Plan Review Stops For Permit 10070171 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2010-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2010-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-04 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-04 |
Time |
11:24 |
Sent To |
|
|
Notes |
2010-08-04 11:24:31 | REVISION REQUIRED | | | | 1) THE PRODUCT APPROVALS SUBMITTED FOR THE 8' X 16' | | GARAGE DOOR NEEDS TO BE UPDATED TO THE 2007 CODE | | EDITION. THE DESIGN PRESSURES FOR THE OAK SUMMIT MODEL | | DO NOT MEET THE REQUIRED OPENING PRESSURES FOR EXPOSURE | | C INDICATED ON THE PLANS. | | | | 2) SUBMIT THE PRODUCT APPROVAL FOR THE POLYSTICK | | UNDERLAYMENT HAS BEEN SUPERSEDED. SUBMIT THE CURRENT | | PRODUCT APPROVAL WITH NOA NO. 09-0806.07. | | | | NOTE: DESIGNER OF RECORD IS REQUIRED TO REVIEW AND | | APPROVE PRODUCT APPROVALS IN WRITING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-08-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2010-08-05 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2010-08-05 |
Time |
10:02 |
Sent To |
|
|
Notes |
2010-08-05 10:03:07 | SEE NOTES PAGES E-1.0--- E-1.3 JL |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-18 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-18 |
Time |
16:21 |
Sent To |
|
|
Notes |
2010-08-18 16:21:46 | OK PER M. CARSILLO |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-07-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-07-28 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-07-28 |
Time |
11:10 |
Sent To |
|
|
Notes |
2010-07-28 11:10:16 | OAKTON PRESERVE | | PERMIT NUMBER 10070137 | | LOTS35,36,37,38,39,40,41, AND 42 | | | | 1. PER FLORIDA STATUE 553.885, THE CARBON MONOXIDE | | DETECTORS SHOWN ON THE SECOND FLOORS MUST BE INSTALLED | | WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. | | | | 2. PER FLORIDA STATUE 633.027 "THE OWNER OF ANY | | COMMERCIAL OR INDUSTRIAL STRUCTURE, OR ANY MULT-UNIT | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, THAT USES | | LIGHT-FRAME TRUSS CONSTRUCTION SHALL MARK THE STRUCTURE | | WITH A SIGN APPROVED BY THE STATE FIRE MARSHAL IN A | | MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE | | CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE | | OF LIGHT FRAME TRUSS TYPE CONSTRUCTION IN THE | | STRUCTURE". | | | | 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 4. THE EGRESS WINDOW FOR BEDROOM 2 NOT IDENTIFIED ON | | PAGE TU-2.1. | | | | 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATION FOR | | WALLS AND CEILINGS IN EACH UNIT. | | | | 6. UNITS 35-36 ON PAGE A-3.1. HAVE NO PREMISES | | IDENTIFICATION. | | | | 7. PORTABLE FIRE EXTINGUISHERS NOT SHOWN? | | | | 8. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT | | LEAST 10 FEET FROM AIR CONDITIONER DIFUSERS. | | | | 9. PROVIDE DETAILS ON FIRE RETARDANT COATINGS DESCRIBED | | ON PAGES A-4.1 AND A-4.2. | | | | 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR HANDRAILS AND GUARDRAILS. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-07-08 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2010-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-18 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-04 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-04 |
Time |
10:29 |
Sent To |
|
|
Notes |
2010-08-04 10:30:13 | BUILDING #6 - 8 UNIT TOWNHOUSES | | | | DENIED BY MECHANICAL | | | | 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER BEDROOM | | SUITE IS UNDER SIZED. FBC R M1602.4 REQUIRES THE | | TRANSFER DUCT TO BE 1.5 TIMES THE SUPPLY, THEREFORE A | | 14" DUCT IS REQUIRED. | | PLEASE CORRECT. | | | | 2) THE EQUIPMENT MODEL NUMBERS ON THE PLANS AND THE | | SIZING CALCS. DO NOT MATCH FOR THE END UNITS. PLEASE | | CORRECT. | | | | 3) THE CU MOUNTING DETAIL ON THE MECHANICAL PLANS | | REFERENCES THE 2004 FBC AND ASCE 02. PLEASE UPDATE TO | | 2007 FBC AND ASCE7-05 AND CORRECT THE SECTIONS THAT ARE | | LISTED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2010-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-04 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-04 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2010-07-27 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-07-27 |
Time |
10:11 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2010-07-27 |
Time |
10:11 |
Sent To |
|
|
Notes |
2010-07-27 10:11:32 | PASSED W/PROVISO | | | | A LANDSCAPE FINAL FOR PERMIT NUMBER 10070645 IS | | REQUIRED PRIOR TO THE PRIOR TO CONSTRUCTION SERVICES | | FINAL INSPECTION AND CERTIFICATE OF OCCUPANCY FOR THIS | | PERMIT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-07-27 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-07-20 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2010-07-20 |
Time |
16:04 |
Sent To |
|
|
Notes |
2010-07-20 16:06:42 | FAILED - WILL PASS UPON THE PROVISION OF THE FOLLOWING: | | | | 1) A LANDSCAPE PERMIT APPLICATION FOR THE BUILDING 6 | | LANDSCAPE INSTALLATION. NOTE AN IRRIGATION PERMIT IS | | REQUIRED FOR THE LANDSCAPE PERMIT TO PASS. | | | | 2) A REVISED SHEET A-3.1 SHOWING THE CORRECT REAR | | ELEVATIONS WITH SLIDING DOORS, NOT WINDOW LEADING OUT | | TO THE PATIO. AN UPDATED LEFT SIDE ELEVATION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
|
|