (1.37 MM) (16 GA) AND 11/2 INCHES (38 MM) WIDE
 SHALL BE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE
 OF THE OPENING WITH NOT LESS THAN EIGHT 10D (0.148 INCH
 DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 11/2 INCHES
 (38 MM) AT EACH SIDE OR EQUIVALENT. SEE FIGURE
 R602.2.7(1).
 EXCEPTION: WHEN THE ENTIRE SIDE OF THE WALL WITH THE
 NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL
 SHEATHING.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2011-06-27 Cont ID  
Sent By jroach Date 2011-06-27 Time 17:09 Rev Time 0.00
Received By jroach Date 2011-06-27 Time 17:09 Sent To  
Notes
2011-06-27 17:09:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.27.2011
 PERMIT NO.: 10070561
 ADDRESS: 716 NEW YORK STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATIONS AND ADDITIONS TO EXISTING
 SINGLE FAMILY HOUSE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. AS THE EXISTING STRUCTURE DOES NOT MEET THE CURRENT
 SETBACK REQUIREMENTS, IF ANY REBUILDING OF THE EXTERIOR
 WALLS, ETC. IS DEEMED NECESSARY OUTSIDE OF THE APPROVED
 SCOPE OF THIS PERMIT, A REVISION TO THE PERMIT WILL BE
 REQUIRED, AND MAY REQUIRE APPROVAL OF A VARIANCE BY THE
 ZONING BOARD OF APPEALS (ZBA)!
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 3 Status F Date 2011-04-04 Cont ID  
Sent By jroach Date 2011-04-04 Time 18:27 Rev Time 0.00
Received By jroach Date 2011-04-04 Time 18:27 Sent To  
Notes
2011-04-04 18:36:29ZONING PLAN REVIEW
  
 PERMIT NO.: 10070561
 ADDRESS: 716 NEW YORK STREET
 CONTRACTOR/CONTACT: PENE LATHAM
 TELEPHONE NO.: 561.832.1500
 SCOPE OF REVIEW: REMODEL OF MAIN HOUSE
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 IMPORTANT - AS THE PROPOSED STRUCTURE DOES NOT MEET THE
 CURRENT SETBACK REQUIREMENTS, A NOTE WILL BE ADDED TO
 THE PERMIT INDICATING THAT IF ANY REBUILDING OF THE
 EXTERIOR WALLS, ETC. IS DEEMED NECESSARY, A REVISION TO
 THE PERMIT WILL BE REQUIRED, AND MAY REQUIRE THE
 APPROVAL OF A VARIANCE FROM THE ZONING BOARD OF
 APPEALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2011-02-07 Cont ID  
Sent By jroach Date 2011-02-07 Time 10:54 Rev Time 0.00
Received By jroach Date 2011-02-07 Time 10:54 Sent To  
Notes
2011-02-07 11:03:43ZONING PLAN REVIEW
  
 PERMIT NO.: 10070561
 ADDRESS: 716 NEW YORK STREET
 CONTRACTOR/CONTACT: PENE LATHAM
 TELEPHONE NO.: 561.832.1500
 SCOPE OF REVIEW: REMODEL OF MAIN HOUSE
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-18 Cont ID  
Sent By jroach Date 2010-08-18 Time 10:15 Rev Time 0.00
Received By jroach Date 2010-08-18 Time 10:15 Sent To  
Notes
2010-08-18 10:15:33ZONING PLAN REVIEW
  
 PERMIT NO.: 10070561
 ADDRESS: 716 NEW YORK STREET
 CONTRACTOR/CONTACT: PENE LATHAM
 TELEPHONE NO.: 561.832.1500
 SCOPE OF REVIEW: REMODEL OF MAIN HOUSE
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) SETS OF ALL PLANS SHALL BE PROVIDED.
  
 2) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3) PURSUANT TO SECTION 94-305(B)(2) OF THE CITY???S
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), THE
 ROOF OVERHANG OF THE PROPOSED BATHROOM ADDITION SHALL
 NOT EXTEND MORE THAN THREE (3) FEET INTO THE REQUIRED
 SETBACK.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved