Plan Review Details - Permit 10060582
Plan Review Stops For Permit 10060582
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-14 Cont ID  
Sent By shill Date 2010-07-14 Time 15:45 Rev Time 0.00
Received By shill Date 2010-07-14 Time 15:45 Sent To  
Notes
2010-07-14 15:48:48****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ALL EXIT DOORS EXCLUDED FROM SCOPE OF WORK FOR THIS
 PERMIT.
  
 2. AS DISCUSSED WITH CONTRACTOR, A REVISION IS REQUIRED
 IN ORDER TO INCLUDE DOORS IN THE SCOPE OF WORK. PROVIDE
 A LIFE SAFETY PLAN. SEE FBC 1003.6, MEANS OF EGRESS
 CONTINUITY. THE PATH OF EGRESS TRAVEL ALONG A MEANS OF
 EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT
 OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN
 THIS CHAPTER. OBSTRUCTIONS SHALL NOT BE PLACED IN THE
 REQUIRED WIDTH OF A MEANS OF EGRESS EXCEPT PROJECTIONS
 PERMITTED BY THIS CHAPTER.
  
 A MINIMUM OF TWO EXITS WHICH COMPLY WITH FBC CHAPTER 10
 ARE REQUIRED:
  
 EXITS TO BE REMOTELY LOCATED (MINIMUM 1/2 THE DIAGONAL
 APART)
 TRAVEL DISTANCE TO BE 200' OR LESS TO THE NEAREST EXIT
 FROM ANY POINT IN THE BUILDING ALONG THE PATH OF TRAVEL
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-06 Cont ID  
Sent By shill Date 2010-07-06 Time 08:52 Rev Time  
Received By shill Date 2010-06-23 Time 20:50 Sent To  
Notes
2010-07-06 09:10:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DECLARE OCCUPANCY; OUR RECORDS SHOW THIS AS A2.
  
 2. PROVIDE A LIFE SAFETY PLAN. SEE FBC 1003.6, MEANS OF
 EGRESS CONTINUITY. THE PATH OF EGRESS TRAVEL ALONG A
 MEANS OF EGRESS SHALL NOT BE INTERRUPTED BY ANY
 BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT
 AS SPECIFIED IN THIS CHAPTER. OBSTRUCTIONS SHALL NOT BE
 PLACED IN THE REQUIRED WIDTH OF A MEANS OF EGRESS
 EXCEPT PROJECTIONS PERMITTED BY THIS CHAPTER. IT
 APPEARS THAT YOU PROPOSE TO BLOCK REQUIRED EXIT DOORS
 WITH SHUTTERS.
  
 ONE OF THE "EGRESS" DOORS SHOWN ON THE PLAN IS THE DOOR
 TO AN ELECTRIC ROOM (NO ACCESS FROM THE INSIDE OF THE
 BUILDING). ANOTHER IS A STORAGE ROOM, AND THE THIRD IS
 A KILN ROOM. HAVE THERE BEEN CHANGES TO THE FLOOR PLAN
 SINCE THE BUILDING WAS CONSTRUCTED?

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-14 Cont ID  
Sent By vmolina Date 2010-07-14 Time 08:35 Rev Time 0.00
Received By vmolina Date 2010-07-12 Time 08:35 Sent To  
Notes
2010-07-14 08:35:18IN MISC.1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-06 Cont ID  
Sent By shill Date 2010-07-06 Time 09:16 Rev Time 0.00
Received By shill Date 2010-06-21 Time 11:37 Sent To  
Notes
2010-06-22 11:38:05IN MISC.1 BOX


Account Summary | Usage Policy | Privacy Policy