Plan Review Stops For Permit 10070522
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-07-27 Cont ID  
Sent By jwitmer Date 2010-07-27 Time 11:18 Rev Time 0.77
Received By jwitmer Date 2010-07-27 Time 10:45 Sent To  
Notes
2010-07-27 11:37:06BUILDING PLAN REVIEW
 PERMIT: 10070522
 ADD: 1400 NORTHPOINT, SUITE P
 CONT: P & T CONSTRUCTION
 TEL: (561)833-0614
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEETS A1.2 & A4.2 THE NEW EXTERIOR DOOR NEEDS TO
 COMPLY WITH 11-4.13.6. A 18 INCH CLEAR SPACE LATCH SIDE
 OF DOOR. MANEUVERING CLEARANCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 25. THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES
 SHALL BE LEVEL AND CLEAR.
  
 2) A1.2 & A4.2 NEW EXTERIOR DOOR PROVIDE NEW WALL /
 COLUMN DETAIL, PRODUCT APPROVAL FOR NEW EXTERIOR DOOR &
 WIND DESIGN CRITERIA INCLUDING PRESSURES.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-09 Cont ID  
Sent By lmartine Date 2010-08-09 Time 15:56 Rev Time 0.00
Received By lmartine Date 2010-08-09 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-30 Cont ID  
Sent By mcarsill Date 2010-08-30 Time 14:06 Rev Time 0.00
Received By mcarsill Date 2010-08-30 Time 14:06 Sent To  
Notes
2010-08-30 14:08:421400 NORTHPOINT PARKWAY
 PERMIT NUMBER 10070522
  
  
 A RESPONSE LETTER AND DRAWINGS FOR FIRE SPRINKLER AND
 FIRE ALARM SYSTEM WORK SUBMITTED BY JEFF CONTE OF P & T
 CONSTRUCTION.
  
 SEPARATE PLANS AND PERMITS EXPECTED FOR FIRE SPRINKLER
 AND FIRE ALARM SYSTEMS.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By mcarsill Date 2010-07-29 Time 15:23 Rev Time 0.00
Received By mcarsill Date 2010-07-29 Time 15:01 Sent To  
Notes
2010-07-29 15:22:561400 NORTHPOINT PARKWAY, SUITE P
 PERMIT NUMBER 10070522
 TENANT IMPROVEMENT BUILD-OUT OF APPROXIMATELY 7,000
 SQUARE FEET
  
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODELING.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW LOW
 VOLTAGE WORK.
  
 4. PLEASE ENSURE THAT ALL EXISTING EMERGENCY LIGHTS AND
 EXIT SIGNS AND ILLUMINATED EXIT SIGNS ARE FUNCTIONING
 PROPERLY.
  
 5. ELECTRICAL INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 6. MORE DETAILS NEEDED ON SECURITY SYSTEM AND DEVICES.
 LOCKING DEVICES SHALL NOT INTERFERE WITH ANY REQUIRED
 EXIT ACCESS OR EXIT DISCHARGE.
  
 7. DOES ANY FIRE ALARM EQUIPMENT EXIST?
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-25 Cont ID  
Sent By lmartine Date 2010-08-25 Time 12:36 Rev Time 0.00
Received By lmartine Date 2010-08-25 Time 12:36 Sent To  
Notes
2010-08-25 12:36:56IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-17 Cont ID  
Sent By hmoser Date 2010-08-17 Time 12:29 Rev Time 0.00
Received By hmoser Date 2010-07-23 Time 10:12 Sent To  
Notes
2010-07-23 10:13:58B--18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-08-17 Cont ID  
Sent By hmoser Date 2010-08-17 Time 12:29 Rev Time 0.00
Received By hmoser Date 2010-08-17 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-28 Cont ID  
Sent By lwagner Date 2010-07-28 Time 12:50 Rev Time 0.00
Received By lwagner Date 2010-07-28 Time 12:22 Sent To  
Notes
2010-07-28 12:51:31*****NOTE*****
  
 CONDENSATE SHALL NOT BE CONNECTED TO ANY VENT.
 CONDENSATE SHALL BE RUN TO AN APPROVED PLACE OF
 DISPOSAL.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-07-29 Cont ID  
Sent By eschneid Date 2010-07-29 Time 08:40 Rev Time 0.25
Received By eschneid Date 2010-07-29 Time 08:40 Sent To  
Notes
2010-07-29 08:41:37INTERIOR WORK ONLY. PERMIT VALUE FOR PAST 12 MONTHS
 UNDER 50% OF BUILDING VALUE.