Plan Review Stops For Permit 10060646 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-09-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-09-16 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-09-16 |
Time |
16:56 |
Sent To |
|
|
Notes |
2010-09-16 17:08:25 | PROVISO | | | | SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR PORCH ROOF | | COVERING MATERIAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-25 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-25 |
Time |
13:33 |
Sent To |
|
|
Notes |
2010-08-25 15:39:52 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF | | COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS, | | STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS | | REQUIRED BY DCA RULE 9B-72. | | | | 2) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A | | KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED. | | THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT | | TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL | | REQUIRED. | | | | 3) THE SIMPSON CONNECTORS SPECIFIED FOR THE 4 X 4 PORCH | | APPEAR TO BE TYPOGRAPHICAL ERRORS. IT APPEARS THEY | | SHOULD BE ACE4 AND EPB44T. PLEASE CLARIFY. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-06-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:47 |
Sent To |
|
|
Notes |
2010-06-22 16:52:47 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO SETS OF STRUCTURAL PLANS FOR THE FRONT | | PORCH. SPECIFY ALL STRAPS AND CONNECTORS. SHOW THAT | | CONSTRUCTION COMPLIES WITH WINDLOADS AND THAT A | | CONTINUOUS LOAD PATH FROM THE ROOF TO THE FOUNDATION IS | | PROVIDED. SPECIFY ROOF PITCH, ROOF FRAMING, ROOF | | SHEATHING, SHEATHING FASTENERS & SPACING, ROOF | | COVERING, HEADER AND COLUMN SIZES AND ATTACHMENTS. SHOW | | ALL DIMENSIONS ON THE PLANS. SPECIFY THE DESIGN | | CRITERIA ON THE PLANS. | | | | 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF | | COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS, | | STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS | | REQUIRED BY DCA RULE 9B-72. | | | | 3) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE NEW | | WINDOW TYPES, SIZES AND LOCATIONS. INDICATE WHICH | | WINDOWS WILL BE MULLED TOGETHER. IDENTIFY THE ROOMS ON | | THE FLOOR PLAN, SUCH AS BEDROOM, BATHROOM, ETC. | | | | 4) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A | | KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED. | | THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT | | TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL | | REQUIRED. | | | | 5) TWO COPIES OF A SURVEY OR SITE PLAN INDICATING THE | | DISTANCE TO PROPERTY LINES OF THE PORCH ARE REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-08-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-08-11 |
Time |
18:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-08-11 |
Time |
18:22 |
Sent To |
|
|
Notes |
2010-08-11 18:23:32 | OK PER JOHN DICKINSON (CONTRACT REVIEWER) | | PX3182 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-06-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-06-23 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-06-23 |
Time |
13:31 |
Sent To |
Z |
|
Notes |
2010-06-23 13:40:01 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE LOCATION | | OF ALL EQUIPMENT AND DEVICES BEING INSTALLED UNDER THE | | SCOPE OF THIS APPLICATION.106.1.1 FBC. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-09-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-09-16 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-31 |
Time |
09:30 |
Sent To |
|
|
Notes |
2010-08-31 09:31:13 | SENT TO R-2. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-25 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-09 |
Time |
10:01 |
Sent To |
|
|
Notes |
2010-08-09 10:02:07 | TO R-7. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-07-15 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-07-02 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-06-22 |
Time |
12:01 |
Sent To |
|
|
Notes |
2010-06-22 12:02:33 | IN PLUMBING BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2010-09-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-09-16 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-09-16 |
Time |
15:12 |
Sent To |
|
|
Notes |
2010-09-16 16:56:38 | PROVISO | | | | 1) THE TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF | | GRILL AREA TO 100 CFM FOR SIZING THROUGH THE WALL | | TRANSFER GRILLS TO ACHIEVE PROPER RETURN AIR BALANCE AS | | REQUIRED BY FBC M1602.4. | | | | 2) NO RETURN AIR SHALL BE TAKEN FROM THE UTILITY ROOM. | | THE RETURN AIR FROM THE HALL SHALL BE DUCTED DIRECTLY | | TO THE AIR HANDLER PER FBC R M1602.2 (4). |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-25 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-25 |
Time |
15:40 |
Sent To |
|
|
Notes |
2010-08-25 15:55:29 | DENIED BY MECHANICAL | | | | COMMENTS OF FIRST REVIEW WERE NOT ADDRESSED. SEE | | COMMENTS FROM PREVIOUS REVIEW. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-06-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:05 |
Sent To |
|
|
Notes |
2010-06-22 14:47:46 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS USING A CODE APPROVED METHOD AS | | REQUIRED BY FBC R M1401.3. | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | STRUCTURE. | | | | 3) SUBMIT 2 SETS OF MECHANICAL PLANS. SPECIFY THE | | SUPPLY AND RETURN DUCT SIZES, GRILL SIZES, LOCATIONS, | | CFMS. SPECIFY THE LOCATIONS OF THE AHU AND CONDENSER | | WITH REQUIRED DISCONNECTS AND SERVICE OUTLETS. SHOW | | COMPLIANCE WITH FBC R M1602.4 FOR BALANCED RETURN AIR. | | SPECIFY THE HVAC EQUIPMENT THAT WILL BE INSTALLED ON | | THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2010-08-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-25 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-25 |
Time |
16:39 |
Sent To |
|
|
Notes |
2010-08-25 16:40:32 | REPLACE EXISTING FIXTURES IN SAME LOCATIONS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2010-06-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-22 |
Time |
14:04 |
Sent To |
E |
|
Notes |
2010-06-22 14:05:25 | REPLACE FIXTURES IN SAME LOCATIONS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2010-09-16 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-09-16 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2010-09-16 |
Time |
15:54 |
Sent To |
B |
|
Notes |
2010-09-16 15:55:07 | PLANNING AND ZONING: **** PASSED - PORCH ENCROACHMENT | | WITHIN FRONT SETBACK APPROVED BY CHARLES WU, PLANNING | | DIRECTOR - BASED ON COMPARISON OF GREEN CARD BUILDING | | DIMENSIONS AND SUBMITTED SURVEY. **** | | | | | | | | PREVIOUS COMMENTS BELOW ADDRESSED 9/16/10: | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE | | PROPERTY LINE. PURSUANT TO THE ZONING AND LAND | | DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY | | ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE | | MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH, | | WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT | | SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING | | STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED | | FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE | | REQUIRED SETBACK. | | | | IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR | | THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT | | SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND | | ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD | | APPEALS. | | | | PLEASE CONTACT ME FOR FURTHER INFORMATION. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2010-08-20 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-08-20 |
Time |
19:28 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2010-08-20 |
Time |
19:14 |
Sent To |
|
|
Notes |
2010-09-16 15:54:01 | PLANNING AND ZONING: **** PASSED PER CHARLES WU, | | PLANNING DIRECTOR - BASED ON COMPARISON OF GREEN CARD | | BUILDING DIMENSIONS AND SUBMITTED SURVEY. **** | | | | | | | | PREVIOUS COMMENTS BELOW ADDRESSED 9/16/10: | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE | | PROPERTY LINE. PURSUANT TO THE ZONING AND LAND | | DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY | | ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE | | MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH, | | WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT | | SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING | | STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED | | FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE | | REQUIRED SETBACK. | | | | IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR | | THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT | | SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND | | ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD | | APPEALS. | | | | PLEASE CONTACT ME FOR FURTHER INFORMATION. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | | | | 2010-08-20 19:39:17 | PLANNING AND ZONING: **** FAILED **** | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. THE SURVEY SHOWS BUILDING AT 7.30' TO 7.92' FROM THE | | PROPERTY LINE. PURSUANT TO THE ZONING AND LAND | | DEVELOPMENT ("ZLDR"), SECTION 94-73 - SINGLE FAMILY | | ("SF11"), HIGH DENSITY RESIDENTIAL DISTRICT, THE | | MINIMUM FRONT SETBACK IS 20 FEET OR 20% OF LOT DEPTH, | | WHICHEVER IS LESS; IN THIS CASE THE MINIMUM FRONT FRONT | | SETBACK IS 18 FEET. THE PROPERTY IS A NON-CONFORMING | | STRUCTURE. CLARIFY IF AND WHEN A PERMIT WAS OBTAINED | | FOR THE PORCH OR THE HOME TO BE PLACED WITHIN THE | | REQUIRED SETBACK. | | | | IF NO PROOF OF PERMITS CAN BE OBTAINED, A PERMIT FOR | | THE PORCH WILL NOT BE ALLOWED, UNLESS A VARIANCE (FRONT | | SETBACK) APPLICATION IS SUBMITTED TO THE PLANNING AND | | ZONING DEPARTMENT AND APPROVED BY THE ZONING BOARD | | APPEALS. | | | | PLEASE CONTACT ME FOR FURTHER INFORMATION. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-07-02 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-07-02 |
Time |
17:57 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2010-07-02 |
Time |
17:57 |
Sent To |
I |
|
Notes |
2010-07-02 18:01:13 | PLANNING AND ZONING: **** FAILED **** | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | 3. THERE WERE NO PLANS SUBMITTED WITH PERMIT; | | THEREFORE, UNABLE TO REVIEW. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | | | |
|
|