Plan Review Details - Permit 10050403
Plan Review Stops For Permit 10050403
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-26 Cont ID  
Sent By vmolina Date 2010-05-26 Time 10:29 Rev Time 0.00
Received By vmolina Date 2010-05-26 Time 10:29 Sent To  
Notes
2010-05-26 10:29:27IN MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-21 Cont ID  
Sent By hmoser Date 2010-05-21 Time 07:18 Rev Time 0.00
Received By hmoser Date 2010-05-18 Time 09:57 Sent To  
Notes
2010-05-18 09:58:25INCOMING SENT TO MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-06-01 Cont ID  
Sent By hmoser Date 2010-06-01 Time 09:55 Rev Time 0.00
Received By hmoser Date 2010-06-01 Time 09:55 Sent To  
Notes
2010-06-01 10:12:02PASS PROVISO
 1) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE .
 2007 FBC (M)
 MECHANICAL EQUIPMENT , APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURE .
 2) PLEASE REFER TO SECTION 507.2.11 OPERATION 2007 FBC
 (M)
 TYPE 1 HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHEN EVER
 COOKING OPERATIONS OCCUR .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-05-21 Cont ID  
Sent By hmoser Date 2010-05-21 Time 07:04 Rev Time 0.00
Received By hmoser Date 2010-05-21 Time 07:04 Sent To  
Notes
2010-05-21 07:18:18PLAN DENIED
 1) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE .2007
 FBC (M)
 2) PLEASE PROVIDE A DETAIL FOR A CURB TIE DOWN TO THE
 ROOF ON THE PLANS (140 MPH)
 3) PLEASE SHOW THE DUCT WORK FOR THE HOOD ON THE PLANS
 .
 4) PLEASE SHOW THE TERMINATION OF THE DUCT WORK ON THE
 PLANS . 506.3.12.3
 5) PLEASE REFER TO SECTION 507.2.1.1 OPERATION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732