Plan Review Details - Permit 10050792
Plan Review Stops For Permit 10050792
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-21 Cont ID  
Sent By jwitmer Date 2010-06-21 Time 10:17 Rev Time 0.55
Received By jwitmer Date 2010-06-21 Time 10:17 Sent To  
Notes
2010-06-21 10:17:56REVIEWED SHEET C-3 FOR BUILDING CODE COMPLIANCE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2010-06-09 Cont ID  
Sent By   Date 2010-06-09 Time   Rev Time 1.00
Received By   Date 2010-06-09 Time   Sent To  
Notes
2010-06-09 16:25:02POST PROJECT PERVIOUS AREA DELETED = 966 SF
 POST PROJECT PERVIOUS AREA ADDED = 1,125 SF
 NET POST PROJECT PERVIOUS AREA = ADDITION OF 159 SF
  
 159 SF PERVIOUS ADDED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-16 Cont ID  
Sent By jwitmer Date 2010-06-16 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2010-06-01 Time 11:42 Sent To  
Notes
2010-06-01 11:42:49IN ENG. BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-15 Cont ID  
Sent By eschneid Date 2010-06-15 Time 10:59 Rev Time 0.50
Received By eschneid Date 2010-06-11 Time 11:48 Sent To B
Notes
2010-06-15 11:01:21FAILED
  
 1) PROVIDE A SURVEY, LESS THAN ONE YEAR OLD, OF THE
 PROPERTY.
  
 2) A MINOR PLANNED DEVELOPMENT AMENDMENT SHALL BE
 SUBMITTED TO THE PLANNING & ZONING DEPARTMENT FOR A
 MODIFICATION TO THE APPROVED PLANS TO FOR THE TRUCK
 RAMP. THE BUILDING PERMIT WILL NOT BE APPROVED UNTIL
 THE MINOR AMENDMENT IS APPROVED.
  
 3) THE RELOCATION OF THE TREES REQUIRES A TREE
 ALTERATION PERMIT FROM THE PLANNING & ZONING DEPARTMENT
 IS REQUIRED AND A LANDSCAPE PERMIT.
  
 4) IT APPEARS THAT THE ACCESSIBLE ROUTE FROM THE NEW
 GATEHOUSE SIDEWALK IS BEING INTERRUPTED BY THE
 RECONFIGURATION OF THE AREA.
  
 5) WHAT IS HAPPENING TO THE AREA THAT WAS FORMERLY THE
 BUS PARKING? THERE IS NO NOTE TO DESCRIBE WHAT THIS
 PAVED AREA WILL BE. IF IT IS TO REMAIN BUS PARKING,
 THEN IT SHALL CONTINUE TO HAVE A TERMINAL LANDSCAPE
 ISLAND ON THE NORTH SIDE.
  
 6) WHERE WILL NEW BUS PARKING AREA BE LOCATED?
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.