Plan Review Details - Permit 10060646
Plan Review Stops For Permit 10060646
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-09-16 Cont ID  
Sent By rmcdouga Date 2010-09-16 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2010-09-16 Time 16:56 Sent To  
Notes
2010-09-16 17:08:25PROVISO
  
 SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR PORCH ROOF
 COVERING MATERIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-25 Cont ID  
Sent By rmcdouga Date 2010-08-25 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2010-08-25 Time 13:33 Sent To  
Notes
2010-08-25 15:39:522007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF
 COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS,
 STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS
 REQUIRED BY DCA RULE 9B-72.
  
 2) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A
 KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED.
 THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT
 TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL
 REQUIRED.
  
 3) THE SIMPSON CONNECTORS SPECIFIED FOR THE 4 X 4 PORCH
 APPEAR TO BE TYPOGRAPHICAL ERRORS. IT APPEARS THEY
 SHOULD BE ACE4 AND EPB44T. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-22 Cont ID  
Sent By rmcdouga Date 2010-06-22 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2010-06-22 Time 14:47 Sent To  
Notes
2010-06-22 16:52:472007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF STRUCTURAL PLANS FOR THE FRONT
 PORCH. SPECIFY ALL STRAPS AND CONNECTORS. SHOW THAT
 CONSTRUCTION COMPLIES WITH WINDLOADS AND THAT A
 CONTINUOUS LOAD PATH FROM THE ROOF TO THE FOUNDATION IS
 PROVIDED. SPECIFY ROOF PITCH, ROOF FRAMING, ROOF
 SHEATHING, SHEATHING FASTENERS & SPACING, ROOF
 COVERING, HEADER AND COLUMN SIZES AND ATTACHMENTS. SHOW
 ALL DIMENSIONS ON THE PLANS. SPECIFY THE DESIGN
 CRITERIA ON THE PLANS.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF
 COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS,
 STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS
 REQUIRED BY DCA RULE 9B-72.
  
 3) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE NEW
 WINDOW TYPES, SIZES AND LOCATIONS. INDICATE WHICH
 WINDOWS WILL BE MULLED TOGETHER. IDENTIFY THE ROOMS ON
 THE FLOOR PLAN, SUCH AS BEDROOM, BATHROOM, ETC.
  
 4) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A
 KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED.
 THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT
 TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL
 REQUIRED.
  
 5) TWO COPIES OF A SURVEY OR SITE PLAN INDICATING THE
 DISTANCE TO PROPERTY LINES OF THE PORCH ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-11 Cont ID  
Sent By shill Date 2010-08-11 Time 18:22 Rev Time 0.00
Received By shill Date 2010-08-11 Time 18:22 Sent To  
Notes
2010-08-11 18:23:32OK PER JOHN DICKINSON (CONTRACT REVIEWER)
 PX3182
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-23 Cont ID  
Sent By btrobaug Date 2010-06-23 Time 13:42 Rev Time 0.00
Received By btrobaug Date 2010-06-23 Time 13:31 Sent To Z
Notes
2010-06-23 13:40:01 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE LOCATION
 OF ALL EQUIPMENT AND DEVICES BEING INSTALLED UNDER THE
 SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-16 Cont ID  
Sent By rmcdouga Date 2010-09-16 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2010-08-31 Time 09:30 Sent To  
Notes
2010-08-31 09:31:13SENT TO R-2.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-25 Cont ID  
Sent By rmcdouga Date 2010-08-25 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2010-08-09 Time 10:01 Sent To  
Notes
2010-08-09 10:02:07TO R-7.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-15 Cont ID  
Sent By lmartine Date 2010-07-02 Time 16:16 Rev Time 0.00
Received By lmartine Date 2010-06-22 Time 12:01 Sent To  
Notes
2010-06-22 12:02:33IN PLUMBING BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-09-16 Cont ID  
Sent By rmcdouga Date 2010-09-16 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2010-09-16 Time 15:12 Sent To  
Notes
2010-09-16 16:56:38PROVISO
  
 1) THE TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF
 GRILL AREA TO 100 CFM FOR SIZING THROUGH THE WALL
 TRANSFER GRILLS TO ACHIEVE PROPER RETURN AIR BALANCE AS
 REQUIRED BY FBC M1602.4.
  
 2) NO RETURN AIR SHALL BE TAKEN FROM THE UTILITY ROOM.
 THE RETURN AIR FROM THE HALL SHALL BE DUCTED DIRECTLY
 TO THE AIR HANDLER PER FBC R M1602.2 (4).

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-08-25 Cont ID  
Sent By rmcdouga Date 2010-08-25 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2010-08-25 Time 15:40 Sent To  
Notes
2010-08-25 15:55:29DENIED BY MECHANICAL
  
 COMMENTS OF FIRST REVIEW WERE NOT ADDRESSED. SEE
 COMMENTS FROM PREVIOUS REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-22 Cont ID  
Sent By rmcdouga Date 2010-06-22 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2010-06-22 Time 14:05 Sent To  
Notes
2010-06-22 14:47:462007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS USING A CODE APPROVED METHOD AS
 REQUIRED BY FBC R M1401.3.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 STRUCTURE.
  
 3) SUBMIT 2 SETS OF MECHANICAL PLANS. SPECIFY THE
 SUPPLY AND RETURN DUCT SIZES, GRILL SIZES, LOCATIONS,
 CFMS. SPECIFY THE LOCATIONS OF THE AHU AND CONDENSER
 WITH REQUIRED DISCONNECTS AND SERVICE OUTLETS. SHOW
 COMPLIANCE WITH FBC R M1602.4 FOR BALANCED RETURN AIR.
 SPECIFY THE HVAC EQUIPMENT THAT WILL BE INSTALLED ON
 THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-08-25 Cont ID  
Sent By rmcdouga Date 2010-08-25 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2010-08-25 Time 16:39 Sent To  
Notes
2010-08-25 16:40:32REPLACE EXISTING FIXTURES IN SAME LOCATIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-22 Cont ID  
Sent By rmcdouga Date 2010-06-22 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2010-06-22 Time 14:04 Sent To E
Notes
2010-06-22 14:05:25REPLACE FIXTURES IN SAME LOCATIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2010-09-16 Cont ID  
Sent By lfranco Date 2010-09-16 Time 15:54 Rev Time 0.00
Received By lfranco Date 2010-09-16 Time 15:54 Sent To B
Notes
2010-09-16 15:55:07PLANNING AND ZONING: **** PASSED - PORCH ENCROACHMENT
 WITHIN FRONT SETBACK APPROVED BY CHARLES WU, PLANNING
 DIRECTOR - BASED ON COMPARISON OF GREEN CARD BUILDING
 DIMENSIONS AND SUBMITTED SURVEY. ****
  
  
  
 PREVIOUS COMMENTS BELOW ADDRESSED 9/16/10:
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE
 PROPERTY LINE. PURSUANT TO THE ZONING AND LAND
 DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY
 ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE
 MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH,
 WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT
 SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING
 STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED
 FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE
 REQUIRED SETBACK.
  
 IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR
 THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT
 SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD
 APPEALS.
  
 PLEASE CONTACT ME FOR FURTHER INFORMATION.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-08-20 Cont ID  
Sent By lfranco Date 2010-08-20 Time 19:28 Rev Time 0.50
Received By lfranco Date 2010-08-20 Time 19:14 Sent To  
Notes
2010-09-16 15:54:01PLANNING AND ZONING: **** PASSED PER CHARLES WU,
 PLANNING DIRECTOR - BASED ON COMPARISON OF GREEN CARD
 BUILDING DIMENSIONS AND SUBMITTED SURVEY. ****
  
  
  
 PREVIOUS COMMENTS BELOW ADDRESSED 9/16/10:
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE
 PROPERTY LINE. PURSUANT TO THE ZONING AND LAND
 DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY
 ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE
 MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH,
 WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT
 SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING
 STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED
 FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE
 REQUIRED SETBACK.
  
 IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR
 THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT
 SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD
 APPEALS.
  
 PLEASE CONTACT ME FOR FURTHER INFORMATION.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
2010-08-20 19:39:17PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE
 PROPERTY LINE. PURSUANT TO THE ZONING AND LAND
 DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY
 ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE
 MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH,
 WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT
 SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING
 STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED
 FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE
 REQUIRED SETBACK.
  
 IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR
 THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT
 SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD
 APPEALS.
  
 PLEASE CONTACT ME FOR FURTHER INFORMATION.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-02 Cont ID  
Sent By lfranco Date 2010-07-02 Time 17:57 Rev Time 0.00
Received By lfranco Date 2010-07-02 Time 17:57 Sent To I
Notes
2010-07-02 18:01:13PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. THERE WERE NO PLANS SUBMITTED WITH PERMIT;
 THEREFORE, UNABLE TO REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  