Plan Review Details - Permit 10050267
Plan Review Stops For Permit 10050267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-09-14 Cont ID  
Sent By rmcdouga Date 2010-09-14 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2010-09-14 Time 13:25 Sent To Z
Notes
2010-09-14 13:29:14PER CBAA CASE NUMBER 1393, THE NEW ADDITION WHICH IS
 LOCATED IN AN "A5" FLOOD ZONE IS TO HAVE A MINIMUM
 FINISH FLOOR ELEVATION OF 7.5' BFE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2010-08-23 Time 09:03 Sent To  
Notes
2010-08-23 10:55:59STATUS TO REMAIN AS FAILED UNTIL REQUIRED A5 FLOOD ZONE
 ELEVATION NOTED IN FIRST REVIEW HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-03 Cont ID  
Sent By rmcdouga Date 2010-06-03 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2010-06-03 Time 14:01 Sent To  
Notes
2010-06-03 14:01:042007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) ALTHOUGH THE PLANS HAVE BEEN REVIEWED AND STAMPED
 FOR IMPACT FEES BY PALM BEACH COUNTY, TWO COPIES OF THE
 PAID RECEIPT FROM PBC ARE REQUIRED TO BE SUBMITTED.
  
 2) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE WITH A
 BASE FLOOD ELEVATION OF 7 FT. THE CITY OF WEST PALM
 BEACH CITY CODE ARTICLE XVII SECTION 94-546 REQUIRES
 ALL NEW RESIDENTIAL CONSTRUCTION OR SUBSTANTIAL
 IMPROVEMENT OF ANY EXISTING RESIDENTIAL STRUCTURE TO
 HAVE THE LOWEST FLOOR ELEVATED TO SIX INCHES ABOVE THE
 BASE FLOOD ELEVATION. THE SURVEY THAT WAS SUBMITTED
 INDICATES THE EXISTING STRUCTURE HAS A FINISHED FLOOR
 ELEVATION OF 6.87 FT. THIS PROJECT WILL REQUIRE THAT
 THE EXISTING STRUCTURE AND THE LOWEST FLOOR OF THE
 ADDITION AS WELL AS THE EQUIPMENT SERVICING THE
 BUILDING BE ELEVATED TO A MINIMUM OF 7.6 FT. ABOVE BFE.
 PROVIDE PLANS SHOWING COMPLIANCE.
  
 3) SUBMIT TWO SETS OF SITE DRAINAGE PLANS SHOWING
 COMPLIANCE WITH FBC R401.3 .
  
 4) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INLAND WATERWAY. BASED ON FBC R301.2.1.4.3 THE EXPOSURE
 CATEGORY IS C AND THE ROOF SHEATHING UPLIFT AND
 ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20
 PERCENT. PLEASE CORRECT PLANS.
  
 5) THE ENERGY CALCULATIONS AND PLANS DO NOT MATCH. THE
 EXTERIOR WALL R-VALUES DIFFER. THE CEILING TYPE ON THE
 FORM IS VENTED ATTIC AND THE PLANS HAVE AN UN-VENTED
 ATTIC WITH ICYNENE. ITEM #1 ON THE FORM SHOULD BE NEW
 ADDITION, NOT EXISTING. THE OWNER AGENT IS REQUIRED TO
 SIGN THE FORM.
  
 6) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY ESCAPE
 AND RESCUE OPENING AT THE GUEST ROOM /OFFICE.
  
 7) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR
 SMOKE ALARMS AND CARBON MONOXIDE DETECTORS.
  
 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR THE STRUCTURAL WINDOW MULLIONS.
  
 9) SUBMIT LEGIBLE DRAWINGS FOR THE RAYNOR SECTIONAL
 GARAGE DOOR PRODUCT APPROVALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By jleahy Date 2010-08-10 Time 10:44 Rev Time 0.00
Received By jleahy Date 2010-08-10 Time 10:44 Sent To  
Notes
2010-08-10 10:45:25SEE RISER ON PAGE 14 FOR NOTES.
  
 1ST MEANS OF DISCONNECT IS AT ATS NOT THE PANEL. JL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-05-17 Cont ID  
Sent By btrobaug Date 2010-05-17 Time 10:22 Rev Time 0.00
Received By btrobaug Date 2010-05-13 Time 14:28 Sent To  
Notes
2010-05-13 15:17:01 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 THESE COMMENTS RELATE TO SHEET 14:
  
 1} NOTE #17 IS INCOMPLETE. SEE 210.12 NEC 2008 FOR ARC
 FAULT LOCATIONS, CHANGE NOTE TO REFLECT SAME. ALSO
 SEE406.11 FOR TAMPER RESISTANT RECEPTACLE REQUIREMENTS.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED SIZED
 PER 250.66. INDICATE LOCATION AND SIZE ON THE RISER.
  
 4} THE AIR HANDLER CIRCUIT 27 & 29 ON THE PANEL
 SCHEDULE (35 AMPS) DOES NOT CORRELATE WITH THE A/C
 SCHEDULE MOCP (20) .408.4.
  
 THESE COMMENTS RELATE TO SHEET 11
  
 6} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO
 OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED.
  
 7} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE. INDICATE LOCATION ON
 PLANS, SEE R313.4 FOR CARBOBON MONOXIDE DETECTION
 REQUIREMENTS.
  
 8} VERIFY FAN CIRCUIT NUMBER IN UPPERBEDROOM. M16 IS
 LABELED "SPARE" ON THE SCHEDULE AND M15 WOULD BE IN
 VIOLATION OF 210.11(C)(3).
  
 9} THE DISCONNECT FOR CU #2 IS IN VIOLATION OF WORKING
 SPACE CLEARANCE 110.26.
  
 NOTE THE GENERATER SHOWN ON SHEET 11 REQUIRES A
 SEPARATE PERMI WITH PLANS AND SPECIFICATIONS. ALSO A
 SURVEY ONDICATING SETBACKS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-22 Cont ID  
Sent By jgomez Date 2010-07-22 Time 09:05 Rev Time 0.00
Received By jgomez Date 2010-07-22 Time 09:05 Sent To  
Notes
2010-07-22 09:05:52SENT TO R2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-03 Cont ID  
Sent By rmcdouga Date 2010-06-03 Time 14:01 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-05-13 Cont ID  
Sent By btrobaug Date 2010-05-13 Time 14:28 Rev Time 0.00
Received By btrobaug Date 2010-05-13 Time 14:28 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-07-26 Cont ID  
Sent By rkussner Date 2010-07-26 Time 11:19 Rev Time 0.00
Received By rkussner Date 2010-07-26 Time 11:19 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By rkussner Date 2010-05-18 Time 10:28 Rev Time 0.00
Received By rkussner Date 2010-05-18 Time 10:28 Sent To  
Notes
2010-05-18 10:33:27***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT TWO
 (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDR. SUBMIT A COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST.
  
 3. PLEASE APPLY FOR AN IRRIGATION PERMIT. SUBMIT TWO
 COPIES ON AN IRRIGATION PLAN THAT PROVIDES 120%
 COVERAGE TO ALL LANDSCAPED AREAS, INCLUDING THE
 RIGHT-OF-WAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2011-02-15 Cont ID  
Sent By jwitmer Date 2011-02-15 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2011-02-15 Time 08:13 Sent To  
Notes
2011-02-15 08:14:11INCOMING SENT TO ROBERT MC DOUGAL DESK. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2010-08-19 Time 17:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-03 Cont ID  
Sent By rmcdouga Date 2010-06-03 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2010-06-03 Time 08:46 Sent To  
Notes
2010-06-03 09:09:452007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS FOR THE ADDITION AS REQUIRED BY FBC
 R M1401.3. THE EQUIPMENT SPECIFIED ON THE PLANS MUST
 CORRESPOND WITH THE CALCULATIONS.
  
 2) THE ATTIC ACCESS OPENING IS REQUIRED TO BE WITHIN 6
 FT OF THE AIR HANDLER AND SHALL MEET ALL REQUIREMENTS
 OF FBC R M1305.1.3.
  
 3) PROVIDE CALCULATIONS OR OTHER DOCUMENTATION THAT THE
 MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND IS
 DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS
 REQUIRED BY FBC R M1307.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-08-19 Cont ID  
Sent By rmcdouga Date 2010-08-19 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2010-08-19 Time 17:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-02 Cont ID  
Sent By rmcdouga Date 2010-06-02 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2010-06-02 Time 16:31 Sent To  
Notes
2010-06-02 17:03:232007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY PLUMBING
  
 1) THE 2" HORIZONTAL DRY VENT FOR THE WATER CLOSET
 SHOWN ON THE SANITARY ISOMETRIC ON SHEET 14 IS NOT
 ALLOWED. FBC R P3104.4 REQUIRES EVERY DRY VENT TO RISE
 VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL OF
 THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2) FBC R P3005.2.6 REQUIRES AN ACCESSIBLE CLEANOUT AT
 THE BASE OF EACH VERTICAL WASTE OR SOIL STACK. SHOW
 CLEANOUT AT BASE OF SOIL STACK FROM THE SECOND FLOOR ON
 ISOMETRIC.
  
 3) THE WATER ISOMETRIC GOES FROM 3/4" TO 1" TO 3/4" ON
 THE HOT WATER JUST PAST THE TANKLESS HEATER. THIS
 APPEARS TO BE AN ERROR. PLEASE REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2010-09-16 Cont ID  
Sent By astelly Date 2010-09-16 Time 14:47 Rev Time 0.00
Received By astelly Date 2010-09-16 Time 14:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-05-19 Cont ID  
Sent By astelly Date 2010-05-19 Time 17:17 Rev Time 0.00
Received By astelly Date 2010-05-19 Time 17:17 Sent To  
Notes
2010-05-19 17:19:07AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/ PROVISO
  
 REAR SETBACK MUST BE A MINIMUM OF 9 FEET.
 A LANDSCAPE PLAN MUST BE SUBMITTED FOR REVIEW.