Plan Review Stops For Permit 10060735 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2010-06-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-06-29 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-06-29 |
Time |
13:43 |
Sent To |
|
|
Notes |
2010-06-29 14:00:42 | 1901 NORTH FLAGLER DRIVE | | PERMIT NUMBER 10060735 | | ADD TO EXISTING FIRE ALARM SYSTEM PER ATTACHED PLANS | | PLANS INDICATE PLANS INDICATE PHASE II, MINOR | | REMODELING, CLASSROOM & OFFICE AREAS | | | | | | 1. ON JUNE 29, 2010, THIS WRITER SPOKE TO DAVE SUMMERS | | OF PULSAR CONCEPTS, INC. ACCORDING TO DAVE SUMMERS AREA | | 3 ON THE KEY PLAN WILL BE EQUIPPED WITH VOICE | | EVACUATION DUE TO THE OCCUPANCY TYPE AND SIZE. HE | | FURTHER ADVISED THAT THE DIFFERENT AREAS ON THE KEY | | PLAN ARE CONNECTED BY EXTERIOR WALKWAYS. | | | | 2. THE FIRE ALARM INSTALLATION TO COMPLY WITH NFPA 72, | | THE NATIONAL FIRE ALARM CODE. | | | | 3. WHEN COMPLETED THE SYSTEM IS TO BE TESTED WITH | | REPRESENTATIVES OF THIS OFFICE. | | | | 4. FIRE ALARM SYSTEM IS TO BE AUDIBLE THROUGHOUT THE | | BUILDING. | | | | | | APPROVED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2010-06-29 |
Time |
|
Rev Time |
0.00 |
Received By |
vmolina |
Date |
2010-06-24 |
Time |
08:23 |
Sent To |
|
|
Notes |
2010-06-28 08:24:10 | IN FIRE BOX |
|
|
|