Plan Review Details - Permit 10060663
Plan Review Stops For Permit 10060663
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 10:58 Rev Time 0.00
Received By wjolin Date 2010-07-23 Time 10:58 Sent To  
Notes
2010-07-23 10:58:39*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-28 Cont ID  
Sent By mawillia Date 2010-06-28 Time 12:36 Rev Time 0.00
Received By mawillia Date 2010-06-28 Time 10:32 Sent To  
Notes
2010-06-28 12:35:32*****DENIED*****
  
 1) SOUTHWEST AREA OF GRILL #109 DOES NOT HAVE SPRINKLER
 COVERAGE. CLOSEST SPRINKLER IS LOCATED ON OPPOSITE SIDE
 OF WALL.
  
 2) ROOM LABELED COMFORT #108 NEAR COLUMN INTERSECTION
 10/G FEATURES A WALL WITH AN ELECTRICAL PANEL. THE
 SPRINKLER IS LOCATED 10'-0" FROM THE WALL.
  
 3) ARCHITECTURAL CEILING DETAIL FOR COMFORT #108 INFERS
 CEILING DOES NOT ENCLOSE THE ENTIRE ROOM. VERIFY
 CEILING IS NOT OPEN TO STRUCTURE ABOVE FLOATING SLOPED
 CLOUDS. IF CEILING HAS OPENINGS, PROVIDE SPRINKLER
 PROTECTION ABOVE CEILING.
  
 4) THE 11'-0" RECTANGULAR CEILING WITH AN OVAL INTERIOR
 CEILING OF 9'-1" AND 8'-0" ONLY PROVIDES SPRINKLER
 PROTECTION FOR THE 9'-1" CEILING. THE FLOOR AREA BELOW
 THE 11'-0" AND 8'-0" CEILINGS ARE UNPROTECTED.
 ADDITIONAL SPRINKLERS MAY REQUIRE A SEPARATE BRANCH
 LINE TO AVOID OVER TAXING THE EXISTING BRANCH LINES.
  
 5) PROVIDE NOTE ON THE DRAWING STATING AREAS OF EXPOSED
 STRUCTURE ARE CONSIDERED OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-13 Cont ID  
Sent By vmolina Date 2010-07-13 Time 08:56 Rev Time 0.00
Received By vmolina Date 2010-07-13 Time 08:56 Sent To  
Notes
2010-07-13 08:56:19IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-13 Cont ID  
Sent By vmolina Date 2010-06-28 Time 08:55 Rev Time 0.00
Received By vmolina Date 2010-06-23 Time 10:43 Sent To  
Notes
2010-06-23 10:43:30IN FIRE BOX