Plan Review Details - Permit 10060598
Plan Review Stops For Permit 10060598
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By jleahy Date 2010-08-18 Time 13:47 Rev Time 0.00
Received By jleahy Date 2010-08-18 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-07-23 Cont ID  
Sent By lfranco Date 2010-07-23 Time 08:34 Rev Time 0.00
Received By jleahy Date 2010-08-18 Time 13:50 Sent To P
Notes
2010-07-23 08:33:48 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SUBMIT A SITE PLAN AND LOCATE ALL THE SERVICE AND
 GENERATOR GEAR ON SAME SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE DISCONNECTING MEANS
 REQUIREMENTS AND 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 2} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.THE LOAD CALC'S ARE AT 70 AMPS, THE GENERATOR IS
 RATED FOR 65 AMPS. CORRECT THE LOADS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By lwagner Date 2010-08-18 Time 12:45 Rev Time 0.00
Received By lwagner Date 2010-08-18 Time 12:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-07-27 Cont ID  
Sent By btrobaug Date 2010-07-27 Time 11:47 Rev Time 0.00
Received By lwagner Date 2010-07-27 Time 11:44 Sent To  
Notes
2010-07-27 11:46:53FBC GAS REVIEW
 DENIED:
  
 1. LOCATIONS FOR TANK AND GENERATOR HAVE NOT BEEN
 APPROVED BY ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-04 Cont ID  
Sent By lmartine Date 2010-08-04 Time 18:03 Rev Time 0.00
Received By lmartine Date 2010-08-04 Time 18:03 Sent To  
Notes
2010-08-04 18:05:36IN ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-27 Cont ID  
Sent By lwagner Date 2010-07-27 Time 11:47 Rev Time 0.00
Received By lwagner Date 2010-06-21 Time 11:27 Sent To  
Notes
2010-06-22 11:27:27IN ZONING BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2010-08-16 Cont ID  
Sent By lfranco Date 2010-08-13 Time 17:15 Rev Time 0.00
Received By lfranco Date 2010-08-06 Time 15:28 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-07-14 Cont ID  
Sent By lfranco Date 2010-07-14 Time 10:15 Rev Time 0.00
Received By lfranco Date 2010-07-14 Time 09:45 Sent To B
Notes
2010-07-15 09:24:11PLANNING AND ZONING: **** FAILED - COMMENTS NOT
 ADDRESSED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED MECHANICAL
 EQUIPMENT (GENERATOR AND LP TANK) TO ALL PROPERTY
 LINES. AS PER SECTION 94-305(B)(4) OF THE ZONING CODE
 ("ZLDR"): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. SHOW GENERATOR TO
 SCALE ON SURVEY AND/OR A SCALED SITE PLAN. CLEARLY SHOW
 DIMENSIONS ON SURVEY. ALTHOUGH LP TANK WILL BE
 UNDERGROUND, THE SETBACKS AND ENCROACHMENT ALLOWANCE
 STILL APPLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-01 Cont ID  
Sent By lfranco Date 2010-07-01 Time 18:41 Rev Time 0.00
Received By lfranco Date 2010-06-23 Time 11:11 Sent To B
Notes
2010-07-01 18:46:33PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. AS PER SECTION
 94-305(B)(4) OF THE ZONING CODE ("ZLDR"): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK. SHOW GENERATOR TO SCALE ON SURVEY
 AND/OR A SCALED SITE PLAN.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  