Plan Review Details - Permit 10060529
Plan Review Stops For Permit 10060529
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-28 Cont ID  
Sent By jwitmer Date 2010-06-28 Time 11:57 Rev Time 3.33
Received By jwitmer Date 2010-06-28 Time 09:03 Sent To  
Notes
2010-06-28 11:10:05BUILDING PLAN REVIEW
 PERMIT: 10060529
 ADD: 2616 E TAMARIND AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: (561)832-9700
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A2.1 INDICATES A NEW INTERIOR STAIR WITHOUT A
 1 HR ENCLOSURE, THIS DOES MEET FBC-B1020.1 EXCEPTION
 #8. THE PROBLEM WILL BE THE NEW EXTERIOR STAIRWAY WILL
 NEED TO MEET THE REQUIREMENTS OF 1023.6 EXTERIOR
 STAIRWAYS SHALL BE SEPERATED FROM THE INTERIOR OF THE
 BUILDING AS REQUIRED BY SECTION 1020.1.
  
 2) SHEET A2.1 THE NEW EXTERIOR STAIRS INDICATE A NEW
 PRE-FAB STAIR AND RAILING BUT THERE IS NO DESIGN
 CRITERIA PROVIDED, FBC 1607.1(36) 100 LBS LIVE LOAD,
 1010, 1012 & 1013.
  
 3) SHEET A2.1 PLEASE PROVIDE BUILDING TYPE OF
 CONSTRUCTION AND LEVEL OF ALTERATION. WE WILL NEED THIS
 INFORMATION TO DETERMINE TYPE OF CONSTRUCTION REQUIRED
 (FBC-B1009.5) FOR THE STAIRS. PLANS FAIL TO PROVIDE
 TTHE FOLLOWING INFORMATION COMPLIANCE WITH 1010, 1012 &
 1013.
  
 4) FL EXISTING BUILDING CODE 706.1 ACCESSIBILITY
 PLANS FAIL TO PROVIDE VERTICAL ACCESSIBILITY AS PER
 FBC-B 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS (1)
 (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
  
 PLEASE REVIEW 11-4.1.3(5) THTE FLORIDA SPECIFIC GRAY
 BOX AND EXCEPTION 4: PLATFORM LIFTS (WHEELCHAIR LIFTS)
 COMPLYING WITH SECTION 11-4.11 OF THIS CODE MAY BE USED
 IN LIEU OF AN ELEVATOR WHERE THIS SECTION WOULD REQUIRE
 AN ELEVATOR ONLY UNDER THE FOLLOWING CONDITIONS:
  
 (A) TO PROVIDE AN ACCESSIBLE ROUTE TO A PERFORMING AREA
 IN AN ASSEMBLY OCCUPANCY.
  
 (B) TO COMPLY WITH THE WHEELCHAIR VIEWING POSITION
 LINE-OF-SIGHT AND DISPERSION REQUIREMENTS OF SECTION
 11-4.13.
  
 (C) TO PROVIDE ACCESS TO INCIDENTAL OCCUPIABLE SPACES
 AND ROOMS WHICH ARE NOT OPEN TO THE GENERAL PUBLIC AND
 WHICH HOUSE NO MORE THAN FIVE PERSONS, INCLUDING BUT
 NOT LIMITED TO EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS.
  
 (D) TO PROVIDE ACCESS WHERE EXISTING SITE CONSTRAINTS
 OR OTHER CONSTRAINTS MAKE USE OF A RAMP OR AN ELEVATOR
 INFEASIBLE.
  
 5) FL EXISTING BUILDING CODE 706.1 ACCESSIBILITY
 11-4.3.11 AREAS OF RESCUE ASSISTANCE.
  
 11-4.3.11.1 LOCATION AND CONSTRUCTION. AN AREA OF
 RESCUE ASSISTANCE SHALL BE ONE OF THE FOLLOWING:
  
 (1) A PORTION OF A STAIRWAY LANDING WITHIN A SMOKEPROOF
 ENCLOSURE (COMPLYING WITH LOCAL REQUIREMENTS).
  
 (2) A PORTION OF AN EXTERIOR EXIT BALCONY LOCATED
 IMMEDIATELY ADJACENT TO AN EXIT STAIRWAY WHEN THE
 BALCONY COMPLIES WITH LOCAL REQUIREMENTS FOR EXTERIOR
 EXIT BALCONIES. OPENINGS TO THE INTERIOR OF THE
 BUILDING LOCATED WITHIN 20 FEET (6 M) OF THE AREA OF
 RESCUE ASSISTANCE SHALL BE PROTECTED WITH FIRE
 ASSEMBLIES HAVING A 3/4 HOUR FIRE PROTECTION RATING.
  
 (3) A PORTION OF A 1-HOUR FIRE-RESISTIVE CORRIDOR
 (COMPLYING WITH LOCAL REQUIREMENTS FOR FIRE-RESISTIVE
 CONSTRUCTION AND FOR OPENINGS) LOCATED IMMEDIATELY
 ADJACENT TO AN EXIT ENCLOSURE.
  
 (4) A VESTIBULE LOCATED IMMEDIATELY ADJACENT TO AN EXIT
 ENCLOSURE AND CONSTRUCTED TO THE SAME FIRE-RESISTIVE
 STANDARDS AS REQUIRED FOR CORRIDORS AND OPENINGS.
  
 (5) A PORTION OF A STAIRWAY LANDING WITHIN AN EXIT
 ENCLOSURE WHICH IS VENTED TO THE EXTERIOR AND IS
 SEPARATED FROM THE INTERIOR OF THE BUILDING WITH NOT
 LESS THAN 1-HOUR FIRE-RESISTIVE DOORS.
  
 (6) WHEN APPROVED BY THE APPROPRIATE LOCAL AUTHORITY,
 AN AREA OR A ROOM WHICH IS SEPARATED FROM OTHER
 PORTIONS OF THE BUILDING BY A SMOKE BARRIER. SMOKE
 BARRIERS SHALL HAVE A FIRE-RESISTIVE RATING OF NOT LESS
 THAN ONE HOUR AND SHALL COMPLETELY ENCLOSE THE AREA OR
 ROOM. DOORS IN THE SMOKE BARRIER SHALL BE TIGHT-FITTING
 SMOKE-AND-DRAFT CONTROL ASSEMBLIES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 20 MINUTES AND SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING. THE AREA OR ROOM
 SHALL BE PROVIDED WITH AN EXIT DIRECTLY TO AN EXIT
 ENCLOSURE. WHERE THE ROOM OR AREA EXITS INTO AN EXIT
 ENCLOSURE WHICH IS REQUIRED TO BE OF MORE THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION, THE ROOM OR AREA SHALL
 HAVE THE SAME FIRE-RESISTIVE CONSTRUCTION, INCLUDING
 THE SAME OPENING PROTECTION, AS REQUIRED FOR THE
 ADJACENT EXIT ENCLOSURE.
  
 6) FL EXISTING BUIULDING CODE 706.1 THE UPSTAIRS
 RESTROOM APPEARS TO BE NOT TOUCHED. PLEASE REVIEW
 EXISTING BUILDING CODE 706.1 ACCESSIBILITY AND11-4.1.6
 (2)
 2) ALTERATIONS TO AN AREA CONTAINING A PRIMARY
 FUNCTION. IN ADDITION TO THE REQUIREMENTS OF SECTION
 11-4.1.6(1), AN ALTERATION THAT AFFECTS OR COULD AFFECT
 THE USABILITY OF OR ACCESS TO AN AREA CONTAINING A
 PRIMARY FUNCTION SHALL BE MADE SO AS TO ENSURE THAT, TO
 THE MAXIMUM EXTENT FEASIBLE, THE PATH OF TRAVEL TO THE
 ALTERED AREA AND THE RESTROOMS, TELEPHONES, AND
 DRINKING FOUNTAINS SERVING THE ALTERED AREA, ARE
 READILY ACCESSIBLE TO AND USABLE BY INDIVIDUALS WITH
 DISABILITIES, UNLESS SUCH ALTERATIONS ARE
 DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN TERMS
 OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-14 Cont ID  
Sent By btrobaug Date 2010-07-14 Time 07:35 Rev Time 0.00
Received By btrobaug Date 2010-07-14 Time 07:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-06-28 Cont ID  
Sent By dlauderm Date 2010-06-28 Time 08:53 Rev Time 0.00
Received By dlauderm Date 2010-06-25 Time 07:20 Sent To  
Notes
2010-06-28 08:45:23IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR
 EMAIL: [email protected]
 OFFICE: 561-494-1083 (ENGINEERING SERVICES)
 OFFICE: 561-805-6716 (CONSTRUCTION SERVICES)
 REVIEW STATUS: FAILED
 1) BUILDING IS LOWER THAN THE STREET, A BACKWATER VALVE
 IS REQUIRED ON THE SANITARY LATERAL.
 2) NO METER OR BACKFLOW PREVENTER ARE SHOWN, WHERE ARE
 THEY LOCATED?
 3) WHERE IS THE SANITARY SEWER LATERAL LOCATED?
 4) CURBS AND SIDEWALKS ACROSS THE FULL FRONTAGE OF THE
 PROPERTY ARE REQUIRED. THIS WILL ALSO HELP STOP ANY
 ROAD RUN-OFF FROM FLOODING THE PROPERTY.
 5) NO STORM DRAINAGE SYSTEM INSTALLED, ONE IS REQUIRED.
 SUPPLY A STORMWATER PLAN AND THE PLANNED PARKING LOT
 ELEVATIONS. DUE TO THE FACT THE PROPERTY IS LOWER THAN
 THE STREET A STORM SEWER MAY NEED TO BE RUN OUT TO 25TH
 STREET (105' SOUTH OF THE SOUTH PROPERTY LINE).
 6) THE BUILDING APPEARS TO BE LOCATED INSIDE A 15' WIDE
 EASEMENT, WHY? SUPPLY A RECENT (LESS THAN ONE YEAR OLD)
 SURVEY. ALSO SUPPLY ELEVATIONS ON THE SURVEY SHOWING
 THE ROAD ELEVATIONS, THE FINISHED FLOOR ELEVATIONS
 (FFE).
 7) THE DUMPSTER CAN NOT GO IN THE LOCATION SHOWN. THE
 CITY GARBAGE TRUCK CAN NOT BACK UP MORE THAN 50'.
 8) THE DUMPSTER DESIGN DOES NOT SHOW THE CORRECT
 MEASUREMENTS. THE ENCLOSURE NEEDS TO BE SHOWN TO HAVE
 12.5' WIDE CLEARANCE AT THE GATES AND FROM THE GATES TO
 THE BACK WALL. THE ENCLOSURE APPEARS TO BE ONLY 12'
 WIDE AND DEEP (INSIDE DIMENSIONS).
 9) WHERE IS THE IRRIGATION SYSTEM?
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-29 Cont ID  
Sent By mcarsill Date 2010-06-29 Time 12:03 Rev Time 0.00
Received By mcarsill Date 2010-06-29 Time 11:36 Sent To  
Notes
2010-06-29 12:03:222616 EAST TAMARIND AVENUE
 PERMIT NUMBER 10060529
  
 1. WRONG LIFE SAFETY CODE REFERENCED ON PAGE A1.1.
 SHOULD READ NFPA 101-2006 EDITION.
  
 2. THE SINGLE EXIT SIGN ON PAGE E-1.1 IS DIRECTING
 PERSONS TO WHICH EXIT? PLEASE EXPLAIN RATIONALE.
  
 3. SINGLE EMERGENCY LIGHT ON PAGE E-1.1 PROVIDES
 ILLUMINATION TO WHICH EXIT ACCESS AREA? PLEASE EXPLAIN
 RATIONALE.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 7. WINDOW APPEARS BELOW EXIT STAIR. PLEASE REVIEW CODE
 SECTION RELATED TO OPENINGS NEAR AN EXIT STAIR.
  
 8. PLEASE PROVIDE MORE DETAILS ON THE FIRE
 EXTINGUISHERS THAT ARE SHOWN ON THE PLANS.
  
 9. NO ELEVATION DRAWINGS PROVIDED WITH PLANS. PLEASE
 SUBMIT ELEVATION DRAWINGS.
  
 10. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" AND 1" WIDE NUMBERS ARE
 REQUIRED.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-14 Cont ID  
Sent By hmoser Date 2010-07-14 Time 13:06 Rev Time 0.00
Received By hmoser Date 2010-06-17 Time 09:13 Sent To  
Notes
2010-06-22 09:13:33C-11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-07-01 Cont ID  
Sent By rkussner Date 2010-07-01 Time 10:26 Rev Time 0.00
Received By rkussner Date 2010-07-01 Time 10:26 Sent To  
Notes
2010-07-01 10:55:44***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. A SEPARATE IRRIGATION PERMIT IS REQUIRED. PLEASE
 APPLY FOR THE IRRIGATION PERMIT AND SUBMIT TWO SETS OF
 PLANS SHOWING THE LAYOUT OF THE SYSTEM, IDENTIFYING ALL
 OF THE COMPONENTS INCLUDING THE BACK FLOW PREVENTER AND
 RAIN GAUGE. THERE SHALL BE 120 PERCENT COVERAGE TO ALL
 LANDCAPED AREAS, INCLUDING THE RIGHT-OF-WAY.
  
 2. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 TWO SETS OF SIGNED AND SEALED PLANS AND A CERTIFIED
 COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COST.
  
 3. THE EXISTING FENCE ALONG TAMARIND SHALL BE RELOCATED
 TO BE ON THE INSIDE OF THE REQUIRED LANDSCAPE SETBACK
 WITH THE HEDGE PLANTED ON THE STREET SIDE OF THE FENCE
  
 4. PURSUANT TO SECTION 94-443 (C) (3) (A), TERMINAL
 LANDSCAPE ISLANDS SHALL NOT BE LESS THAN FIVE FEET IN
 WIDTH, EXCLUDING THE REQUIRED CURB.
  
 5. PLEASE PROVIDE ALL DIMENSIONS ON THE SITE PLAN. THE
 PARKING STALLS AND ACCESS DRIVE DO NOT SCALE OUT AT THE
 PROPOSED DIMENSIONS.
  
 6. PLEASE USE THE CITY APPROVED STRIPING DETAILS. A
 COPY OF THESE DETAILS CAN BE OBTAINED AT THE PLANNING
 AND ZONING DEPARTMENT.
  
 7. PLEASE PROVIDE SCREENING FOR THE CONDENSER UNITS.
  
 8. IF CAR STOPS ARE USED, CURBING IS NOT REQUIRED AT
 THE HEAD OF THE PARKING STALLS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-07-14 Cont ID  
Sent By hmoser Date 2010-07-14 Time 12:50 Rev Time 0.00
Received By hmoser Date 2010-07-14 Time 12:50 Sent To  
Notes
2010-07-14 13:01:28PLAN DENIED
 1) PLEASE PROVIDE GRILL AND CAN AND ALL DUCT SIZE ON
 THE PLANS .
 2) PLEASE INDICATE THE TYPE OF DOOR THAT IS BEING USED
 FOR THE MECHANICAL ROOM CLOSET ,PLEASE REFER TO SECTION
 602.2.1 MATERIALS EXPOSED IN PLENUM'S .
 3) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR .
 4) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-24 Cont ID  
Sent By lwagner Date 2010-06-24 Time 09:43 Rev Time 0.00
Received By lwagner Date 2010-06-24 Time 07:08 Sent To  
Notes
2010-06-24 09:43:01PLUMBING REVIEW #1
 DENIED:
  
 SHEET P-1.0 -
 1. A DRINKING FOUNTAIN AND SERVICE SINK WILL BE
 REQUIRED FOR FACTORY/ BUSINESS OCCUPANCY.
 TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES
 DRINKING FOUNTAIN-1 PER 100, 1 SERVICE SINK.
  
 2. SANITARY FROM SECOND FLOOR IS NOT PERMITTED TO FLOW
 THROUGH THE FIRST FLOOR FIXTURES.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT.
  
 3. A VENT WILL BE REQUIRED BETWEEN OR UPSTREAM OF THE
 FIRST FLOOR WATER CLOSETS. THE LAV. STACK WOULD BE
 ACCEPTABLE AS A WET VENT.
  
 4. MINIMUM WATER PIPE SIZE IS 3/4" UP TO THE LAST TWO
 FIXTURES: TABLE 603.1
 604.1 GENERAL. THE DESIGN OF THE WATER DISTRIBUTION
 SYSTEM SHALL CONFORM TO ACCEPTED ENGINEERING PRACTICE.
 METHODS UTILIZED TO DETERMINE PIPE SIZES SHALL BE
 APPROVED. TABLE 603.1 SHALL BE PERMITTED TO BE USED TO
 SIZE THE WATER DISTRIBUTION SYSTEM.
  
 SHEET A2.1
 1. THE SECOND FLOOR RESTROOM DOES NOT APPEAR TO BE ADA
 ACCESSABLE.
 FBC 2007 11-4.1.3 ACCESSIBLE BUILDINGS:(11) TOILET
 FACILITIES. IF TOILET ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-14 Cont ID  
Sent By astelly Date 2010-07-14 Time 08:45 Rev Time 0.00
Received By astelly Date 2010-07-14 Time 08:45 Sent To  
Notes
2010-07-14 09:11:46AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 AN INFORMAL SITE PLAN REVIEW WILL BE REQUIRED FOR THE
 APPROVAL OF THE REDUCTION IN PARKING.