Plan Review Stops For Permit 10050267 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-09-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-09-14 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-09-14 |
Time |
13:25 |
Sent To |
Z |
|
Notes |
2010-09-14 13:29:14 | PER CBAA CASE NUMBER 1393, THE NEW ADDITION WHICH IS | | LOCATED IN AN "A5" FLOOD ZONE IS TO HAVE A MINIMUM | | FINISH FLOOR ELEVATION OF 7.5' BFE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-23 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-23 |
Time |
09:03 |
Sent To |
|
|
Notes |
2010-08-23 10:55:59 | STATUS TO REMAIN AS FAILED UNTIL REQUIRED A5 FLOOD ZONE | | ELEVATION NOTED IN FIRST REVIEW HAS BEEN ADDRESSED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-06-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-03 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-03 |
Time |
14:01 |
Sent To |
|
|
Notes |
2010-06-03 14:01:04 | 2007 FBC W/2009 REVISIONS | | ADDITION | | | | DENIED BY BUILDING | | | | 1) ALTHOUGH THE PLANS HAVE BEEN REVIEWED AND STAMPED | | FOR IMPACT FEES BY PALM BEACH COUNTY, TWO COPIES OF THE | | PAID RECEIPT FROM PBC ARE REQUIRED TO BE SUBMITTED. | | | | 2) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE WITH A | | BASE FLOOD ELEVATION OF 7 FT. THE CITY OF WEST PALM | | BEACH CITY CODE ARTICLE XVII SECTION 94-546 REQUIRES | | ALL NEW RESIDENTIAL CONSTRUCTION OR SUBSTANTIAL | | IMPROVEMENT OF ANY EXISTING RESIDENTIAL STRUCTURE TO | | HAVE THE LOWEST FLOOR ELEVATED TO SIX INCHES ABOVE THE | | BASE FLOOD ELEVATION. THE SURVEY THAT WAS SUBMITTED | | INDICATES THE EXISTING STRUCTURE HAS A FINISHED FLOOR | | ELEVATION OF 6.87 FT. THIS PROJECT WILL REQUIRE THAT | | THE EXISTING STRUCTURE AND THE LOWEST FLOOR OF THE | | ADDITION AS WELL AS THE EQUIPMENT SERVICING THE | | BUILDING BE ELEVATED TO A MINIMUM OF 7.6 FT. ABOVE BFE. | | PROVIDE PLANS SHOWING COMPLIANCE. | | | | 3) SUBMIT TWO SETS OF SITE DRAINAGE PLANS SHOWING | | COMPLIANCE WITH FBC R401.3 . | | | | 4) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE | | INLAND WATERWAY. BASED ON FBC R301.2.1.4.3 THE EXPOSURE | | CATEGORY IS C AND THE ROOF SHEATHING UPLIFT AND | | ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20 | | PERCENT. PLEASE CORRECT PLANS. | | | | 5) THE ENERGY CALCULATIONS AND PLANS DO NOT MATCH. THE | | EXTERIOR WALL R-VALUES DIFFER. THE CEILING TYPE ON THE | | FORM IS VENTED ATTIC AND THE PLANS HAVE AN UN-VENTED | | ATTIC WITH ICYNENE. ITEM #1 ON THE FORM SHOULD BE NEW | | ADDITION, NOT EXISTING. THE OWNER AGENT IS REQUIRED TO | | SIGN THE FORM. | | | | 6) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY ESCAPE | | AND RESCUE OPENING AT THE GUEST ROOM /OFFICE. | | | | 7) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR | | SMOKE ALARMS AND CARBON MONOXIDE DETECTORS. | | | | 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | DCA RULE 9B-72 FOR THE STRUCTURAL WINDOW MULLIONS. | | | | 9) SUBMIT LEGIBLE DRAWINGS FOR THE RAYNOR SECTIONAL | | GARAGE DOOR PRODUCT APPROVALS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-08-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2010-08-10 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2010-08-10 |
Time |
10:44 |
Sent To |
|
|
Notes |
2010-08-10 10:45:25 | SEE RISER ON PAGE 14 FOR NOTES. | | | | 1ST MEANS OF DISCONNECT IS AT ATS NOT THE PANEL. JL |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-05-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-17 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-13 |
Time |
14:28 |
Sent To |
|
|
Notes |
2010-05-13 15:17:01 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | THESE COMMENTS RELATE TO SHEET 14: | | | | 1} NOTE #17 IS INCOMPLETE. SEE 210.12 NEC 2008 FOR ARC | | FAULT LOCATIONS, CHANGE NOTE TO REFLECT SAME. ALSO | | SEE406.11 FOR TAMPER RESISTANT RECEPTACLE REQUIREMENTS. | | | | 2} THE EQUIPMENT GROUND BETWEEN THE METER AND | | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH | | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN | | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN | | FROM THE FIRST MEANS OF DISCONNECT. 250.6. | | | | | | 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED SIZED | | PER 250.66. INDICATE LOCATION AND SIZE ON THE RISER. | | | | 4} THE AIR HANDLER CIRCUIT 27 & 29 ON THE PANEL | | SCHEDULE (35 AMPS) DOES NOT CORRELATE WITH THE A/C | | SCHEDULE MOCP (20) .408.4. | | | | THESE COMMENTS RELATE TO SHEET 11 | | | | 6} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO | | OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. | | | | 7} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | RESIDENTIAL FLORIDA BUILDING CODE. INDICATE LOCATION ON | | PLANS, SEE R313.4 FOR CARBOBON MONOXIDE DETECTION | | REQUIREMENTS. | | | | 8} VERIFY FAN CIRCUIT NUMBER IN UPPERBEDROOM. M16 IS | | LABELED "SPARE" ON THE SCHEDULE AND M15 WOULD BE IN | | VIOLATION OF 210.11(C)(3). | | | | 9} THE DISCONNECT FOR CU #2 IS IN VIOLATION OF WORKING | | SPACE CLEARANCE 110.26. | | | | NOTE THE GENERATER SHOWN ON SHEET 11 REQUIRES A | | SEPARATE PERMI WITH PLANS AND SPECIFICATIONS. ALSO A | | SURVEY ONDICATING SETBACKS. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-07-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-07-22 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-07-22 |
Time |
09:05 |
Sent To |
|
|
Notes |
2010-07-22 09:05:52 | SENT TO R2. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-06-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-03 |
Time |
14:01 |
Rev Time |
|
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2010-05-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-13 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-13 |
Time |
14:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
P |
Date |
2010-07-26 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-07-26 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-07-26 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-05-18 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-05-18 |
Time |
10:28 |
Sent To |
|
|
Notes |
2010-05-18 10:33:27 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDR. | | | | 2. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT TWO | | (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | SECTIONS 94-442 AND 94-445 OF THE ZLDR. SUBMIT A COST | | ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE | | MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST. | | | | 3. PLEASE APPLY FOR AN IRRIGATION PERMIT. SUBMIT TWO | | COPIES ON AN IRRIGATION PLAN THAT PROVIDES 120% | | COVERAGE TO ALL LANDSCAPED AREAS, INCLUDING THE | | RIGHT-OF-WAY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462, | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2011-02-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2011-02-15 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2011-02-15 |
Time |
08:13 |
Sent To |
|
|
Notes |
2011-02-15 08:14:11 | INCOMING SENT TO ROBERT MC DOUGAL DESK. JW |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2010-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-23 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-19 |
Time |
17:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-06-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-03 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-03 |
Time |
08:46 |
Sent To |
|
|
Notes |
2010-06-03 09:09:45 | 2007 FBC W/2009 REVISIONS | | ADDITION | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS FOR THE ADDITION AS REQUIRED BY FBC | | R M1401.3. THE EQUIPMENT SPECIFIED ON THE PLANS MUST | | CORRESPOND WITH THE CALCULATIONS. | | | | 2) THE ATTIC ACCESS OPENING IS REQUIRED TO BE WITHIN 6 | | FT OF THE AIR HANDLER AND SHALL MEET ALL REQUIREMENTS | | OF FBC R M1305.1.3. | | | | 3) PROVIDE CALCULATIONS OR OTHER DOCUMENTATION THAT THE | | MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND IS | | DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS | | REQUIRED BY FBC R M1307.3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2010-08-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-08-19 |
Time |
17:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-08-19 |
Time |
17:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2010-06-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-06-02 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-06-02 |
Time |
16:31 |
Sent To |
|
|
Notes |
2010-06-02 17:03:23 | 2007 FBC W/2009 REVISIONS | | ADDITION | | | | DENIED BY PLUMBING | | | | 1) THE 2" HORIZONTAL DRY VENT FOR THE WATER CLOSET | | SHOWN ON THE SANITARY ISOMETRIC ON SHEET 14 IS NOT | | ALLOWED. FBC R P3104.4 REQUIRES EVERY DRY VENT TO RISE | | VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL OF | | THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | 2) FBC R P3005.2.6 REQUIRES AN ACCESSIBLE CLEANOUT AT | | THE BASE OF EACH VERTICAL WASTE OR SOIL STACK. SHOW | | CLEANOUT AT BASE OF SOIL STACK FROM THE SECOND FLOOR ON | | ISOMETRIC. | | | | 3) THE WATER ISOMETRIC GOES FROM 3/4" TO 1" TO 3/4" ON | | THE HOT WATER JUST PAST THE TANKLESS HEATER. THIS | | APPEARS TO BE AN ERROR. PLEASE REVIEW. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2010-09-16 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2010-09-16 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2010-09-16 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2010-05-19 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2010-05-19 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2010-05-19 |
Time |
17:17 |
Sent To |
|
|
Notes |
2010-05-19 17:19:07 | AMY STELLY | | PLANNING AND ZONING | | 561-822-1442 | | | | PASSED W/ PROVISO | | | | REAR SETBACK MUST BE A MINIMUM OF 9 FEET. | | A LANDSCAPE PLAN MUST BE SUBMITTED FOR REVIEW. |
|
|