Plan Review Details - Permit 10070171
Plan Review Stops For Permit 10070171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-08-04 Cont ID  
Sent By rmcdouga Date 2010-08-04 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2010-08-04 Time 11:24 Sent To  
Notes
2010-08-04 11:24:31REVISION REQUIRED
  
 1) THE PRODUCT APPROVALS SUBMITTED FOR THE 8' X 16'
 GARAGE DOOR NEEDS TO BE UPDATED TO THE 2007 CODE
 EDITION. THE DESIGN PRESSURES FOR THE OAK SUMMIT MODEL
 DO NOT MEET THE REQUIRED OPENING PRESSURES FOR EXPOSURE
 C INDICATED ON THE PLANS.
  
 2) SUBMIT THE PRODUCT APPROVAL FOR THE POLYSTICK
 UNDERLAYMENT HAS BEEN SUPERSEDED. SUBMIT THE CURRENT
 PRODUCT APPROVAL WITH NOA NO. 09-0806.07.
  
 NOTE: DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE PRODUCT APPROVALS IN WRITING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-05 Cont ID  
Sent By jleahy Date 2010-08-05 Time 10:02 Rev Time 0.00
Received By jleahy Date 2010-08-05 Time 10:02 Sent To  
Notes
2010-08-05 10:03:07SEE NOTES PAGES E-1.0--- E-1.3 JL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 16:21 Sent To  
Notes
2010-08-18 16:21:46OK PER M. CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-28 Cont ID  
Sent By mcarsill Date 2010-07-28 Time 11:10 Rev Time 0.00
Received By mcarsill Date 2010-07-28 Time 11:10 Sent To  
Notes
2010-07-28 11:10:16OAKTON PRESERVE
 PERMIT NUMBER 10070137
 LOTS35,36,37,38,39,40,41, AND 42
  
 1. PER FLORIDA STATUE 553.885, THE CARBON MONOXIDE
 DETECTORS SHOWN ON THE SECOND FLOORS MUST BE INSTALLED
 WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES.
  
 2. PER FLORIDA STATUE 633.027 "THE OWNER OF ANY
 COMMERCIAL OR INDUSTRIAL STRUCTURE, OR ANY MULT-UNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, THAT USES
 LIGHT-FRAME TRUSS CONSTRUCTION SHALL MARK THE STRUCTURE
 WITH A SIGN APPROVED BY THE STATE FIRE MARSHAL IN A
 MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE
 CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE
 OF LIGHT FRAME TRUSS TYPE CONSTRUCTION IN THE
 STRUCTURE".
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. THE EGRESS WINDOW FOR BEDROOM 2 NOT IDENTIFIED ON
 PAGE TU-2.1.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS IN EACH UNIT.
  
 6. UNITS 35-36 ON PAGE A-3.1. HAVE NO PREMISES
 IDENTIFICATION.
  
 7. PORTABLE FIRE EXTINGUISHERS NOT SHOWN?
  
 8. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST 10 FEET FROM AIR CONDITIONER DIFUSERS.
  
 9. PROVIDE DETAILS ON FIRE RETARDANT COATINGS DESCRIBED
 ON PAGES A-4.1 AND A-4.2.
  
 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2010-07-08 Time 09:22 Sent To  
Notes
2010-07-08 09:22:59C-30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-08-04 Cont ID  
Sent By rmcdouga Date 2010-08-04 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2010-08-04 Time 10:29 Sent To  
Notes
2010-08-04 10:30:13BUILDING #6 - 8 UNIT TOWNHOUSES
  
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER BEDROOM
 SUITE IS UNDER SIZED. FBC R M1602.4 REQUIRES THE
 TRANSFER DUCT TO BE 1.5 TIMES THE SUPPLY, THEREFORE A
 14" DUCT IS REQUIRED.
 PLEASE CORRECT.
  
 2) THE EQUIPMENT MODEL NUMBERS ON THE PLANS AND THE
 SIZING CALCS. DO NOT MATCH FOR THE END UNITS. PLEASE
 CORRECT.
  
 3) THE CU MOUNTING DETAIL ON THE MECHANICAL PLANS
 REFERENCES THE 2004 FBC AND ASCE 02. PLEASE UPDATE TO
 2007 FBC AND ASCE7-05 AND CORRECT THE SECTIONS THAT ARE
 LISTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-08-04 Cont ID  
Sent By rmcdouga Date 2010-08-04 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2010-08-04 Time 10:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-07-27 Cont ID  
Sent By eschneid Date 2010-07-27 Time 10:11 Rev Time 0.25
Received By eschneid Date 2010-07-27 Time 10:11 Sent To  
Notes
2010-07-27 10:11:32PASSED W/PROVISO
  
 A LANDSCAPE FINAL FOR PERMIT NUMBER 10070645 IS
 REQUIRED PRIOR TO THE PRIOR TO CONSTRUCTION SERVICES
 FINAL INSPECTION AND CERTIFICATE OF OCCUPANCY FOR THIS
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-27 Cont ID  
Sent By eschneid Date 2010-07-20 Time 16:04 Rev Time 0.00
Received By eschneid Date 2010-07-20 Time 16:04 Sent To  
Notes
2010-07-20 16:06:42FAILED - WILL PASS UPON THE PROVISION OF THE FOLLOWING:
  
 1) A LANDSCAPE PERMIT APPLICATION FOR THE BUILDING 6
 LANDSCAPE INSTALLATION. NOTE AN IRRIGATION PERMIT IS
 REQUIRED FOR THE LANDSCAPE PERMIT TO PASS.
  
 2) A REVISED SHEET A-3.1 SHOWING THE CORRECT REAR
 ELEVATIONS WITH SLIDING DOORS, NOT WINDOW LEADING OUT
 TO THE PATIO. AN UPDATED LEFT SIDE ELEVATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446