Plan Review Details - Permit 10060288
Plan Review Stops For Permit 10060288
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-08-11 Cont ID  
Sent By shill Date 2010-08-11 Time 14:54 Rev Time 0.00
Received By shill Date 2010-08-11 Time 14:54 Sent To  
Notes
2010-08-03 17:01:48***FERN MODEL*** DCAFMT2356A ***
 PROVISO - SITE PERMITS WILL REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4 SEPARATE PERMITS FOR ELECTRIC, PLUMBING, MECHANICAL,
 IMPACT PROTECTION, ROOF
 5. LOAD CALCS & SITE SPECIFIC ENERGY CALCS (IF
 REQUIRED) TO BE SUBMITTED WITH MECHANICAL PERMIT
 6. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-08-03 Cont ID  
Sent By shill Date 2010-08-03 Time 07:50 Rev Time 0.00
Received By shill Date 2010-08-03 Time 07:50 Sent To  
Notes
2010-08-03 07:53:48CORRECTION:
  
 PROVIDE LETTER FROM ARCHITECT AND ENGINEER WHICH GRANTS
 PERMISSION TO MASTER THE PLANS PREPARED BY THEM
 (STAIRS, FOUNDATION)
 SHEETS SK1, SK01 NOT IN PERMIT PACKAGE, PLEASE PROVIDE
  
  
 ***FERN MODEL*** DCAFMT2356A ***
 PROVISO - SITE PERMITS WILL REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4 SEPARATE PERMITS FOR ELECTRIC, PLUMBING, MECHANICAL,
 IMPACT PROTECTION, ROOF
 5. LOAD CALCS & SITE SPECIFIC ENERGY CALCS (IF
 REQUIRED) TO BE SUBMITTED WITH MECHANICAL PERMIT
 6. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-07-12 Cont ID  
Sent By shill Date 2010-07-12 Time 15:29 Rev Time 0.00
Received By shill Date 2010-07-07 Time 15:14 Sent To  
Notes
2010-07-12 15:31:22****CORRECTIONS****
 ****DCA MODEL FMT2356A***MFGR MODEL FERN (BAYBERRY)***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. AS DISCUSSED WITH CONTRACTOR, PLEASE PROVIDE LETTER
 FROM MANUFACTURER STATING THAT THE PORCH DECK DOES NOT
 INCLUDE SHEATHING.
  
 2. AS DISCUSSED WITH CONTRACTOR, SINCE THE STRUCTURE
 WAS NOT MANUFACTURED OR UNDER CONTRACT PRIOR TO
 3/1/2009, PROVIDE 2007 APPROVAL.
  
 THE ABOVE ITEMS MAY BE ADDRESSED VIA EMAIL.
  
 THE FOLLOWING DOES NOT NEED TO BE ADDRESSED, AVISORY
 ONLY:
  
 AFTER ISSUANCE OF THE MASTER, SITE PERMITS WILL
 REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3.
 5. STAIR OR DOOR LANDING DETAIL
 6. DETAIL FOR STRUCTURAL CONNECTION BETWEEN MODULES
 7 SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING
 HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF
 8. SITE SPECIFIC ENERGY CALCS REEQUIRED
 9. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By shill Date 2010-06-21 Time 18:20 Rev Time 0.00
Received By shill Date 2010-06-21 Time 18:20 Sent To  
Notes
2010-06-21 18:21:03****CORRECTIONS****
 ****DCA MODEL FMT2356A***MFGR MODEL FERN (BAYBERRY)***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R408.2, SPECIFY VENTILATION OPENING SIZE TO SHOW
 COMPLIANCE WITH THE FBC REQUIREMENT.
  
 2. ACCESS IS SHOWN UNDER THE PORCH. ENGINEER'S NOTE
 STATES THAT ACCESS IS NOT TO BE LOCATED UNDER THE
 PORCH. THIS LOCATION PROHIBITS ACCESS TO THE OTHER
 SECTION OF CRAWL SPACE. PROVIDE ACCESS TO ALL AREAS OF
 THE CRAWL SPACE FBC408.2.
  
 3. SK3 EXTERIOR STEM WALL SHOWS 8" MIN FROM GRADE TO
 BOTTOM OF FLOOR. SEE FBC R408.4, IF EXTERIOR GRADE IS
 AT 8", AN ACCESS AREA COMPLYING WITH FBC R408.4 SHALL
 BE PROVIDED. IN ORDER TO AVOID FIELD ISSUES, IT IS
 SUGGESTED THAT A DETAIL OR SPECIFICATION WITH SPECIFIC
 REQUIREMENTS BE PROVIDED.
  
  
  
 THE FOLLOWING DOES NOT NEED TO BE ADDRESSED, AVISORY
 ONLY:
  
 AFTER ISSUANCE OF THE MASTER, SITE PERMITS WILL
 REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3.
 5. STAIR OR DOOR LANDING DETAIL
 6. DETAIL FOR STRUCTURAL CONNECTION BETWEEN MODULES
 7 SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING
 HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF
 8. SITE SPECIFIC ENERGY CALCS REQUIRED
 9. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-07-27 Cont ID  
Sent By shill Date 2010-07-27 Time 17:35 Rev Time 0.00
Received By shill Date 2010-07-27 Time 17:35 Sent To  
Notes
2010-07-27 17:35:41TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-06 Cont ID  
Sent By vmolina Date 2010-07-06 Time 11:28 Rev Time 0.00
Received By vmolina Date 2010-07-01 Time 11:28 Sent To  
Notes
2010-07-08 09:57:577/8 TO ZONING
  
  
2010-07-06 11:28:36GAVE TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-21 Cont ID  
Sent By shill Date 2010-06-21 Time 18:21 Rev Time 0.00
Received By shill Date 2010-06-16 Time 09:41 Sent To  
Notes
2010-06-16 09:42:07TO SH DESK
  