Plan Review Stops For Permit 10050482 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2010-08-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-16 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-16 |
Time |
14:38 |
Sent To |
|
|
Notes |
2010-08-16 14:44:36 | THE APPRAISAL THAT WAS SUBMITTED AND REVIEWED BY THE | | BUILDING OFFICIAL INDICATES THAT THE WORK BEING DONE IS | | NOT A SUBSTANCIAL IMPROVEMENT. THEREFORE, PER THE NFIP | | THE STRUCTURE IS NOT REQUIRED TO BE ELEVATED AND NO | | ELEVATION CERTIFICATE IS REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-08 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-08 |
Time |
16:35 |
Sent To |
|
|
Notes |
2010-06-08 14:31:08 | 2007 FBC W/2009 REVISIONS | | ADDITION AND REMODEL | | | | DENIED BY BUILDING | | | | 1) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE WITH A | | BASE FLOOD ELEVATION OF 7 FEET. THE CITY OF WEST PALM | | BEACH MUNICIPAL CODE ARTICLE XVII SECTION 94-546 | | REQUIRES ALL NEW RESIDENTIAL CONSTRUCTION OR | | SUBSTANTIAL IMPROVEMENT OF ANY EXISTING RESIDENTIAL | | STRUCTURE TO HAVE THE LOWEST FLOOR ELEVATED TO SIX | | INCHES ABOVE THE BASE FLOOD ELEVATION. THIS REQUIREMENT | | ALSO APPLIES TO ALL SYSTEMS THAT SUPPLY THE STRUCTURE | | SUCH AS A/C EQUIPMENT. PROVIDE ELEVATIONS ON DRAWINGS | | THAT SHOW COMPLIANCE. | | | | 2) PROVIDE TWO COPIES OF A SURVEY. | | | | 3) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND | | WITHIN 600 FEET OF THE INTRACOASTAL WATERWAY. SECTION | | FBC R301.2.1.4.3 (2) OF THE 2009 REVISIONS TO THE 2007 | | FBC REQUIRES THE ROOF SHEATHING UPLIFT AND THE ROOF TO | | WALL UPLIFT LOADS TO BE INCREASED BY 20 PERCENT. SHOW | | COMPLIANCE. | | | | 4) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM | | BEACH COUNTY FOR IMPACT FEES AND A COPY OF THE PAID | | RECEIPT SUBMITTED BEFORE THE PERMIT IS ISSUED. | | | | 5) THERE HAVE BEEN SOME HANDWRITTEN CHANGES MADE TO | | SHEETS A101 AND A103 OF THE PLANS. HANDWRITTEN CHANGES | | TO SIGNED AND SEALED PLANS ARE NOT ALLOWED EXCEPT BY | | THE ARCHITECT OR ENGINEER. FS 471 AND 481. | | | | 6) PLEASE UPDATE THE CODE EDITION ON SHEETS S-0 AND S-4 | | TO THE 2007 FBC W/2009 REVISIONS AND ASCE 7-05. ALSO | | SPECIFY THE 2005 EDITIONS OF ACI 318 AND 530 PER | | CHAPTER 43 OF FBC RESIDENTIAL. | | | | 7) COORDINATE THE REVISED ARCHITECTURAL DIMENSIONS OF | | THE PORCH ADDITION WITH THE STRUCTURAL DRAWINGS. | | | | 8) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES | | GUTTERS WITH DOWNSPOUTS AT THE NEW PORCH ADDITION WITH | | EAVES OF LESS THAN 6 INCHES OF HORIZONTAL PROJECTION. | | | | 9) PLEASE CORRECT THE WINDOW SCHEDULE ID MARKS ON A103. | | THEY SHOULD BE W01 AND W02. | | | | 10) THE WINDOW AND DOOR PRESSURES ON S-4 APPEAR TO BE | | LOW. PLEASE REVIEW AND PROVIDE CALCULATIONS. | | | | 11) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS OR EVALUATION REPORTS FOR THE SPRAY FOAM | | INSULATION. | | | | 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | STRUCTURAL MULLIONS AS REQUIRED BY DCA RULE 9B-72. | | | | 13) PLEASE SPECIFY THE APPROVED ASSEMBLY, FASTENING | | OPTION AND THE DESIGN PRESSURE FOR THE TAMKO MODIFIED | | ROOF SYSTEM. SUBMIT TWO COPIES OF RAS 117 CALCULATIONS | | FOR ENHANCED UPLIFT AT THE PERIMETER AND CORNERS AS | | REQUIRED BY THE GENERAL LIMITATIONS ON PAGE 18 OF THE | | NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-05-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-24 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-20 |
Time |
15:39 |
Sent To |
|
|
Notes |
2010-05-24 08:32:01 | SEE PROVISO'S./WRT. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
swurafti |
Date |
2010-05-18 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
swurafti |
Date |
2010-05-18 |
Time |
15:25 |
Sent To |
|
|
Notes |
2010-05-18 15:25:39 | HISTORIC APPROVED BY JPAPA |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-08-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-07-23 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-07-23 |
Time |
11:33 |
Sent To |
|
|
Notes |
2010-07-23 11:33:35 | IN ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-08 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-05-19 |
Time |
10:44 |
Sent To |
|
|
Notes |
2010-05-19 10:47:26 | SENT TO R-19. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2010-08-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-17 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-17 |
Time |
12:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:23 |
Sent To |
|
|
Notes |
2010-06-08 09:23:49 | NEEDS IMPACT FEE REVIEW |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
N |
Date |
2010-08-17 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2010-08-17 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2010-08-17 |
Time |
09:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-08-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-16 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-16 |
Time |
10:45 |
Sent To |
|
|
Notes |
2010-08-16 11:35:29 | 2007 FBC W/2009 REVISIONS | | | | MECHANICAL REVISIONS REQUIRED. | | | | 1) THE ENERGY CALCULATION COVERSHEET APPEARS TO BE | | USING THE WHOLE HOUSE METHOD TO SHOW COMPLIANCE BY | | LISTING THE CONDITIONED AREA AS 3976 SQFT. IN ORDER TO | | USE THIS METHOD THE WHOLE BUILDING ENVELOPE AND ALL OF | | ITS MAJOR ENERGY CONSUMING SYSTEMS ARE REQUIRED TO BE | | CALCULATED AND COMPARED TO A BASELINE HOUSE OF THE SAME | | CONFIGURATION. HOWEVER, ONLY TWO HVAC SYSTEMS ARE | | SPECIFIED, A 12K AND AN 18K. THE FORM 1100A-08 LISTS | | THE COOLING SYSTEMS CAPACITY AS 41.2 K BTUH AND THE | | MANUAL J CALCS. SPECIFIES 32,539 BTUH FOR THE 592 SQFT | | OF ADDED SPACE. PLEASE COORDINATE THE CALCULATIONS, | | FORMS AND PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:23 |
Sent To |
|
|
Notes |
2010-06-08 09:26:38 | 2007 FBC W/2009 REVISIONS | | ADDITION AND REMODEL | | | | DENIED BY MECHANICAL | | | | 1) THE A/C UNIT SIZES SPECIFIED ON THE ENERGY | | CALCULATION FORM DOES NOT MATCH THE PLANS. THE PLANS | | SPECIFIES A 17,000 BTU COOLING WITH A 14.7 SEER AND THE | | ENERGY CALCS. LISTS A 12,000 BTU WITH A 17.8 SEER. | | PLEASE COORDINATE THE ENERGY CALCULATIONS AND EQUIPMENT | | SIZING CALCULATIONS WITH THE PLANS AND MAKE REQUIRED | | CORRECTIONS. FBC R M1401 | | | | 2) MECHANICAL EQUIPMENT TO BE LOCATED AT A MINIMUM OF | | 7.5 FEET BASE FLOOD ELEVATION. FBC R M1401.5 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-08 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2010-08-02 |
Time |
|
Rev Time |
0.00 |
Received By |
ajones |
Date |
2010-07-27 |
Time |
10:49 |
Sent To |
B |
|
Notes |
2010-08-02 14:10:16 | PLANNED APPROVED PER STAMPED/SIGNED PLANS BY CHARLES | | WU, PLANNING DIRECTOR, DATED AUGUST 2, 2010. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-06-15 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2010-06-15 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2010-06-15 |
Time |
15:45 |
Sent To |
|
|
Notes |
2010-06-15 15:45:25 | ZONING PLAN REVIEW | | | | PERMIT NO.: 10050482 | | ADDRESS: 2121 S. FLAGLER DRIVE | | CONTRACTOR/CONTACT: JOHN G. MITCHELL, INC. | | TELEPHONE NO.: 561.655.6000 | | SCOPE OF REVIEW: ADD ENCLOSED, AIR CONDITIONED PORCH | | AND PATIO ON EAST SIDE; ENCLOSE EXISTING WEST SIDE | | PORCH AND ADD AIR CONDITIONING; REMODEL KITCHEN; ALL | | RELATED ELECTRICAL, MECHANICAL, ROOFING AND PLUMBING, | | PER PLANS. | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | SHALL BE PROVIDED. BE SURE THE SURVEY NOTES THE | | DIMENSIONS FROM ALL PROPERTY LINES TO THE EXISTING | | STRUCTURE. | | | | 2) AS THE PROPOSED IMPROVEMENTS EXCEED 50% OF THE | | ASSESSED VALUE OF THE STRUCTURE, THE PROPERTY SHALL | | CONFORM TO THE PROVISIONS OF ARTICLE XIV (LANDSCAPING) | | OF THE CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS | | (ZLDRS). SEE LANDSCAPE PLAN REVIEWER???S COMMENTS FOR | | DETAIL. | | | | 3) THE DRIVEWAY SHALL NOT BE EXTENDED ONTO THE ???NEW | | SITE AREA??? AS THE SUBDIVISION PROCESS HAS NOT BEEN | | FINALIZED. THE PLANS NOTE THAT THIS WILL BE DONE ???BY | | OTHERS??????PLEASE CLARIFY THAT THIS IS NOT A PART OF | | THE SCOPE OF THIS PERMIT APPLICATION. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN ROACH, SENIOR PLANNER | | CITY OF WEST PALM BEACH | | PLANNING AND ZONING DEPARTMENT | | 401 CLEMATIS STREET - P.O. BOX 3366 | | WEST PALM BEACH, FLORIDA 33402 | | | | PHONE: 561.822.1435 | | FAX: 561.822.1460 | | | | EMAIL: [email protected] | | | | WWW.CITYOFWPB.COM | | |
|
|