Plan Review Details - Permit 10070193
Plan Review Stops For Permit 10070193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-08-26 Cont ID  
Sent By shill Date 2010-08-26 Time 12:04 Rev Time 0.00
Received By shill Date 2010-08-26 Time 12:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-11 Cont ID  
Sent By shill Date 2010-08-11 Time 17:49 Rev Time 0.00
Received By shill Date 2010-08-11 Time 17:49 Sent To  
Notes
2010-08-11 17:59:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. NOTICE OF COMMENCEMENT TO BE SIGNED BY THE OWNER,
 FS714.
  
 2. OWNER ON APPLICATION NOT CORRECCT, PLEASE REVISE.
  
 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL,
 FS481.
  
 4. ADDRESSED.
  
 5. PROVIDE A DETAIL FOR THE CHECKOUT COUNTER,
 FBC11-7.2.
  
 6. FBC EB401.1, THE DESIGN PROFESSIONAL IS TO ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION; PLEASE
 INCLUDE ON THE PLAN.
  
 7-11. ADDRESSED.
  
 12. FOR ALL AMENITIES, SHOW ACCESSIBILITY (NAIL
 STATIONS, PEDICURE STATIONS), FBC 11.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-12 Cont ID  
Sent By shill Date 2010-07-12 Time 18:12 Rev Time 0.00
Received By shill Date 2010-07-12 Time 18:12 Sent To  
Notes
2010-07-12 18:35:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. NOTICE OF COMMENCEMENT TO BE SIGNED BY THE OWNER,
 FS714.
  
 2. OWNER ON APPLICAITON NOT CORRECCT, PLEASE REVISE.
  
 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL,
 FS481.
  
 4. PROVIDE INFORMATION REGARDING THE CURRENT AND
 PROPOSED OCCUPANCY CLASSIFICATION ON THE PLAN, FBC
 CHAPTER 3.
  
 5. PROVIDE A DETAIL FOR THE CHECKOUT COUNTER,
 FBC11-7.2.
  
 6. FBC EB401.1, THE DESIGN PROFESSIONAL IS TO ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION; PLEASE
 INCLUDE ON THE PLAN.
  
 7. PROVIDE A DIMENSIONED FLOOR PLAN, TO SCALE, FBC106.
 PROVIDE DETAILS OR SECTIONS AS NECESSARY. THE PLAN
 SHOWS A NUMBER OF SQUARES ON IT WITHOUT ANY INFORMATION
 AS TO WHAT THE SQUARES REPRESENT.
  
 8. PROVIDE A LIFE SAFETY PLAN SHOWING ALL PROPOSED
 IMPROVEMENTS (COUNTERS, FURNITURE, ETC.), WIDTH OF
 EGRESS TRAVEL, FBC 1014.
  
 9. STATE PROPOSED OCCUPANT LOAD FBC 1004.
  
 10. SHOW ACCESSIBLE ROUTE CONNECTING ALL ACCESSIBLE
 SPACES AND ELEMENTS FBC11-4.1.3. SEE ALSO DEFINITION OF
 PLACE OF PUBLIC ACCOMODATION FBC11-3.
  
 NOTE THAT THE DISTANCE BETWEEN THE PROPOSED PEDICURE
 STATIONS DOES NOT COMPLY WITH FBC11-4.3.3 OR FBC1014.4.
  
 11. AS PROPSED USE IS A NAIL SALON, WILL THERE BE NAIL
 STATIONS? PLEASE SHOW ON THE PLAN.
  
 12. FOR ALL AMENITIES, SHOW ACCESSIBILITY (NAIL
 STATIONS, PEDICURE STATIONS).
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2010-08-26 Cont ID  
Sent By shill Date 2010-08-26 Time 08:51 Rev Time 0.00
Received By shill Date 2010-08-26 Time 08:51 Sent To  
Notes
2010-08-26 08:52:25VOIDED ELECTRIC SUB PERMIT, INFORMED CONTRACTOR, PLANS
 AND APPLICATION TO BE SUBMITTED SEPARATELY
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-08-24 Cont ID  
Sent By shill Date 2010-08-24 Time 16:23 Rev Time 0.00
Received By shill Date 2010-08-24 Time 16:23 Sent To  
Notes
2010-08-24 16:28:20JOHN DICKINSON CONTRACT PLAN REVIEWER PX3182
2010-08-24 16:25:46APPROVED ELECT PLAN VOID,DOES NOT MATCH NEW FLOOR PLAN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-13 Cont ID  
Sent By shill Date 2010-08-13 Time 12:34 Rev Time 0.00
Received By shill Date 2010-08-13 Time 12:34 Sent To  
Notes
2010-08-13 12:35:00OK PER JOHN DICKINSON (CONTRACT REVIEWER)
 PX3182
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-28 Cont ID  
Sent By jleahy Date 2010-07-28 Time 10:53 Rev Time 0.00
Received By jleahy Date 2010-07-28 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 14:28 Rev Time 0.00
Received By wjolin Date 2010-07-23 Time 14:17 Sent To  
Notes
2010-07-23 14:27:56*****APPROVED*****
  
 1) PLEASE ENSURE ILLUMINATED EXIT SIGNS ARE INSTALLED
 AT EXIT DOOR LOCATIONS. PLANS DO NOT INDICATE ANY
 EXISTING SIGNS.
  
 2) NO EMERGENCY LIGHTS DIPLAYED ON PLANS.
  
 3) NO PORTABLE FIRE EXTINGUISHERS SHOWN ON PLANS.
  
 ON 7/23 WRITER CALLED WILLIAM MARTIN WHO ADVISED
 ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS, AND A
 PORTABLE FIRE EXTINGUISHER IS PRESENT.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 561-804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-08-19 Cont ID  
Sent By shill Date 2010-08-19 Time 15:57 Rev Time 0.00
Received By shill Date 2010-08-19 Time 15:58 Sent To  
Notes
2010-08-19 15:57:59***** EXPEDITED 3RD ROUND ****
  
 B9
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-19 Cont ID  
Sent By shill Date 2010-08-19 Time 15:57 Rev Time 0.00
Received By shill Date 2010-08-05 Time 16:25 Sent To  
Notes
2010-08-05 16:25:41SENT TO B9.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-30 Cont ID  
Sent By lmartine Date 2010-07-28 Time 09:06 Rev Time 0.00
Received By lmartine Date 2010-07-12 Time 15:33 Sent To  
Notes
2010-07-12 15:43:06*******************EXPEDITED******************
 B--9

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-08-27 Cont ID  
Sent By rregueir Date 2010-08-27 Time 11:03 Rev Time 0.00
Received By rregueir Date 2010-08-27 Time 10:58 Sent To B
Notes
2010-08-27 11:03:25**PROVISO**
  
 ROOF CAP DETAIL SHOWS BIRDSCREEN, WHICH IS PROHIBITED
 AT THE TERMINATION. A BACKDRAFT DAMPER IS ALSO REQUIRED
 PER FBC-M 504.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-08-13 Cont ID  
Sent By hmoser Date 2010-08-13 Time 10:20 Rev Time 0.00
Received By hmoser Date 2010-08-13 Time 10:20 Sent To  
Notes
2010-08-13 13:06:00****CORRECTIONS****
 ****PLAN REVIEW IN PROGRESS****
  
 1. PREVIOUS LIST REQUESTED THAT PLAN SHOW DRYER EXHAUST
 DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH FBC
 M504.1 AND 504.6.2. MANUFACTURER'S INSTRUCTIONS NOT
 PROVIDED AND EXHAUST DETAIL NOT PROVIDED. DISTANCE FROM
 DRYER TO DISCHARGE NOT SHOWN ON PLAN. DUCT DETAIL NOT
 PROVIDED, DUCTWORK APPEARS TO BE SHOWN IN WALL BUT
 ISN'T THIS A FIRE RATED TENANT SEPARATION WALL?
  
 2. COMMENT FROM PREVIOUS LIST, SHOW HOW REQUIRED
 VENTILATION RATES FOR THIS USE ARE TO BE ACHIEVED IN
 ACCORDANCE WITH FBC EB 901.2 AND FBC M403.3. SEE TABLE
 FBC M403.1, ALSO FOOTNOTE (B) AND (I).
  
 3. SEE FBC501.2.1, PROVIDE A SITE PLAN SHOWING DISTANCE
 BETWEEN INTAKES AND OPENINGS.
  
 4. PROVIDE A DETAIL SHOWING HOW OTHER EXHAUST DUCTWORK
 IS TO BE INSTALLED.
  
 5. THE PLAN IS TO BE PREPARED BY A PROFESSIONAL
 LICENSED FOR DESIGN OF MECHANICAL SYSTEMS.
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-07-13 Cont ID  
Sent By rregueir Date 2010-07-13 Time 10:25 Rev Time 0.00
Received By rregueir Date 2010-07-13 Time 10:19 Sent To  
Notes
2010-07-13 10:25:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN SHOWS NEW DRYER BEING INSTALLED. SHOW DRYER
 EXHAUST DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH
 FBC-M 504.1 AND 504.6.2.
  
 2. NO INFORMATION ON PLANS REGARDING VENTILATION. SHOW
 HOW REQUIRED VENTILATION RATES FOR THIS USE ARE TO BE
 ACHIEVED IN ACCORDANCE WITH FBC-EB 901.2 AND FBC-M
 403.3.
  
 A THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-08-25 Cont ID  
Sent By lwagner Date 2010-08-25 Time 13:24 Rev Time 0.00
Received By lwagner Date 2010-08-25 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-08-09 Cont ID  
Sent By lwagner Date 2010-08-09 Time 09:26 Rev Time 0.00
Received By lwagner Date 2010-08-09 Time 08:59 Sent To  
Notes
2010-08-09 09:25:48FBC 2007
 PLUMBING PLAN REVIEW
 DENIED
  
  
 1. OK
 2. OK
 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL,
 FS481.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-07-26 Cont ID  
Sent By lwagner Date 2010-07-26 Time 15:00 Rev Time 0.00
Received By lwagner Date 2010-07-26 Time 14:34 Sent To  
Notes
2010-07-26 14:59:26FBC 2007
 PLUMBING PLAN REVIEW
 DENIED
  
 NOT ENOUGH INFORMATION FOR REVIEW.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 13. PLUMBING RISER DIAGRAMS
  
 1. CAN NOT TELL IF NEW TUBS ARE CONNECTING INTO A WET
 VENT. ONLY BATHROOM FIXTURES MAY CONNECT INTO A WET
 VENT.
  
 2. IS WASHING MACHINE NEW OR EXISTING? SEE ABOVE FOR
 WET VENTING
  
 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL,
 FS481.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-07-13 Cont ID  
Sent By eschneid Date 2010-07-13 Time 16:37 Rev Time 0.25
Received By eschneid Date 2010-07-13 Time 16:37 Sent To  
Notes
2010-07-13 16:42:301) NO REVIEW DUE TO NO EXTERIOR WORK SHOWN. VALUE LESS
 THAN 50% OF STRUCTURE.
  
 2) ZONING NEEDS TO REVIEW IF EXTERIOR DUCT WORK OR
 MECHANICAL EQUIPMENT IS REQUIRED TO ADDRESS OTHER
 REVIEWERS COMMENTS.