Plan Review Details - Permit 10070239
Plan Review Stops For Permit 10070239
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-02 Cont ID  
Sent By mcarsill Date 2010-08-02 Time 09:26 Rev Time 0.00
Received By mcarsill Date 2010-08-02 Time 09:21 Sent To  
Notes
2010-08-02 09:26:04SUBSEQUENT TO THE FIRE PLAN REVIEW COMMENTS A MEETING
 WAS HELD WITH A REPRESENTATIVE OF FLORIDA FILTRATION.
 THE MASTER PLANS WERE REVIEWED AND DISCUSSIONS OCCURRED
 REGARDING THE PERMIT APPLICATION FOR THE MIXING ROOM
 DRY CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 1. NO SPRAYING OF VEHICLES WILL OCCUR WITHIN THE MIXING
 ROOM. THE ROOM IS TO BE USED ONLY FOR MIXING PAINT.
  
 2. ADDRESS IS MIXING FROM TITLE BLOCK.
  
 3. A REVIEW OF THE MASTER DRAWINGS CLEARED SOME
 CONFUSION WITH REGARDS TO THE SUB PERMIT.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 13:08 Rev Time 0.00
Received By wjolin Date 2010-07-23 Time 13:07 Sent To  
Notes
2010-07-23 13:08:51*****DENIED*****
  
 1) PROVIDE ADDRESS IN TITLEBLOCK
 2) PROVIDE SUPPRESSION COVERAGE IN EXHAUST PLENUM AND
 EXHAUST DUCTWORK PER NFPA 33 (2003 ED.), SECTION 9.5.
 3) PROVIDE SYSTEM SPECIFICATION SHEET
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 13:07 Rev Time 0.00
Received By wjolin Date 2010-07-08 Time 09:23 Sent To  
Notes
2010-07-12 09:21:43IN FIRE BOX