Plan Review Details - Permit 10050143
Plan Review Stops For Permit 10050143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-21 Cont ID  
Sent By shill Date 2010-06-21 Time 14:53 Rev Time 0.00
Received By shill Date 2010-06-21 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-05-10 Cont ID  
Sent By shill Date 2010-05-10 Time 17:20 Rev Time 0.00
Received By shill Date 2010-05-10 Time 17:20 Sent To  
Notes
2010-05-10 17:21:41PROVISO
  
 REVISION REQUIRED - REVISE INSTALLATION SCHEDULE TO
 CORRECT SPANS AND REVISE ANCHOR SPACING AS REQUIRED
 FOR INSTANCE, OPENING 5 HAS A SIZE OF 85", SO SPAN
 SHOULD BE 89" (SPAN = BLADE LENGTH FOR ACCORDIONS,
 ANCHOR TO ANCHOR FOR PANELS)
  
 REVISE FLOOR PLAN TO SHOW EMERGENCY MEANS OF ESCAPE
  
 ISSUED AT CONTRACTOR'S RISK
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-10 Cont ID  
Sent By shill Date 2010-05-10 Time 17:21 Rev Time 0.00
Received By shill Date 2010-05-06 Time 13:34 Sent To  
Notes
2010-05-06 13:35:44MISC. 1