Plan Review Stops For Permit 10070193 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-08-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-26 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-26 |
Time |
12:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-08-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-11 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-11 |
Time |
17:49 |
Sent To |
|
|
Notes |
2010-08-11 17:59:31 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: | | | | 1. NOTICE OF COMMENCEMENT TO BE SIGNED BY THE OWNER, | | FS714. | | | | 2. OWNER ON APPLICATION NOT CORRECCT, PLEASE REVISE. | | | | 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL, | | FS481. | | | | 4. ADDRESSED. | | | | 5. PROVIDE A DETAIL FOR THE CHECKOUT COUNTER, | | FBC11-7.2. | | | | 6. FBC EB401.1, THE DESIGN PROFESSIONAL IS TO ELECT ONE | | OR A COMBINATION OF LEVELS OF ALTERATION; PLEASE | | INCLUDE ON THE PLAN. | | | | 7-11. ADDRESSED. | | | | 12. FOR ALL AMENITIES, SHOW ACCESSIBILITY (NAIL | | STATIONS, PEDICURE STATIONS), FBC 11. | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-07-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-07-12 |
Time |
18:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-07-12 |
Time |
18:12 |
Sent To |
|
|
Notes |
2010-07-12 18:35:41 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. NOTICE OF COMMENCEMENT TO BE SIGNED BY THE OWNER, | | FS714. | | | | 2. OWNER ON APPLICAITON NOT CORRECCT, PLEASE REVISE. | | | | 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL, | | FS481. | | | | 4. PROVIDE INFORMATION REGARDING THE CURRENT AND | | PROPOSED OCCUPANCY CLASSIFICATION ON THE PLAN, FBC | | CHAPTER 3. | | | | 5. PROVIDE A DETAIL FOR THE CHECKOUT COUNTER, | | FBC11-7.2. | | | | 6. FBC EB401.1, THE DESIGN PROFESSIONAL IS TO ELECT ONE | | OR A COMBINATION OF LEVELS OF ALTERATION; PLEASE | | INCLUDE ON THE PLAN. | | | | 7. PROVIDE A DIMENSIONED FLOOR PLAN, TO SCALE, FBC106. | | PROVIDE DETAILS OR SECTIONS AS NECESSARY. THE PLAN | | SHOWS A NUMBER OF SQUARES ON IT WITHOUT ANY INFORMATION | | AS TO WHAT THE SQUARES REPRESENT. | | | | 8. PROVIDE A LIFE SAFETY PLAN SHOWING ALL PROPOSED | | IMPROVEMENTS (COUNTERS, FURNITURE, ETC.), WIDTH OF | | EGRESS TRAVEL, FBC 1014. | | | | 9. STATE PROPOSED OCCUPANT LOAD FBC 1004. | | | | 10. SHOW ACCESSIBLE ROUTE CONNECTING ALL ACCESSIBLE | | SPACES AND ELEMENTS FBC11-4.1.3. SEE ALSO DEFINITION OF | | PLACE OF PUBLIC ACCOMODATION FBC11-3. | | | | NOTE THAT THE DISTANCE BETWEEN THE PROPOSED PEDICURE | | STATIONS DOES NOT COMPLY WITH FBC11-4.3.3 OR FBC1014.4. | | | | 11. AS PROPSED USE IS A NAIL SALON, WILL THERE BE NAIL | | STATIONS? PLEASE SHOW ON THE PLAN. | | | | 12. FOR ALL AMENITIES, SHOW ACCESSIBILITY (NAIL | | STATIONS, PEDICURE STATIONS). | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
N |
Date |
2010-08-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-26 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-26 |
Time |
08:51 |
Sent To |
|
|
Notes |
2010-08-26 08:52:25 | VOIDED ELECTRIC SUB PERMIT, INFORMED CONTRACTOR, PLANS | | AND APPLICATION TO BE SUBMITTED SEPARATELY | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2010-08-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-24 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-24 |
Time |
16:23 |
Sent To |
|
|
Notes |
2010-08-24 16:28:20 | JOHN DICKINSON CONTRACT PLAN REVIEWER PX3182 | 2010-08-24 16:25:46 | APPROVED ELECT PLAN VOID,DOES NOT MATCH NEW FLOOR PLAN |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-08-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-13 |
Time |
12:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-13 |
Time |
12:34 |
Sent To |
|
|
Notes |
2010-08-13 12:35:00 | OK PER JOHN DICKINSON (CONTRACT REVIEWER) | | PX3182 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-07-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2010-07-28 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2010-07-28 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2010-07-23 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2010-07-23 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2010-07-23 |
Time |
14:17 |
Sent To |
|
|
Notes |
2010-07-23 14:27:56 | *****APPROVED***** | | | | 1) PLEASE ENSURE ILLUMINATED EXIT SIGNS ARE INSTALLED | | AT EXIT DOOR LOCATIONS. PLANS DO NOT INDICATE ANY | | EXISTING SIGNS. | | | | 2) NO EMERGENCY LIGHTS DIPLAYED ON PLANS. | | | | 3) NO PORTABLE FIRE EXTINGUISHERS SHOWN ON PLANS. | | | | ON 7/23 WRITER CALLED WILLIAM MARTIN WHO ADVISED | | ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS, AND A | | PORTABLE FIRE EXTINGUISHER IS PRESENT. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 561-804-4709 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-08-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-19 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-19 |
Time |
15:58 |
Sent To |
|
|
Notes |
2010-08-19 15:57:59 | ***** EXPEDITED 3RD ROUND **** | | | | B9 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-08-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-19 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-05 |
Time |
16:25 |
Sent To |
|
|
Notes |
2010-08-05 16:25:41 | SENT TO B9. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-07-30 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-07-28 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-07-12 |
Time |
15:33 |
Sent To |
|
|
Notes |
2010-07-12 15:43:06 | *******************EXPEDITED****************** | | B--9 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2010-08-27 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2010-08-27 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2010-08-27 |
Time |
10:58 |
Sent To |
B |
|
Notes |
2010-08-27 11:03:25 | **PROVISO** | | | | ROOF CAP DETAIL SHOWS BIRDSCREEN, WHICH IS PROHIBITED | | AT THE TERMINATION. A BACKDRAFT DAMPER IS ALSO REQUIRED | | PER FBC-M 504.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2010-08-13 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2010-08-13 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2010-08-13 |
Time |
10:20 |
Sent To |
|
|
Notes |
2010-08-13 13:06:00 | ****CORRECTIONS**** | | ****PLAN REVIEW IN PROGRESS**** | | | | 1. PREVIOUS LIST REQUESTED THAT PLAN SHOW DRYER EXHAUST | | DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH FBC | | M504.1 AND 504.6.2. MANUFACTURER'S INSTRUCTIONS NOT | | PROVIDED AND EXHAUST DETAIL NOT PROVIDED. DISTANCE FROM | | DRYER TO DISCHARGE NOT SHOWN ON PLAN. DUCT DETAIL NOT | | PROVIDED, DUCTWORK APPEARS TO BE SHOWN IN WALL BUT | | ISN'T THIS A FIRE RATED TENANT SEPARATION WALL? | | | | 2. COMMENT FROM PREVIOUS LIST, SHOW HOW REQUIRED | | VENTILATION RATES FOR THIS USE ARE TO BE ACHIEVED IN | | ACCORDANCE WITH FBC EB 901.2 AND FBC M403.3. SEE TABLE | | FBC M403.1, ALSO FOOTNOTE (B) AND (I). | | | | 3. SEE FBC501.2.1, PROVIDE A SITE PLAN SHOWING DISTANCE | | BETWEEN INTAKES AND OPENINGS. | | | | 4. PROVIDE A DETAIL SHOWING HOW OTHER EXHAUST DUCTWORK | | IS TO BE INSTALLED. | | | | 5. THE PLAN IS TO BE PREPARED BY A PROFESSIONAL | | LICENSED FOR DESIGN OF MECHANICAL SYSTEMS. | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-07-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2010-07-13 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2010-07-13 |
Time |
10:19 |
Sent To |
|
|
Notes |
2010-07-13 10:25:19 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PLAN SHOWS NEW DRYER BEING INSTALLED. SHOW DRYER | | EXHAUST DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH | | FBC-M 504.1 AND 504.6.2. | | | | 2. NO INFORMATION ON PLANS REGARDING VENTILATION. SHOW | | HOW REQUIRED VENTILATION RATES FOR THIS USE ARE TO BE | | ACHIEVED IN ACCORDANCE WITH FBC-EB 901.2 AND FBC-M | | 403.3. | | | | A THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2010-08-25 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2010-08-25 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2010-08-09 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2010-08-09 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2010-08-09 |
Time |
08:59 |
Sent To |
|
|
Notes |
2010-08-09 09:25:48 | FBC 2007 | | PLUMBING PLAN REVIEW | | DENIED | | | | | | 1. OK | | 2. OK | | 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL, | | FS481. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2010-07-26 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2010-07-26 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2010-07-26 |
Time |
14:34 |
Sent To |
|
|
Notes |
2010-07-26 14:59:26 | FBC 2007 | | PLUMBING PLAN REVIEW | | DENIED | | | | NOT ENOUGH INFORMATION FOR REVIEW. | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS: | | 13. PLUMBING RISER DIAGRAMS | | | | 1. CAN NOT TELL IF NEW TUBS ARE CONNECTING INTO A WET | | VENT. ONLY BATHROOM FIXTURES MAY CONNECT INTO A WET | | VENT. | | | | 2. IS WASHING MACHINE NEW OR EXISTING? SEE ABOVE FOR | | WET VENTING | | | | 3. PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL, | | FS481. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2010-07-13 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-07-13 |
Time |
16:37 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2010-07-13 |
Time |
16:37 |
Sent To |
|
|
Notes |
2010-07-13 16:42:30 | 1) NO REVIEW DUE TO NO EXTERIOR WORK SHOWN. VALUE LESS | | THAN 50% OF STRUCTURE. | | | | 2) ZONING NEEDS TO REVIEW IF EXTERIOR DUCT WORK OR | | MECHANICAL EQUIPMENT IS REQUIRED TO ADDRESS OTHER | | REVIEWERS COMMENTS. |
|
|