Plan Review Details - Permit 10060636
Plan Review Stops For Permit 10060636
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 07:51 Rev Time 0.00
Received By btrobaug Date 2010-06-30 Time 07:48 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-24 Cont ID  
Sent By btrobaug Date 2010-06-24 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2010-06-24 Time 10:20 Sent To  
Notes
2010-06-24 10:21:19 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE.
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE
 SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS
 ARE NOT PROVIDED WITH OVERCURRENT PROTECTION WHERE THEY
 RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST
 OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE
 DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF
 CURRENT THAT COULD BE IMPOSED ON FEEDER OR
 BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME
 RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN
 THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT
 CONDUCTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 07:51 Rev Time 0.00
Received By btrobaug Date 2010-06-28 Time 10:14 Sent To PC
Notes
2010-06-28 10:14:36IN ELECTRICAL BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved