Plan Review Details - Permit 10060354
Plan Review Stops For Permit 10060354
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-08-16 Cont ID  
Sent By lmartine Date 2010-08-16 Time 14:43 Rev Time 0.00
Received By lmartine Date 2010-08-16 Time 14:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2010-08-02 Cont ID  
Sent By dlauderm Date 2010-08-02 Time 12:15 Rev Time 1.50
Received By dlauderm Date 2010-08-02 Time 12:10 Sent To  
Notes
2010-08-02 12:23:23PERMIT COMMENTS:
 REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR
 CONTACT INFORMATION: DIRECT DIAL: 494-1083, FAX:
 494-1116, EMAIL: [email protected]
 FAILED:
 1) THERE IS NO ROOF OVER THE DUMPSTER PAD. A SANITARY
 SEWER CONNECTION CAN NOT BE MADE TO THE "FLOOR DRAINS"
 UNLESS THE AREA IS COVERED BY A ROOF. TO ALLOW THIS
 AREA TO DRAIN INTO THE SANITARY SEWER SYSTEM WOULD
 ALLOW RAIN WATER ACCESS TO THE SANITARY SYSTEM, WHICH
 IS NOT ALLOWED. THE ONLY WAY A DRAIN SYSTEM FOR THE
 ENCLOSURE CAN BE ALLOWED IS TO HAVE IT ROOFED.
 2) PRIOR TO ALLOWING THE "FLOOR DRAINS" UNDER A ROOF WE
 WOULD NEED TO SEE A SURVEY SHOWING THE GROUND OUTSIDE
 OF THE ROOFED AREA DRAINS AWAY FROM THE ROOFED AREA TO
 ENSURE THAT NO RAIN WATER WILL TRAVEL TO THE FLOOR
 DRAINS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-06-25 Cont ID  
Sent By efabian Date 2010-06-25 Time 09:05 Rev Time 1.00
Received By efabian Date 2010-06-25 Time 09:05 Sent To  
Notes
2010-06-25 09:15:19DENIED
  
 PLANS CONSTITUTE AN ILLEGAL DISCHARGE INTO A PUBLIC
 WATERS STORM WATER SYSTEM PER CITY OF WEST PALM BEACH
 ORDINANCE, ARTICLE V, SEC. 90-203(A):
  
 GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
  
 PLEASE CONTACT PLAN REVIEWER:
  
 EMERY P. FABIAN
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-822-1200
 FAX: 561-494-1116
 MOBILE: 561-662-2269
 EMAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-28 Cont ID  
Sent By rmcdouga Date 2010-07-28 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2010-07-28 Time 16:38 Sent To  
Notes
2010-08-11 10:05:418/11 TO PLUMBING
  
2010-07-28 16:39:39SENT TO ENGINEERING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-11 Cont ID  
Sent By shill Date 2010-06-25 Time 10:05 Rev Time 0.00
Received By shill Date 2010-06-14 Time 12:48 Sent To  
Notes
2010-06-14 12:48:33IN ENGINEERING BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-08-11 Cont ID  
Sent By lwagner Date 2010-08-11 Time 15:12 Rev Time 0.00
Received By lwagner Date 2010-08-11 Time 15:08 Sent To  
Notes
2010-08-11 15:12:48PLEASE SEE ENGINEERING COMMENTS.
 RAINWATER IS NOT PERMITTED TO ENTER THE SEWER SYSTEM
 SEC. 90-125 PROHIBITIONS AND LIMITATIONS OF DISCHARGE
 (5)