Plan Review Details - Permit 10060862
Plan Review Stops For Permit 10060862
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-01 Cont ID  
Sent By jwitmer Date 2011-03-01 Time 08:50 Rev Time 0.55
Received By jwitmer Date 2011-03-01 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-15 Cont ID  
Sent By jgomez Date 2010-07-15 Time 14:07 Rev Time 0.00
Received By jgomez Date 2010-07-15 Time 14:06 Sent To  
Notes
2010-07-15 14:07:28BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION SUBMITTED IS FOR MECHANICAL AND
 ELECTRICAL PERMITS ONLY. QUALIFIED CONTRACTOR NEEDS TO
 APPLY FOR THE BUILDING PERMIT FOR THE CONSTRUCTION OF
 THE COUNTERTOP BY THE TAKE OUT AREA. UPDATE VALUATION
 TO INCLUDE THE SCOPE OF WORK TO BE DONE BY THE GENERAL
 CONTRACTOR AND THE DESIGN PROFESSIONAL FEES AS REQUIRED
 BY SEC. 108.3 OF CITY AMENDMENTS TO FBC.
  
 2- DRAWING C1:
 A) REVISE CODE ANALYSIS INFORMATION.
 (1) OCCUPANCY CLASSIFICATION IS NOT BUSINESS. SEE
 CHAPTER 3 OF 2007 FBC AND REVISE AS REQUIRED.
 (2) REVISE CONSTRUCTION TYPE. THIS BUILDING IS NOT
 TIMBER CONSTRUCTION. REVISE AS REQUIRED.
 (3) REVISE TOTAL OCCUPANT LOAD SPECIFIED TO INCLUDE THE
 EXISTING RETAIL AREA.. SEE TABLE 1004.1.1 AND REVISE AS
 REQUIRED.
  
 B) REVISE THE MINIMUM INTERIOR FINISH CLASSIFICATION
 TABLE AT THE BOTTOM OF THE GENERAL NOTES COLUMN ON THE
 LEFT BOTTOM OF THE PAGE TO MATCH SPECIFIED OCCUPANCY
 CLASSIFICATION. THIS IS NOT ASSEMBLY TYPE. COORDINATE
 WITH ITEM 2(A)(1) ABOVE.
  
 3- DRAWING A-1: A) SPECIFY ALL DIMENSIONS BY THE TAKE
 OUT COUNTER AREA TO VERIFY COMPLIANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF CHAPTER 11 OF 2007 FBC.
 SHOW THE WHEELCHAIR TURNING SPACE IN FRONT OF DISPLAY
 CABINET AND COUNTERTOP AREA AS REQUIRED BY SEC.
 11-4.2.3 OF 2007 FBC.
  
 B) WALL SHOWN BY EXISTING OFFICE IS NOT SHOWN ON THE
 WALL LEGEND. CLARIFY IF NEW WALL. CHECK WITH CHAPTER 11
 DOOR MANEUVERING REQUIREMENTS.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-14 Cont ID  
Sent By btrobaug Date 2010-07-14 Time 11:30 Rev Time 0.00
Received By btrobaug Date 2010-07-14 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-05-03 Cont ID  
Sent By ddaniels Date 2011-05-03 Time 11:59 Rev Time 0.00
Received By ddaniels Date 2011-05-03 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-26 Cont ID  
Sent By mcarsill Date 2010-07-26 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2010-07-26 Time 13:48 Sent To  
Notes
2010-07-26 14:01:07PERMIT APPLICATION INDICATES HOOD INSTALL, WI FREEZER
 PERMIT NUMBER 10060862
  
  
 1. CONSTRUCTION, DEMOLITIION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF A HOOD,DUCT, AND FIRE SUPPRESSION
 SYSTEM.
  
 3. DOES THE AREA INDICATED AS A NO WORK ON THIS AREA
 EQUIPPPED WITH ANY ILLUMINATED EXIT SIGNS OR EMERGENCY
 LIGHTING EQUIPMENT.
  
 4. GAS INSTALLATION TO COMPLY WITH NFPA 54.
  
 5. SOME DISCREPANCIES EXIST ON THE PLANS AS IDENTIFIED
 BY THE BUILDING PLANS EXAMINER.
  
 6. SEPARATE PLAMS AND PERMITS REQUIRED FOR THE HOOD
 FIRE SUPPRESSION SYSTEM PLANNED FOR THE HOOD.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2010-07-12 Cont ID  
Sent By lwagner Date 2010-07-12 Time 14:34 Rev Time 0.00
Received By lwagner Date 2010-07-12 Time 14:01 Sent To  
Notes
2010-07-12 14:35:06GAS PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-26 Cont ID  
Sent By lmartine Date 2010-07-26 Time 14:41 Rev Time 0.00
Received By lmartine Date 2010-07-01 Time 09:53 Sent To  
Notes
2010-07-14 11:38:28C-19./WRT.
2010-07-06 16:00:42PUT IN PLUMBING BOX
2010-07-01 09:53:37IN MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-07-06 Cont ID  
Sent By hmoser Date 2010-07-06 Time 11:30 Rev Time 0.00
Received By hmoser Date 2010-07-06 Time 09:54 Sent To  
Notes
2010-07-06 11:33:20PROVISO
 PLEASE PROVIDE A LETTER FROM THE ENGINEER ON THE STAND
 TIE DOWN TO THE ROOF , FOR THE ROUGH INSPECTION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-12 Cont ID  
Sent By lwagner Date 2010-07-12 Time 14:47 Rev Time 0.00
Received By lwagner Date 2010-07-12 Time 14:35 Sent To E
Notes
2010-07-12 14:47:17PLUMBING PERMIT REQUIRED
 SUBMIT GREASE TRAP AT 1ST INSPECTION

Review Stop Z ZONING
Rev No 2 Status P Date 2011-03-03 Cont ID  
Sent By astelly Date 2011-03-03 Time 17:10 Rev Time 0.00
Received By astelly Date 2011-03-03 Time 17:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-21 Cont ID  
Sent By kdfreema Date 2010-07-21 Time 11:31 Rev Time 0.00
Received By kdfreema Date 2010-07-21 Time 11:31 Sent To  
Notes
2010-07-21 13:34:45***FAILED***
  
 1. SHEET A-1, FLOOR PLAN, SHOWS A DOOR TO BE CLOSED.
 PLEASE PROVIDE DETAILS. NOTE THAT SECTION 94-221(D)(5)
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 REQUIRES A MINIMUM OF 70 PERCENT OF THE FACADE OF THE
 BUILDING BETWEEN 2 AND 8 FEET TO BE CLEAR GLAZED.
 ALTHOUGH THE STRUCTURE IS BELOW THE REQUIRED 70
 PERCENT, YOU MAY GO NO LOWER THAN WHAT IS PROVIDED
 TODAY. IF THERE IS GLAZING INCORPORATED INTO THE DOOR
 TO BE REMOVED, AN AMOUNT OF GLAZING EQUAL OR GREATER
 THAN THAT IN THE DOOR MUST BE PROVIDED.
  
 2. SECTION 94-221(D)(8) REQUIRES THAT MECHANICAL
 SYSTEMS BE SCREENED FROM VIEW ON ALL SIDES TO THE FULL
 HEIGHT OF THE EQUIPMENT BY BUILT ELEMENTS.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 OR [email protected] WITH QUESTIONS.