Plan Review Details - Permit 10050319
Plan Review Stops For Permit 10050319
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-06-10 Cont ID  
Sent By wjolin Date 2010-06-10 Time 15:45 Rev Time 0.00
Received By wjolin Date 2010-06-10 Time 15:06 Sent To  
Notes
2010-06-10 15:10:00*****APPROVED*****
  
 REVISION #3 DRAWINGS (FP-1 AND FP-2) AND HYDRAULIC
 CALCULATIONS WERE STAMPED, DATED AND APPROVED.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-06-03 Cont ID  
Sent By wjolin Date 2010-06-03 Time 13:55 Rev Time 0.00
Received By wjolin Date 2010-06-03 Time 12:38 Sent To  
Notes
2010-06-03 13:40:25*****DENIED REVISION*****
  
 1) SPRINKLERS PROTECTING SMALL COMPARTMENTS CANNOT BE
 OMMITTED FROM THE HYDRAULIC CALCULATION WHEN THE REMOTE
 AREA IS ALREADY REDUCED IN SIZE FROM 1,500 SQ.FT. TO
 900 SQ.FT. WITH THE USE OF QUICK RESPONSE SPRINKLERS
 (NFPA 13, SECTION 14.4.4.4.2). THIS AFFECTS PROOF
 CALCULATION #2 AND #3.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
 561-804-4700
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2010-05-25 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2010-05-25 Time 15:05 Sent To  
Notes
2010-05-25 15:15:45ON MAY 25, 2010, THIS WRITER ALONG WITH WESLEY JOLIN
 MET WITH BOB TOUCHE OF SOUTHERN FIRE PROTECTION. WE
 DISCUSSED THE REVISED PLANS AND IT WAS AGREED THAT NEW
 PLANS AND HYDRAULIC CALCULATIONS BE SUBMITTED FOR
 REVIEW TO THIS OFFICE. A REVIEW OF THE HYDRAULIC
 CALCULATIONS AND THE IMPACT ON THE BACKFLOW PREVENTION
 DEVICE AND FIRE LINE IS TO BE ASSURED. IT IS EXPECTED
 THAT NEW PLANS AND HYDRAULIC CALCULATIONS WILL BE
 SUMBITTED IN A DAY OR SO.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-10 Cont ID  
Sent By wjolin Date 2010-06-10 Time 15:06 Rev Time 0.00
Received By wjolin Date 2010-06-10 Time 15:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-03 Cont ID  
Sent By vmolina Date 2010-06-03 Time 09:05 Rev Time 0.00
Received By vmolina Date 2010-06-03 Time 09:04 Sent To  
Notes
2010-06-03 09:05:09IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-13 Cont ID  
Sent By rmcdouga Date 2010-05-13 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2010-05-13 Time 07:26 Sent To  
Notes
2010-05-13 07:27:24SENT TO FIRE BOX