Plan Review Details - Permit 10070434
Plan Review Stops For Permit 10070434
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-07 Cont ID  
Sent By jwitmer Date 2010-09-07 Time 11:25 Rev Time 2.20
Received By jwitmer Date 2010-09-07 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-27 Cont ID  
Sent By jwitmer Date 2010-07-27 Time 08:14 Rev Time 1.75
Received By jwitmer Date 2010-07-26 Time 14:41 Sent To  
Notes
2010-07-27 10:08:59BUILDING PLAN REVIEW
 PERMIT: 10070434
 ADD: 600 VILLAGE BLVD
 CONT: 3-D HOMES INC
 TEL: (561)662-9327
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) THE LIFE SAFETY PLAN 1.8A PLEASE IDENTIFY THE AREA
 BY BAR# 4 IT APPEARS TO BE A RAMP. SHEET 1.9A THERE
 APPEARS TO BE A 3 INCH DIFFERENCE IN HEIGHT AND THIS
 AREA IS LABELED A RAMP.
 PLEASE IDENTIFY THE RAMP AS SUCH.
 1B) SHEET 1.1A THERE APPEARS TO BE SOME TYPE OF
 EQUIPMENT LABELED # 71 A UNDER BAR PASS THRU- SERVICE
 STATION, THIS APPEARS TO BE BLOCKING THE AISLE,
 PROTRUDING OBJECTS, 11-4.4.1.
 PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF
 AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE
 8(E)].
  
 2) SHEET 1.7A CUT SECTION 2/1.3A AND NOTE# 4, 36"
 OPENING WITH WOOD CAP. THE DETAIL INDICATES A NEW 6
 INCH METAL STUD WALL ON SIX INCH CURB. THE PLANS DO NOT
 INDICATE IN THIS SECTION HOW THE CURB IS TO BE ANCHORED
 TO THE SLAB AND BE PART OF TTHE MWFRS. THE SECOND ISSUE
 WITH THIS DETAIL IS NO CLARIFICATION IF THE PLYWOOD
 SHEATHING IS TO STOP AT THE BOTTOM METAL TRACK OR TO GO
 TO THE SLAB HEIGHT. 2304.11.2.6 WOOD SIDING. CLEARANCE
 BETWEEN WOOD SIDING AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM)
 EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 3) THIS SAME SECTION ALSO INDICATES THTE USE OF WIRE
 LATH AND STUCCO, PLEASE REFER TO FBC-B 1404.2.1
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
  
 3.1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 OR
  
 3.2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
  
 3.3 OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 4) PLEASE IDENTIFY HOW THE TOP AND BOTTOM TRACKS ARE TO
 BE FASTENED & SPACING TO THE STRUCTURE TO BACOME PART
 OF THE MWFRS.
  
 5) SHEET 1.7A NOTE # 6 INDICATES THE RELOCATION OF AN
 EXISTING BILCO HATCH, IS THE LOCATION ON THIS PLAN THE
 CURRENT LOCATION OR THE NEW LOCCATION, AND WHAT TYPE OF
 FRAMING IS TO BE REQUIRED FOR BLOCKING AND TYPE OF
 FASTENERS AND SPACING. THIS IS PART OF COMPONENTS AND
 CLADDING, PLEASE INCLUDE PRESSURES FOR ROOF ZONE WHERE
 THE ROOF HATCH IS LOCATED.
  
 6) SHEET 1.7A LOCATED AT BAR# 2 AND TO THE RIGHT OF BAR
 # 2 THERE ARE TO CONSTRUCTION NOTE SYMBOLS # 1
 INDICATING THE REPLACEMEN OF FIXED WINDOWS, IS THIS A
 TYPO? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 7) SHEET 1.4A SECTION# 1 INDICATES A 42 INCH HIGH DRINK
 RAIL ON POST, PLEASE REVIEW SECTION 11-4.4.1
 FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS MAY
 OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO 80
 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR FINISHED
 FLOOR [SEE FIGURE 8(C) AND FIGURE 8(D)].
  
 8) SHEET 1.4A AND 1.6A THERE APPEARS TO BE A LIGHT
 TRUSS THAT HANGS FROM THE ROOF FRAMING ABOVE, PLEASE
 IDENTIFY THE TYPE OF ROOF STRUCTURE THAT EXIST, WOOD
 TRUSSES OR STEEL BAR JOIST?
 HOW THE LIGHT TRUSS WILL BE ATTACHED TO THE ROOF
 FRAMING STRUCTURE AND THE ADDITIONAL LOADS THAT WILL
 OCCUR, WILL THIS POINT LOADING REQUIRE ADDITIONAL
 STRENGTHING OF THE EXISTING ROOF FRAMING SYSTEM?
  
 9) THE PLANS INDICATE THE USE OF NEW WALK IN FREEZERS
 AND COOLER, PLEASE PROVIDE MANUFACTURERS SPEC IN
 COMPLIANCE WITH FBC-B 2603.4.1.2.
  
 10) PLEASE PROVIDE ON THE LIFE SAFETY PLAN COMPLIANCE
 WITH 11-5.1- 11-5.3.
  
 11) ADDITIONAL INFORMATION REQUIRED 106.1.2. SHEET 2.2E
 PANEL D INDICATES ON CIRCIUT# 5 A ALARM/ PHONE. IS THIS
 A FIRE ALRM SYSTEM OR BURGALAR ALARM SYSTEM? FBC-B WITH
 OCCUPANT LOADS OF 300 OR MORE UNDER ASSEMBLY A MANUAL
 FIRE ALARM SYSTEM WOULD BE REQUIRED 907.2.1.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-09-08 Cont ID  
Sent By jleahy Date 2010-09-08 Time 09:51 Rev Time 0.00
Received By jleahy Date 2010-09-08 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-11 Cont ID  
Sent By jleahy Date 2010-08-11 Time 16:28 Rev Time 0.00
Received By jleahy Date 2010-08-11 Time 16:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-02 Cont ID  
Sent By mcarsill Date 2010-09-02 Time 11:40 Rev Time 0.00
Received By mcarsill Date 2010-09-02 Time 10:51 Sent To  
Notes
2010-09-02 11:40:34600 VILLAGE BOULEVARD
 RENEGADES
 PERMIT NUMBER 10070434
  
  
 1. ON AUGUST 31, 2010, REPRESENTATIVES OF THE FIRE
 MARSHAL'S OFFICE MET WITH PETE RUSSO, ARCHITECT TO
 DISCUSS EXITING ISSUES FOR THE ESTABLISHMENT. A NEW
 LIFE SAFETY PLAN WAS SUBMITTED LATER IN THE DAY ON
 AUGUST 31, 2010 WHICH DISPLAYED NEW EXIT SIGNS AND
 EMERGENCY LIGHTS AND ALSO A NEW EXIT OPENING HAS BEEN
 PROVIDED FOR NEAR BAR # 2. ALSO DOORS HAVE BEEN REMOVED
 APPROACHING THE HOST STAND WHICH APPEARS TO ACCOMMODATE
 THE 2/3 REQUIRED EXIT CAPACITY FOR THE ESTABLISHMENT.
  
 2. AS NOTED ON THE NEW LIFE SAFETY PLAN, SEPARATE PLANS
 AND PERMITS REQUIRED FOR THE FIRE SPRINKLER, FIRE
 ALARM, HOOD SUPPRESSION, AND GREASE HOOD EXHAUST
 SYSTEMS.
  
 3. CROWD MANAGEMENT CERTIFICATES FROM MANAGEMENT
 PERSONNEL ARE TO BE SUBMITTED TO THE FIRE MARSHAL'S
 OFFICE PRIOR TO OPENING.
  
 4. THE MAXIMUM OCCUPANT LOAD WILL BE ESTABLISHED BY THE
 FIRE MARSHAL'S OFFICE AND SHALL BE POSTED. THIS LEGAL
 OCCUPANT LOAD IS NOT TO BE EXCEEDED FOR ANY REASON.
  
 5. WHEN THE FIRE ALARM SYSTEM SHOP DRAWINGS ARE
 SUBMITTED, PLEASE INDICATE ON THESE PLANS WHAT
 EMERGENCY INSTRUCTIONS WILL BE PROVIDED TO OCCUPANTS.
  
 6. ALL EXIT DOORS THAT ARE SUBJECT TO LOADS OF 100 OR
 MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 7. THE LIGHTING PLAN SHEET 2.0E WILL NEED TO BE CHANGED
 TO MATCH THE REVISED LIFE SAFETY PLAN.
  
 8. GAS INSTALLATIONS SHALL COMPLY WITH THE APPLICABLE
 NFPA STANDARDS AND BE INSTALLED IN A SAFE AND
 WORKMANLIKE MANNER.
  
  
 APPROVED PROVISO
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-26 Cont ID  
Sent By mcarsill Date 2010-07-26 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2010-07-26 Time 11:27 Sent To  
Notes
2010-07-26 12:06:44INTERIOR REMODEL OF EXISTING TGIF RESTARAUNT TO NEW
 RESTAURANT AND BAR PER CONSTRUCTION DOCUMENTS
 PERMIT NUMBER 10070434
  
 1. FLOOR PLAN DOES NOT ILLUSTRATE ANY SEATING FOR
 PHYSICALLY CHALLENGED PERSONS. PLEASE ILLUSTRATE THESE
 SEATING LOCATIONS.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. THE BUILDING HAS BEEN VACANT FOR SEVERAL YEARS. ALL
 EXISTING SYSTEMS AND DEVICES THAT ARE TO REMAIN ARE TO
 BE THOROUGHLY INSPECTED BY LICENSED CONTRACTORS TO
 ENSURE SUITABILITY FOR CONTINUED USE. PROPER
 DOCUMENTATION IS REQUIRED TO BE SUBMITTED TO THIS
 OFFICE.
  
 4. BASED ON ASSUMED OCCUPANT LOADS, CROWD MANAGEMENT
 TRAINING WILL BE REQUIRED FOR MANAGEMENT STAFF. PLEASE
 GO TO THE MARYLAND STATE FIRE MARSHALS OFFICE WEB-SITE
 AND CLICK ON THE CROWD MANAGEMENT TRAINING ICON. STAFF
 MEMBERS ARE TO WATCH THE VIDEO, TAKE THE ONLINE TEST,
 AND SUBMIT CERTFIICATES TO THIS OFFICE.
  
 5. PLEASE DISPLAY CIRCULATION PATHS THAT WILL BE USED
 FOR EXIT ACCESS PURPOSES WITHIN THE ESTABLISHMENT.
  
 6. THE REQUIRED FIRE ALARM SYSTEM SHALL BE CAPABLE OF
 PROVIDING VOICE EVACUATION MESSAGES WHEN THE FIRE ALARM
 OR FIRE SPRINKLER SYSTEM HAS ACTIVATED. PLEASE PROVIDE
 SEPARATE PLANS AND PERMITS FOR ANY FIRE SPRINKLER OR
 FIRE ALARM SYSTEM REMODELING.
  
 7. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS. THE FIRE
 SUPPRESSION SYSTEM FOR THE HOOD AND DUCT SHALL MEET THE
 REQUIREMENTS OF UL 300.
  
 9. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 10. NO FIRE SPRINKLER SYSTEM DETAILS PROVIDED WITH
 DRAWINGS.
  
 11. ANY BUILDING THAT HAS A LIGHT WEIGHT ROOF OR LIGHT
 WEIGHT FLOOR TRUSS SHALL BE PROPERLY PLACARDED AS PER
 FLORIDA STATUE. PLEASE VERIFY THAT THIS FACILITY DOES
 NOT REQUIRE THIS PLACARDING.
  
 12. A KNOX-BOX IS REQUIRED. PLEASE CONTACT THE KNOX
 COMPANY AT WWW.KNOXBOX.COM TO ORDER THE KEY BOX IF ONE
 DOES NOT CURRENTLY EXIST.
  
 13. PLEASE INDICATE LOCATIONS OF PORTABLE FIRE
 EXTINGUISHING EQUIPMENT.
  
 14. PLEASE ILLUSTRATE ALL LOCATIONS OF FIRE ALARM
 SIGNALING AND NOTIFICATION APPLIANCES.
  
 15. FINAL OCCUPANT LOAD WILL BE DETERMINED BY THIS
 OFFICE.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-09-09 Cont ID  
Sent By lwagner Date 2010-09-09 Time 10:50 Rev Time 0.00
Received By lwagner Date 2010-09-09 Time 10:50 Sent To  
Notes
2010-09-09 10:50:59GAS PERMIT REQUIRED
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-07-28 Cont ID  
Sent By lwagner Date 2010-07-28 Time 10:58 Rev Time 0.00
Received By lwagner Date 2010-07-28 Time 10:46 Sent To  
Notes
2010-07-28 10:58:25GAS PLAN REVIEW #1
 DENIED:
  
 1. WATER HEATER REQUIRES 1 1/4" PIPE UP TO THE
 CONNECTOR TABLE 402.4(2)
  
 2. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2007 FUEL GAS SEC. 402.2
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-26 Cont ID  
Sent By lmartine Date 2010-08-26 Time 10:53 Rev Time 0.00
Received By lmartine Date 2010-08-26 Time 10:53 Sent To  
Notes
2010-08-26 10:54:39*******************EXPEDITED********************
 C--25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-26 Cont ID  
Sent By lmartine Date 2010-08-11 Time 10:55 Rev Time 0.00
Received By lmartine Date 2010-07-22 Time 16:29 Sent To  
Notes
2010-07-22 16:33:46SENT TO C6.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-17 Cont ID  
Sent By hmoser Date 2010-09-17 Time 11:40 Rev Time 0.00
Received By hmoser Date 2010-09-17 Time 11:40 Sent To  
Notes
2010-09-17 11:45:24PROVISO
 PLEASE PROVIDE A DETAIL FROM THE ENGINEER ON THE NEW
 CURB TO ROOF TIEDOWN . PLEASE PROVIDE THE DETAIL AT
 FIRST INSPECTION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-11 Cont ID  
Sent By hmoser Date 2010-08-11 Time 10:42 Rev Time 0.00
Received By hmoser Date 2010-08-11 Time 10:42 Sent To  
Notes
2010-08-11 10:52:36PLANS DENIED
 1) ADDRESS ON PLANS AND APPLICATION DO NOT MATCH .
 2) EXHAUST FOR WOMAN'S BATHROOM SHALL BE A MINIMUM OF
 350 CFM PER TABLE 403.3 2007 FBC (M)
 3) SEPARATE PLANS AND PERMIT ARE REQUIRED FOR THE HOOD.
 4) PLEASE REFER TO SECTION 506.3.12.3 TERMINATION
 LOCATION OF EXHAUST OUTLETS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-09-09 Cont ID  
Sent By lwagner Date 2010-09-09 Time 10:51 Rev Time 0.00
Received By lwagner Date 2010-09-08 Time 14:19 Sent To  
Notes
2010-09-09 11:05:30PLUMBING PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-07-28 Cont ID  
Sent By lwagner Date 2010-07-28 Time 10:46 Rev Time 0.00
Received By lwagner Date 2010-07-28 Time 07:34 Sent To  
Notes
2010-07-28 10:16:19PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. A UNISEX TOILET ROOM WILL BE REQUIRED.
 FBC PLUMBING 2007 403.7 UNISEX TOILET AND BATHING
 ROOMS. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN
 ACCESSIBLE UNISEX TOILET ROOM SHALL BE PROVIDED WHERE
 AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER
 CLOSETS IS REQUIRED.
  
 2. PLEASE SHOW CALCULATIONS FOR GREASE INTERCEPTOR
 CAPACITY FROM TABLE 1003.3.4.1 OR 1003.5.1. BELOW IS AN
 EXAMPLE FROM THE PLUMBING CODE
 TABLE 1003.5.1 SIZING FORMULAS FOR GREASE INTERCEPTORS
 PRIVATE SEWAGE DISPOSAL SYSTEM
 SIZING FORMULA FOR RESTAURANTS:
 (S) X (GS) X (HR/12 X (LF) = EFFECTIVE CAPACITY OF
 GREASE INTERCEPTOR IN GALLONS
 WHERE:
 S = NUMBER OF SEATS IN DINING AREA
 GS = GALLONS OF WASTE WATER PER SEAT (USE 25 GALLONS
 FOR RESTAURANTS WITH CHINA DISHES AND/OR AUTOMATIC
 DISHWASHER) (USE 10 GALLONS FOR RESTAURANTS WITH PAPER
 OR BASKETS AND NO DISHWASHERS)
 HR = NUMBER OF HOURS RESTAURANT IS OPEN
 LF = LOADING FACTOR (USE 2.00 INTERSTATE HIGHWAY; 1.50
 OTHER FREEWAYS; 1.25 RECREATIONAL AREA; 1.00 MAIN
 HIGHWAY; 0.75 OTHER HIGHWAY)
  
 ******NOTE: FOR OTHER THAN PRIVATE SEWAGE DISPOSAL
 SYSTEMS, REDUCE GALLON VALUES BY 25 PERCENT.******
  
 3. COLD WATER DROP IN WOMENS ROOM FOR THE 4 WC'S WOULD
 BE 1 1/4" USING TABLE 603.1
  
 4. COLD WATER DROP IN MENS ROOM SHOULD BE 1 1/4" USING
 TABLE 603.1, ALSO THE ADA WC AND LAV ARE MISSING FROM
 THE ISOMETRIC.
  
 5. THE REGULAR WC IN THE MENS ROOM IS NOT VENTED.
  
 6. ALL FLOOR DRAINS WILL REQUIRE TRAP PRIMERS EXCEPT
 THOSE THAT ARE RECEIVING DRAINAGE FROM FLOOR SINKS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2010-09-16 Cont ID  
Sent By jroach Date 2010-09-16 Time 17:40 Rev Time 0.00
Received By jroach Date 2010-09-16 Time 17:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-09-15 Cont ID  
Sent By jroach Date 2010-09-15 Time 10:06 Rev Time 0.00
Received By jroach Date 2010-09-15 Time 10:06 Sent To  
Notes
2010-09-15 10:12:50ZONING PLAN REVIEW
  
 PERMIT NO.: 10076434
 ADDRESS: 580 VILLAGE BOULEVARD, SUITE 600
 CONTRACTOR/CONTACT: 3-D HOMES, INC.
 TELEPHONE NO.: 561.721.5611
 SCOPE OF REVIEW: INTERIOR REMODEL OF EXISTING TGIF
 RESTAURANT TO NEW RESTAURANT AND BAR.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) REPEAT COMMENT: PLEASE PROVIDE A COPY OF AN
 APPRAISAL INDICATING THE VALUE OF THE EXISTING
 STRUCTURE. PURSUANT TO SECTION 94-411(C)(2) OF THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), RENOVATIONS THAT EXCEED 50 PERCENT OF THE
 APPRAISED VALUE OF THE STRUCTURE SHALL REQUIRE THE SITE
 TO BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPE CODE) OF THE CITY'S ZLDRS. RESPONSE LETTER
 INDICATES AN EMAIL AND DOCUMENTATION TO BE PROVIDED BY
 OWNER....NO EMAIL OR DOCUMENTATION WAS IN THE
 RESUBMITTAL PACKAGE. PLEASE NOTE, THE VALUE OF WORK TO
 THIS STRUCTURE SHALL ONLY BE COMPARED TO THE VALUE OF
 THE RESAURANT STRUCTURE. IT SHALL NOT INCLUDE THE VALUE
 OF ANY OF THE OFFICE BUILDINGS, BANK, LAND, ETC. PLEASE
 PROVIDE DOCUMENTATION INDICATING THE CURRENT VALUE OF
 THE RESTAURANT STRUCTURE ONLY.
  
 THE FOLLOWING COMMENTS ARE APPLICABLE TO BUSINESSES
 OPERATING WITH A FULL 4COP ALCOHOL LICENSE AND THAT DO
 NOT SATISFY ANY OF THE EXEMPTIONS LISTED IN SECTION 6-2
 OF THE CITY'S CODE OF ORDINANCES.
  
 2) PURSUANT TO SECTION 6-2 OF THE CITY'S CODE OF
 ORDINANCES, NO RETAIL ESTABLISHMENT FOR THE SALE OF
 LIQUOR TO BE CONSUMED ON THE PREMISES SHALL BE ALLOWED
 WHERE THE LOCATION IS WITHIN 500 FEET OF A CHURCH. AS
 INDICATED IN NUMEROUS DISCUSSIONS WITH THE OWNER OF THE
 PROPOSED BUSINESS, THE PROPERTY WILL NEED TO BE
 SUBDIVIDED. AS PART OF THE SUBDIVISION, ADDITIONAL
 IMPROVEMENTS MAY BE NEEDED ON THE SITE REGARDING
 PARKING, LANDSCAPING, ETC. THIS COMMENT WILL NOT HOLD
 UP THE ISSUANCE OF THE PERMIT, BUT IS BEING PROVIDED AS
 ADDITIONAL INFORMATION.
  
 3) PURSUANT TO SECTION 6-2(C)(7)(B), PARKING LOTS ON
 THE PREMISE SHALL BE SEPARATED FROM THE ADJACENT
 RESIDENTIAL DISTRICT BY A SIX (6) FOOT HIGH SOLID EIGHT
 (8) INCH MASONRY WALL. THIS COMMENT WILL NOT HOLD UP
 THE ISSUANCE OF THE PERMIT, BUT IS BEING PROVIDED AS
 ADDITIONAL INFORMATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-10 Cont ID  
Sent By jroach Date 2010-08-10 Time 10:10 Rev Time 0.00
Received By jroach Date 2010-08-10 Time 10:10 Sent To  
Notes
2010-08-10 10:10:32ZONING PLAN REVIEW
  
 PERMIT NO.: 10076434
 ADDRESS: 580 VILLAGE BOULEVARD, SUITE 600
 CONTRACTOR/CONTACT: 3-D HOMES, INC.
 TELEPHONE NO.: 561.721.5611
 SCOPE OF REVIEW: INTERIOR REMODEL OF EXISTING TGIF
 RESTAURANT TO NEW RESTAURANT AND BAR.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PLEASE PROVIDE A COPY OF AN APPRAISAL INDICATING THE
 VALUE OF THE EXISTING STRUCTURE. PURSUANT TO SECTION
 94-411(C)(2) OF THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), RENOVATIONS THAT
 EXCEED 50 PERCENT OF THE APPRAISED VALUE OF THE
 STRUCTURE SHALL REQUIRE THE SITE TO BE BROUGHT INTO
 COMPLIANCE WITH ARTICLE XIV (LANDSCAPE CODE) OF THE
 CITY???S ZLDRS.
  
 2) PLANS INDICATE THE PROVISION OF ADDITIONAL OUTDOOR
 SEATING AREA. IN ORDER TO EXPAND THE SEATING AREA,
 ADDITIONAL PARKING MAY BE REQUIRED. PLEASE PROVIDE A
 SITE PLAN INDICATING THAT THE PROPERTY HAS EXCESS
 PARKING (BEYOND CURRENT CODE REQUIREMENTS) TO
 ACCOMMODATE THE ADDITIONAL SEATING AREA.
  
 3) PURSUANT TO THE MINOR AMENDMENT APPROVED ON DECEMBER
 16, 2004, THE ADDITIONAL OUTDOOR SEATING AREA WAS
 APPROVED ON THE CONDITION THAT THE LANDSCAPING
 DISPLACED BY THE ADDITION WILL BE RELOCATED. PLEASE
 PROVIDE A SIGNED/SEALED LANDSCAPE PLAN INDICATING THE
 LOCATION OF THE NEW LANDSCAPING. SUCH LANDSCAPING SHALL
 ALSO BE SUBMITTED UNDER A SEPARATE PERMIT.
  
 THE FOLLOWING COMMENTS ARE APPLICABLE TO BUSINESSES
 OPERATING WITH A FULL 4COP ALCOHOL LICENSE AND THAT DO
 NOT SATISFY ANY OF THE EXEMPTIONS LISTED IN SECTION 6-2
 OF THE CITY???S CODE OF ORDINANCES.
  
 4) PURSUANT TO SECTION 6-2 OF THE CITY???S CODE OF
 ORDINANCES, NO RETAIL ESTABLISHMENT FOR THE SALE OF
 LIQUOR TO BE CONSUMED ON THE PREMISES SHALL BE ALLOWED
 WHERE THE LOCATION IS WITHIN 500 FEET OF A CHURCH. AS
 INDICATED IN NUMEROUS DISCUSSIONS WITH THE OWNER OF THE
 PROPOSED BUSINESS, THE PROPERTY WILL NEED TO BE
 SUBDIVIDED. AS PART OF THE SUBDIVISION, ADDITIONAL
 IMPROVEMENTS MAY BE NEEDED ON THE SITE REGARDING
 PARKING, LANDSCAPING, ETC.
  
 5) PURSUANT TO SECTION 6-2(C)(7)(A), BUILDINGS USED FOR
 CONSUMPTION ON PREMISE SHALL HAVE NO OPENINGS WITHIN
 200 FEET OF A RESIDENTIAL ZONING DISTRICT, OTHER THAN
 DOORS FOR THE PURPOSE OF INGRESS AND EGRESS WHICH ARE
 TO BE KEPT CLOSED AT ALL TIMES. AS SUCH, NEITHER THE
 ADDITIONAL OUTDOOR SEATING/BAR, NOR HORIZONTAL SLIDING
 WINDOWS SHALL BE PERMITTED TO BE INSTALLED ALONG THE
 SOUTHWEST SIDE OF THE BUILDING.
  
 6) PURSUANT TO SECTION 6-2(C)(7)(B), PARKING LOTS ON
 THE PREMISE SHALL BE SEPARATED FROM THE ADJACENT
 RESIDENTIAL DISTRICT BY A SIX (6) FOOT HIGH SOLID EIGHT
 (8) INCH MASONRY WALL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  