Plan Review Details - Permit 10060009
Plan Review Stops For Permit 10060009
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By mawillia Date 2010-06-08 Time 12:52 Rev Time 0.00
Received By mawillia Date 2010-06-08 Time 12:30 Sent To  
Notes
2010-06-08 12:37:38*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-03 Cont ID  
Sent By wjolin Date 2010-06-03 Time 12:29 Rev Time 0.00
Received By wjolin Date 2010-06-03 Time 11:22 Sent To  
Notes
2010-06-03 12:26:56*****DENIED*****
  
 1) DEVICE LABELED AS "SECURITY HORN" SHOULD BE LABELED
 A FIRE ALARM SPEAKER PER NFPA 72.
  
 2) VERIFY DEVICE LABELED AS SECURITY KEY PAD DOES NOT
 RESTRICT EXIT ACCESS FOR TENANTS.
  
 3) NORTHEAST CORRIDOR ON FLOOR PLAN SHOWS A WALL
 CLOSING OFF THE CORRIDOR. THIS WALL DOES
 NOT MATCH THE ARCHITECTURAL FLOOR PLAN.
  
 4) PLEASE EXPLAIN THE BLANK "ENGINEER" BOX LOCATED IN
 THE TITLEBLOCK.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-08 Time 11:55 Rev Time 0.00
Received By vmolina Date 2010-06-08 Time 11:55 Sent To  
Notes
2010-06-08 11:55:51IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-03 Cont ID  
Sent By wjolin Date 2010-06-03 Time 11:21 Rev Time 0.00
Received By wjolin Date 2010-06-01 Time 12:03 Sent To  
Notes
2010-06-01 12:03:48IN FIRE BOX