Plan Review Details - Permit 10050764
Plan Review Stops For Permit 10050764
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-16 Cont ID  
Sent By mawillia Date 2010-06-16 Time 13:25 Rev Time 0.00
Received By mawillia Date 2010-06-16 Time 12:44 Sent To  
Notes
2010-06-16 13:21:16*****APPROVED*****
  
 DRAWINGS AND CALCULATIONS WERE SIGNED, DATED AND
 STAMPED APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-28 Cont ID  
Sent By wjolin Date 2010-05-28 Time 15:35 Rev Time 0.00
Received By wjolin Date 2010-05-28 Time 14:46 Sent To  
Notes
2010-05-28 15:29:10*****DENIED*****
  
  
 1) PROVIDE HYDRAULIC CALCULATIONS AS ADDITIONAL
 SPRINKLERS HAVE BEEN ADDED TO EXISTING BRANCH LINES.
  
 2) 2-1/2" CROSS MAIN SIZE CONFLICTS WITH ORIGINAL 2007
 DRAWINGS SHOWING 2" CROSS MAINS.
  
 3) DRAWING SCALE IS 1/8"=1'-0" NOT 1/4"=1'-0".
  
  
 WESLEY JOLIN &
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-16 Cont ID  
Sent By vmolina Date 2010-06-16 Time 11:28 Rev Time 0.00
Received By vmolina Date 2010-06-16 Time 11:28 Sent To  
Notes
2010-06-16 11:29:00IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-28 Cont ID  
Sent By wjolin Date 2010-05-28 Time 14:46 Rev Time 0.00
Received By wjolin Date 2010-05-27 Time 11:24 Sent To  
Notes
2010-05-27 11:24:53IN FIRE BOX