Plan Review Details - Permit 10060390
Plan Review Stops For Permit 10060390
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-16 Cont ID  
Sent By jgomez Date 2010-06-16 Time 14:13 Rev Time 0.00
Received By jgomez Date 2010-06-16 Time 14:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-16 Cont ID  
Sent By jgomez Date 2010-06-16 Time 09:32 Rev Time 0.00
Received By jgomez Date 2010-06-16 Time 08:25 Sent To  
Notes
2010-06-16 09:47:01RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION DESCRIBES REPAIR OF 800 S.F. OF
 FLAT ROOF. CLARIFY IF REPAIR OR REPLACEMENT TO VERIFY
 COMPLIANCE WITH SEC. 611 OF 2007 FBC-EXISTING BUILDING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR FLAT ROOF TO BE INSTALLED.
 CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION # 7 ON LAST PAGE OF NOA SUBMITTED.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 GENERAL LIMITATION #7 REQUIRES IT.
 ***NOTE: TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" WHEN DOING THE RAS 117
 CALCULATIONS.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
  
 4- SEPARATE PERMITS ARE REQUIRED WHEN REMOVING AND
 RELOCATING ANY ROOF EQUIPMENT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-16 Cont ID  
Sent By jgomez Date 2010-06-16 Time 08:25 Rev Time 0.00
Received By jgomez Date 2010-06-16 Time 08:25 Sent To  
Notes
***NONE***