Plan Review Stops For Permit 10070403 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2010-07-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-07-28 |
Time |
18:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-07-28 |
Time |
18:21 |
Sent To |
|
|
Notes |
2010-07-28 18:23:58 | ****PROVISO**** | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | | 1. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | INSTALLATION SCHEDULE. FBC R301, FBC1609, FBC*106. | | | | 2. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. | | | | 3. REVISE EXPOSURE CATEGORY OR PROVIDE ENGINEERING | | RATIONALE FOR EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE | | THAT THE CODE CHANGED EFFECTIVE MARCH 1, 2009. | | | | 4. SUBMIT A REVISED INSTALLATION SCHEDULE WITH REVISED | | DESIGN PRESSURES. | | | | | | |
|
|