Plan Review Details - Permit 10060240
Plan Review Stops For Permit 10060240
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-08-26 Cont ID  
Sent By rregueir Date 2010-08-26 Time 14:31 Rev Time 0.00
Received By rregueir Date 2010-08-26 Time 14:31 Sent To  
Notes
2010-08-26 14:32:18OK TO PASS PER JWITMER. CONTRACTOR SUBMITTED
 APPLICATION. RJR

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-07-22 Cont ID  
Sent By jwitmer Date 2010-07-22 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2010-07-22 Time 16:39 Sent To  
Notes
2010-07-22 16:40:152ND REVIEW: PLANS ARE STAMPED CODE COMPLIANT FOR
 BUILDING, WILL NEED TO VERIFY LICNSURE OF CONTRACTOR,
 CURRENTLY TO BE DETRERMINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-14 Cont ID  
Sent By jwitmer Date 2010-06-14 Time 15:03 Rev Time 1.33
Received By jwitmer Date 2010-06-14 Time 15:03 Sent To  
Notes
2010-06-14 15:04:34PLANS ARE STAMPED CODE COMPLIANT FOR BUILDING, WILL
 NEED TO VERIFY LICNSURE OF CONTRACTOR, CURRENTLY TO BE
 DETRERMINED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-17 Cont ID  
Sent By jleahy Date 2010-08-17 Time 06:43 Rev Time 0.00
Received By jleahy Date 2010-08-17 Time 06:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-22 Cont ID  
Sent By btrobaug Date 2010-06-22 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2010-06-22 Time 12:18 Sent To  
Notes
2010-06-22 13:33:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SECTION 13-415.2.ABC.1. AND 13-415.2.C
 REFERENCED ON SHEET E-9 ARE FROM THE 2004 BUILDING CODE
 SEE ABOVE REFERENCED CODES FOR THE CURRENTLY ADOPTED
 CODES.
  
 2} 4.1 WATTS PER SQ/FT SHOWN IN THE "LUMINARY
 SCHEDULE", SHEET E-9 IS MUCH HIGHER THAN THE ALLOWED
 WATTAGES IN TABLE 13-415.B.1, 2007 FBC.
  
 3} THE 2005 NEC IS REFERENCED ON SHEET E-9 ALSO 220.20,
 220.11, 220.13, 220.15ON THE PANEL SCHEDULES ARE NOT
 ARTICLES IN THE 2008 NEC.
  
 4}PANEL 7LC CURCUITS #2, 4, 15 AND 22 HAVE # 12
 CONDUCTORS ON A 25 AMP OVERCURRENT DEVICE IN VIOLATION
 OF TABLE 310.16 AND 240.2(D) NEC.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-25 Cont ID  
Sent By mawillia Date 2010-06-25 Time 14:36 Rev Time 0.00
Received By mawillia Date 2010-06-25 Time 14:21 Sent To  
Notes
2010-06-25 14:36:10*****APPROVED*****
  
  
 APPROPRIATE PLAN SHEETS A-, A-2, A-3, E-4, AND E-11
 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-14 Cont ID  
Sent By vmolina Date 2010-07-14 Time 09:06 Rev Time 0.00
Received By vmolina Date 2010-07-14 Time 09:06 Sent To  
Notes
2010-07-14 09:10:32C-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-06-30 Time   Rev Time 0.00
Received By vmolina Date 2010-06-09 Time 10:20 Sent To  
Notes
2010-06-09 10:22:03C-26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-06-14 Cont ID  
Sent By jwitmer Date 2010-06-14 Time 15:04 Rev Time 0.00
Received By jwitmer Date 2010-06-14 Time 15:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By hmoser Date 2010-08-10 Time 10:36 Rev Time 0.00
Received By hmoser Date 2010-08-10 Time 10:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-30 Cont ID  
Sent By rregueir Date 2010-06-30 Time 14:34 Rev Time 0.00
Received By rregueir Date 2010-06-29 Time 16:35 Sent To  
Notes
2010-06-30 11:38:18REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE OVERALL SCOPE OF MECHANICAL WORK IS NOT CLEAR
 DUE TO THE MECHANICAL LEGEND. IT USES THE SAME WEIGHT
 LINE TO IDENTIFY BOTH NEW DUCT AND DUCT TO BE REMOVED.
 ALSO, THE SYMBOL FOR A FIRE DAMPER IS NOT THE SAME AS
 THE ONE USED ON THE FLOOR PLAN. ADDITIONALLY, THE
 SYMBOL FOR NEW DUCT TO BE ATTACHED TO EXISTING DUCT IS
 NOT USED ON FLOOR PLAN, EVEN THOUGH THIS CONDITION
 APPEARS TO OCCUR AT SEVERAL LOCATIONS. LASTLY, THE
 SYMBOLS FOR SUPPLY AND RETURN GRILLS APPEAR TO BE
 REVERSED FROM WHAT IS SHOWN ON THE FLOOR PLANS. PLEASE
 COORDINATE SYMBOL LEGEND AND FLOOR PLANS TO CLEARLY
 IDENTIFY THE SCOPE OF WORK PROPOSED AND FACILITATE A
 THOROUGH REVIEW PER FBC-B 106.1.1.
  
 2. PAGE M-2 SHOWS A MOVINCOOL CM 25 CEILING MOUNTED
 PACKAGE UNIT ABOVE THE SERVER ROOM. PLAN ALSO SHOW A
 12" ROUND CONDENSER EXHAUST DUCT DISCHARGING INTO THE
 RETURN AIR PLENUM. EXHAUST AIR SHALL BE DISCHARGED
 OUTDOORS TO A LOCATION FROM WHICH IT CANNOT AGAIN BE
 READILY DRAWN IN BY A VENTILATING SYSTEM IN ACCORDANCE
 WITH FBC-M 501.2. ALSO, EXHAUST DUCTS UNDER POSITIVE
 PRESSURE SHALL NOT BE LOCATED WITHIN A PLENUM IN
 ACCORDANCE WITH FBC-M 601.5.
  
 3. THE OPERATION MANUAL FOR THE CM 25 CALLS FOR A 1/2"
 DRAIN LINE. CONDENSATE WASTE AND DRAIN LINE SIZE SHALL
 BE NOT LESS THAN 3/4 INCH (19 MM) INTERNAL DIAMETER IN
 ACCORDANCE WITH FBC-M 307.2.2. ALSO, ENSURE
 NONCOMBUSTIBLE OR PLENUM RATED MATERIALS ARE USED FOR
 CONDENSATE DRAIN AND CONTROL/POWER WIRING IN ACCORDANCE
 WITH FBC-M 602.2.1.
  
 4. THE OPERATION MANUAL FOR THE CM 25 INDICATES THAT
 THE DRAIN LINE FROM THE UNIT IS NOT TO BE TRAPPED.
 HOWEVER, NOTE ON PAGE P-1 CALLS FOR 1 1/4" CD TRAP.
 CONDENSATE DRAINS SHALL BE TRAPPED AS REQUIRED BY THE
 EQUIPMENT OR APPLIANCE MANUFACTURER PER FBC-M 307.2.4.
  
 5. SHOW A MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION FOR THE CM 25 IN ACCORDANCE WITH FBC-M
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-08-26 Cont ID  
Sent By lwagner Date 2010-08-26 Time 09:10 Rev Time 0.00
Received By lwagner Date 2010-07-21 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-22 Cont ID  
Sent By lwagner Date 2010-06-22 Time 09:00 Rev Time 0.00
Received By lwagner Date 2010-06-21 Time 15:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-06-10 Cont ID  
Sent By lfranco Date 2010-06-10 Time 19:12 Rev Time 0.25
Received By lfranco Date 2010-06-10 Time 19:12 Sent To E
Notes
2010-06-10 19:13:15PLANNING AND ZONING: **** PASSED, *ZONING REVIEW NOT
 REQUIRED: INTERIOR WORK ONLY AND THE VALUE OF PROPOSED
 WORK DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  