2010-07-14 17:46:29 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. INSTALLATION SCHEDULE STATES THAT CONNECTION TYPE |
| PROPOSED IS C1, BUT THE PRODUCT APPROVAL SUBMITTED DOES |
| NOT HAVE CONNECTION MOUNTING TYPES C1 THROUGH C5 (AS IS |
| TYPICAL ON MANY PRODUCT APPROVALS). THIS PRODUCT |
| APPROVAL IMPLEMENTS A NAMING CONVENTION OF 1 (TOP) |
| THROUGH 5 (BOTTOM). PLEASE REVISE INSTALLATION SCHEDULE |
| TO CORRELATE WITH THE PRODUCT APPROVAL. SEE ANCHOR |
| CHARTS ON PAGE 7. |
| |
| 2. SPECIFIC ANCHOR TYPE IS TO CORRELATE WITH THE |
| PRODUCT APPROVAL. PANELMATES ARE PROPOSED, BUT I WAS |
| UNABLE TO LOCATE THIS ANCHOR TYPE ON THE PRODUCT |
| APPROVAL (HAS TWO DIFFERENT TAPCONS, SOLID SET). IF AN |
| ANCHOR IS PROPOSED WHICH IS NOT INCLUDED IN THE PRODUCT |
| APPROVAL, ENGINEERING REQUIRED. SEE PAGE 7 OF PRODUCT |
| APPROVAL. |
| |
| 3. A 2.5" EDGE DISTANCE IS PROPOSED. PLEASE SEE SHEET |
| 7; A FACTOR OF .71 OR .50 IS TO BE APPLIED TO 2.5" |
| ANCHOR SPACING. |
| |
| 4. SPANS DO NOT APPEAR TO BE CORRECT. FOR INSTANCE, |
| OPENING 15, 34" WIDE OPENING WITH A HORIZONTAL |
| INSTALLATION, 2.5" EDGE DISTANCE, SHOULD HAVE A SPAN OF |
| 39" BUT 44" IS STATED. SOME OPENINGS HAVE A DIFFERENCE |
| OF 20" BETWEEN SPAN AND OPENING SIZE. FOR PANELS, SPANS |
| SHOULD BE THE DISTANCE BETWEEN ANCHORS, TYPICALLY |
| OPENING SIZE PLUS EDGE DISTANCE ON EACH SIDE OF PANEL. |
| |
| ANOTHER EXAMPLE: OPENING 18, 58" WITH 2.5" EDGE |
| DISTANCE, SPAN SHOULD BE 63", BUT 62" IS SPECIFIED. |
| PLEASE CHECK ALL. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE. |
| |