Plan Review Details - Permit 10050763
Plan Review Stops For Permit 10050763
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-07 Cont ID  
Sent By mawillia Date 2010-06-07 Time 13:42 Rev Time 0.00
Received By mawillia Date 2010-06-07 Time 13:07 Sent To  
Notes
2010-06-07 13:25:56*****APPROVED W/PROVISO*****
  
 AFTER CONFERRING WITH THE FIRE ALARM CONTRACTOR, PLAN
 SHEET FA-1 WAS STAMPED, INITIALED, AND DATED; READY FOR
 PERMIT ISSUANCE. IT WAS UNDERSTOOD OF THE FOLLOWING
 PROVISO FOR THE ISSUANCE OF THIS PERMIT:
  
 PRIOR TO THE FIRE ALARM FINAL - INSPECTION CODE #302,
 REVISED PLANS (SHOWING THE ADDED DUCT DETECTOR'S
 ADDRESS AND SHOWING HOW IT IS ADDED TO THE FIRE ALARM
 RISER DIAGRAM) SHALL BE SUBMITTED TO THIS OFFICE FOR
 REVIEW, APPROVAL, AND RETENTION.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-28 Cont ID  
Sent By mawillia Date 2010-05-28 Time 15:46 Rev Time 0.00
Received By mawillia Date 2010-05-28 Time 15:31 Sent To  
Notes
2010-05-28 15:43:37*****UNSAT*****
  
  
 THE ADDED DUCT DETECTOR DOES NOT HAVE A DEVICE ADDRESS
 NOR DOES IT SHOW HOW IT IS ADDED TO THE FIRE ALARM
 RISER DIAGRAM.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-05-28 Time 15:32 Rev Time 0.00
Received By vmolina Date 2010-05-27 Time 11:26 Sent To  
Notes
2010-05-27 11:26:20IN FIRE BOX