Plan Review Details - Permit 10050791
Plan Review Stops For Permit 10050791
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-10 Cont ID  
Sent By jwitmer Date 2010-06-10 Time 10:18 Rev Time 0.77
Received By jwitmer Date 2010-06-10 Time 10:18 Sent To  
Notes
2010-06-10 11:22:13BUILDING PLAN REVIEW
 PERMIT: 10050791
 ADD: 1610 PALM BEACH LAKES
 CONT: CFR COASTAL ENTERPRISES
 TEL: (954)868-9692
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A200.5:
 1A) FLOOR PLAN DETAIL 1A/A200.5 INDICATES A EXISTING
 MASONARY COLUMN TO BE MODIFIED BUT IN THE OTHER DETAILS
 THERE IS NO CLARIFICATION AS TO WHAT THE MODIFICATION
 SHALL BE, PART OF THE
 MAIN WIND FORCE RESISTING SYSTEM, A CORNER COLUMN? 2007
 FBC-B 2107.2(1-7)
  
 1B) 1A/1B/& 1C / A200.5 NONE OF THESE DETAILS INDICATE
 THE TYPE OF CONCRETE NOR STRENGTH OF MIX FOR THE
 FOUNDATION, SLAB, COLUMN BLOCK OR POURED CONCRETE BEAM.
 2007 FBC-B 1901.4(9) MINIMUM CONCRETE COMPRESSIVE
 STRENGTH AT TIME OF POSTTENSIONING.
  
  
 1C) ROOF FRAMING DETAIL 1C/A200.5 INDICATES THE
 INSTALATION OF A 8X12 CONCRETE BEAM WTIH 4#5 BARS
 CONTINIOUS. PLANS DO NOT INDICATE COMPLIANCE WITH 2107
 ACI 530 -
 7.5.3.1 SHEAR REINFORCEMENT SHALL BE PROVIDED PARALLEL
 TO THE DIRECTION OF APPLIED SHEAR FORCE. SPACING OF
 SHEAR REINFORCEMENT SHALL NOT EXCEED THE LESSER OF D/2
 OR 48 INCHES.
 12"/2= 6" O.C.
  
 1D) THERE APPEARS TO BE A CONTRADICTION IN IF THE STEEL
 TRUSSES ARE TO BE ENGINEERED OR FIELD BUILT. SEE
 COMMENTS UNDER DETAIL 1C INDICATING SEE ATTACHED TRUSS
 DRAWINGS WHERE AS DETAIL # 5 INDICATES FIELD BUILT
 PRE-DESIGNED METAL TRUSSES. 2210.3 TRUSSES. THE DESIGN,
 QUALITY ASSURANCE, INSTALLATION AND TESTING OF
 COLD-FORMED STEEL TRUSSES SHALL BE IN ACCORDANCE WITH
 AISI-TRUSS, SUBJECT TO THE LIMITATIONS THEREIN.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2A) GLAZED DOOR- INTERIOR SWING
  
 2B) GLAZED WINDOWS
  
 2C) ROOFING ASSEMBLIES
  
 2D) TRUSS ANCHORS
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-15 Cont ID  
Sent By btrobaug Date 2010-06-15 Time 15:18 Rev Time 0.00
Received By btrobaug Date 2010-06-15 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-25 Cont ID  
Sent By mawillia Date 2010-06-25 Time 14:58 Rev Time 0.00
Received By mawillia Date 2010-06-25 Time 14:37 Sent To  
Notes
2010-06-25 14:58:28*****DENIED*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. THE GATE SHALL BE INSTALLED WITH A KNOX GATE ENTRY
 KEY SWITCH FOR EMERGENCY FIRE ACCESS. AMEND NOTE 4 ON
 A200.OR DRAWING.
  
 3. IN ADDITION TO ADDRESS NUMBER SHOWN ON THE GATE AS
 BEING AT LEAST 6" IN HEIGHT, WEST PALM BEACH CODE ALSO
 REQUIRES THAT ADDRESS NUMBERS SHALL BE AT LEAST 1" IN
 WIDTH.
  
 4. VERIFY (IF ANY) THAT THE STRUCTURE'S OVERHANG DOES
 NOT IMPEDE THE MINIMUM VERTICAL CLEARANCE OF 13' 6"
 REQUIRED FOR FIRE EMERGENCY APPARATUS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-06-25 Time 15:00 Rev Time 0.00
Received By vmolina Date 2010-06-01 Time 11:06 Sent To  
Notes
2010-06-01 11:08:10C-28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-15 Cont ID  
Sent By eschneid Date 2010-06-15 Time 10:39 Rev Time 1.25
Received By eschneid Date 2010-06-15 Time 10:39 Sent To  
Notes
2010-06-15 10:41:42FAILED
  
 1) PROVIDE A SURVEY, LESS THAN ONE YEAR OLD, OF THE
 PROPERTY.
  
 2) PROVIDE THE SETBACK DIMENSION FROM THE GATEHOUSE TO
 THE PROPERTY LINE. THIS SETBACK SHALL BE AT LEAST 25
 FEET.
  
 3) PROVIDE HEIGHT OF THE GATEHOUSE.
  
 4) PROVIDE THE ROOF OVERHANG ON THE PALM BEACH LAKES
 SIDE OF THE GATEHOUSE. PLEASE NOTE THAT THE ROOF
 OVERHANG MAY NOT EXTEND MORE THAN THREE (3) FEET INTO
 THE SETBACK (NO CLOSER THAN 22 FEET FROM FRONT PROPERTY
 LINE).
  
 5) DESCRIBE THE "ENTRY CONTROL CENTER". THIS IS AGAINST
 THE FLOW OF TRAFFIC IF IT IS USED AS A CALL BOX.
  
 6) THE INSTALLATION OF GATES, FENCES AND COLUMNS
 REQUIRES A SEPARATE PERMIT.
  
 7) NOTE: GATES, FENCES AND COLUMNS MAY ONLY BE A
 MAXIMUM OF 4 FEET TALL WITHIN THE FRONT 25 FOOT
 SETBACK. PLEASE PROVIDE THE 25 FOOT SETBACK LINE ON THE
 PLANS.
  
 8) THE AERIAL OF THE AREA SHOWS TREES AND OTHER
 LANDSCAPE IN CLOSE PROXIMITY TO THE PROPOSED GUARD
 HOUSE AND ENTRY SIDEWALKS. PLEASE INDICATE WHAT IF ANY
 LANDSCAPE IS BEING AFFECTED. IF TREES ARE TO BE REMOVED
 AND/OR RELOCATED THEN A TREE ALTERATION PERMIT FROM THE
 PLANNING & ZONING DEPARTMENT IS REQUIRED AND A
 LANDSCAPE PERMIT IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.