Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-11-17 Cont ID  
Sent By shill Date 2010-11-17 Time 17:18 Rev Time 0.00
Received By shill Date 2010-11-17 Time 17:18 Sent To  
Notes
2010-11-17 17:18:54ROOF PRODUCT APPROVAL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-08-04 Cont ID  
Sent By shill Date 2010-08-04 Time 17:05 Rev Time 0.00
Received By shill Date 2010-08-04 Time 17:05 Sent To  
Notes
2010-08-04 09:51:05****DCA MODEL FMP3446J***MFGR MODEL BANYAN***
 SITE PERMITS WILL REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4. SEPARATE PERMITS FOR ELECTRIC, PLUMBING, GAS,
 MECHANICAL, IMPACT PROTECTION, ROOF
 5. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY,
 561-233-5025.
 6. MASTER PERMIT TO EXPIRE WHEN CODE CHANGES OR ON
 6/9/2011, WHICHEVER IS EARLIER, PER ROBERT C.
 SCROGGINS, P.E. LETTER
  
 PROVISO - PROVIDE SIGNED & SEALED ENERGY CALC "SOUTH"
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-08-04 Cont ID  
Sent By shill Date 2010-08-04 Time 08:38 Rev Time 0.00
Received By shill Date 2010-08-04 Time 08:38 Sent To  
Notes
2010-08-04 08:40:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE REUSE LETTER FROM ARCHITECT. THIS MAY
 BE SUBMITTED VIA EMAIL. (ADDRESSED 8/4)
  
 2. PLEASE NOTE THAT NO ENERGY CALCS WERE SUBMITTED FOR
 THE SOUTHERN ZONE. EITHER SUBMIT WORST CASE ENERGY
 CALCS TO BE A PART OF THE MASTER, OR SITE SPECIFIC
 ENERGY CALCS WILL BE REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-07-27 Cont ID  
Sent By shill Date 2010-07-27 Time 09:37 Rev Time 0.00
Received By shill Date 2010-07-27 Time 09:37 Sent To  
Notes
2010-07-27 09:39:15****CORRECTIONS****
 ****DCA MODEL FMP4586C***MFGR MODEL ALTHEA***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. AS DISCUSSED, PLEASE INCLUDE THE STAIR DETAIL WITH
 THE MASTER PERMITS. PLEASE REVISE THE DETAIL TO
 INCLUDE:
  
 FBC311.5.3.2, THE SUM OF TWO RISERS AND A TREAD TO
 EQUAL NOT LESS THAN 24" NOR MORE THAN 25".
  
 SPECIFY STRINGER ATTACHMENT, TOP AND BOTTOM.
  
 SPECIFY GUARD OPENING LIMITATIONS FBC R312.2 AND STAIR
 RAIL HEIGHT FBC R 311.5.6.1.
  
 2. AS DISCUSSED, THE MATING DETAIL WILL BE INCLUDED IN
 THE MASTER PERMITS. PLEASE PROVIDE AN ORIGINAL UNIT
 CONNECTION DETAIL, AND REVISE THE SECOND SHEET TO
 INCLUDE THE TITLE BLOCK OF THE PERSON RESPONSIBLE FOR
 THE DESIGN AND HAVE THE DOCUMENT SIGNED AND SEALED.
 FS471.
  
 3. ONLY ONE SET OF DCA PLANS WAS SUBMITTED, TWO SETS OF
 STRUCTURALS. PLEASE PROVIDE TWO IDENTICAL COLLATED SETS
 OF PLANS FOR PERMIT ISSUANCE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By shill Date 2010-07-06 Time 16:55 Rev Time 0.00
Received By shill Date 2010-06-21 Time 16:55 Sent To  
Notes
2010-07-07 09:41:12****CORRECTIONS****
 ****DCA MODEL FMP3446J***MFGR MODEL BANYAN (MONET)***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R408.2, SPECIFY VENTILATION OPENING SIZE TO SHOW
 COMPLIANCE WITH THE FBC REQUIREMENT, SK02B.
  
 2. ACCESS IS SHOWN UNDER THE PORCH. ENGINEER'S NOTE
 STATES THAT ACCESS IS NOT TO BE LOCATED UNDER THE
 PORCH, PLEASE REVISE. NOTE THAT THIS APPEARS TO BE
 ACCEPTABLE AS ACCESS IS PROVIDED TO THE CRAWL SPACE
 UNDER THE REMAINDER OF THE HOUSE SEPARATELY, FBC408.2.
  
 3. SK3 EXTERIOR STEM WALL SHOWS 8" MIN FROM GRADE TO
 BOTTOM OF FLOOR. SEE FBC R408.4, IF EXTERIOR GRADE IS
 AT 8", AN ACCESS AREA COMPLYING WITH FBC R408.4 SHALL
 BE PROVIDED. IN ORDER TO AVOID FIELD ISSUES, IT IS
 SUGGESTED THAT A DETAIL OR SPECIFICATION WITH SPECIFIC
 REQUIREMENTS BE PROVIDED.
  
 4. PLEASE CORRELATE NOTES. FOR INSTANCE, CRAWL SPACE
 ACCESS REFERS TO NOTE 7, WHICH IS CRAWL SPACE
 VENTILATION. CRAWL SPACE VENTILATION REFERS TO NOTE 8,
 WHICH IS FOR STUD WALLS.
  
 THE FOLLOWING DOES NOT NEED TO BE ADDRESSED, ADVISORY
 ONLY:
  
 AFTER ISSUANCE OF THE MASTER, SITE PERMITS WILL
 REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3.
 5. STAIR OR DOOR LANDING DETAIL
 6. DETAIL FOR STRUCTURAL CONNECTION BETWEEN MODULES
 7. STRUCTURAL DETAIL FOR GABLE WALL
 8. SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING
 HOOKUP, GAS HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF
 9. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY,
 561-233-5025.
 10. MASTER PERMIT TO EXPIRE WHEN CODE CHANGES OR ON
 6/9/2011, WHICHEVER IS EARLIER, PER ROBERT C.
 SCROGGINS, P.E. LETTER
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-27 Cont ID  
Sent By shill Date 2010-07-27 Time 16:43 Rev Time 0.00
Received By shill Date 2010-07-27 Time 16:43 Sent To  
Notes
2010-07-27 16:44:05TP SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-21 Cont ID  
Sent By shill Date 2010-07-06 Time 18:18 Rev Time 0.00
Received By shill Date 2010-06-16 Time 09:42 Sent To  
Notes
2010-06-16 09:42:50TO SH DESK
  