Plan Review Details - Permit 10040634
Plan Review Stops For Permit 10040634
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-08-12 Cont ID  
Sent By jgomez Date 2010-08-12 Time 12:07 Rev Time 0.00
Received By jgomez Date 2010-08-12 Time 12:03 Sent To  
Notes
2010-08-12 12:08:46ROOF INFORMATION REQUESTED ON PROVISO IS PROVIDED ON
 ROOF PERMIT #10080317.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-06-10 Cont ID  
Sent By jgomez Date 2010-06-10 Time 13:54 Rev Time 0.00
Received By jgomez Date 2010-06-10 Time 13:52 Sent To  
Notes
2010-06-10 14:07:49BUILDING REVIEW APPROVED WITH PROVISO:
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO
 THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". REVISE THE OPENING
 DESIGN PRESSURES ON SHEET S1 TO REFLECT EXPOSURE "C".
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE TO BE INSTALLED.
 B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE
 INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES. SPECIFY HOW ARE TILES GOING TO BE INSTALLED.
 C) FLAT ROOF TO BE INSTALLED AND,
 * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE
 SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
 ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST
 PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA
 SUBMITTED.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 D) FRENCH DOOR: FRENCH DOOR NOA 07-0103.02 SUBMITTED
 EXPIRED ON FEBRUARY 24, 2010. NEED TO PROVIDE CURRENT
 NOA.
  
 3- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT
 APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- ARCHITECT TO SPECIFY ROOF VENTILATION AS REQUIRED BY
 SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 5- REVISE SHEET A3 TO OMIT WORK ON PORCH ROOF.
  
 6- SHEET S3: ROOF FRAMING DETAIL #3 AND SECOND FLOOR
 FRAMING DETAIL #2 WERE REVISED AND NOW THEY ARE MISSING
 THE WOOD FRAMING MEMBERS. MISSING THE TOP AND BOTTOM
 PLATES.
  
 7- REVISE STUCCO THICKNESS ON BUILDING SECTION #1 ON
 SHEET A2 AND NOTE S7 ON SHEET S2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-06-08 Cont ID  
Sent By jgomez Date 2010-06-08 Time 11:14 Rev Time 0.00
Received By jgomez Date 2010-06-08 Time 11:14 Sent To PC
Notes
2010-06-08 11:32:47RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO
 THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN
 CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1.
  
 RESPONSE: EXPOSURE WAS REVISED ON SHEET S1, BUT THE
 OPENING DESIGN PRESSURES WERE NOT REVISED TO REFLECT
 EXPOSURE "C".
  
 2- OWES $2093.06. PERMIT FEE BALANCE.
  
 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE TO BE INSTALLED.
  
 RESPONSE: NOT SUBMITTED.
  
 B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE
 INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES. SPECIFY HOW ARE TILES GOING TO BE INSTALLED.
  
 RESPONSE: NOT SUBMITTED.
  
 C) FLAT ROOF TO BE INSTALLED AND,
 * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE
 SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
 ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST
 PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA
 SUBMITTED.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
  
 RESPONSE: NOT SUBMITTED.
  
 D) FRENCH DOOR: FRENCH DOOR NOA 07-0103.02 SUBMITTED
 EXPIRED ON FEBRUARY 24, 2010. NEED TO PROVIDE CURRENT
 NOA.
  
 4- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT
 APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS
 APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH
 THIS SUBMITTAL.
  
 5- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED
 ATTIC.
  
 RESPONSE: ARCHITECT'S PLANS DON'T SPECIFY ANY FOAM
 INSULATION AS SHOWN ON RESPONSE LETTER. ALSO, PLANS
 DON'T SPECIFY INSULATION VALUE FOR THE WALLS. AND,
 ENERGY CALCULATIONS WERE NOT REVISED. ARCHITECT TO
 SPECIFY WALL AND CEILING INSULATION ON PLANS AND
 COORDINATE INFORMATION WITH THE ENERGY CALCULATIONS AS
 REQUIRED.
  
 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO
 BE INSTALLED.
  
 RESPONSE: ARCHITECT'S RESPONSE WAS THAT WORK OMITTED
 FROM SCOPE OF WORK, BUT SHEET A3 WAS NOT REVISED TO
 OMIT THIS WORK.
  
 7- SHEET S3: ROOF FRAMING DETAIL #3 AND SECOND FLOOR
 FRAMING DETAIL #2 WERE REVISED AND NOW THEY ARE MISSING
 THE WOOD FRAMING MEMBERS. MISSING THE TOP AND BOTTOM
 PLATES.
  
 8- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 RESPONSE: NOT DONE.
  
 B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH
 INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK
 ROOF VENTILATION, ETC. SEE ITEM #5 ABOVE.
  
 RESPONSE: NOT DONE.
  
 9- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS
 AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS
 REQUIRED BY TABLE R702.1(1).
  
 RESPONSE: REVISE BUILDING SECTION #1 ON SHEET A2 AND
 NOTE S7 ON SHEET S2.
  
 10- BRING ALL REVISED PLANS TO HISTORIC TO GET THEM
 RE-STAMPED PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By jgomez Date 2010-05-18 Time 16:17 Rev Time 0.00
Received By jgomez Date 2010-05-18 Time 16:17 Sent To PC
Notes
2010-05-18 16:22:44RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO
 THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN
 CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- PROVIDE COPY OF THE PAID IMPACT FEES RECEIPT.
  
 4- OWES $2093.06. PERMIT FEE BALANCE.
  
 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE TO BE INSTALLED.
  
 B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE
 INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLAT ROOF TO BE INSTALLED AND,
 * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE
 SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
 ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST
 PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA
 SUBMITTED.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
  
 D) FRENCH DOOR WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 6- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT
 APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS
 APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH
 THIS SUBMITTAL.
  
 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED
 ATTIC.
  
 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO
 BE INSTALLED.
  
 9- CLEARLY COORDINATE TRUSS CONNECTOR SCHEDULE WITH
 FRAMING PLANS TO VERIFY COMPLIANCE WITH THE DESIGN
 LOADS OF SEC. R301.. FRAMING PLANS DON'T SPECIFY ANY
 CONNECTORS.
 ALSO, COORDINATE TRUSS CONNECTOR SCHEDULE WITH THE
 CONNECTORS SPECIFIED ON DETAILS SHOWN ON SHEET S3. EG:
 DETAIL #2 SPECIFIES SIMPSON HETA24. THIS IS A MASONRY
 EMBEDDED CONNECTOR. NEED TO SPECIFY WOOD TO WOOD
 CONNECTOR. REVISE AS REQUIRED.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5
 AND SEC. R312.
  
 11- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY
 THE OWNER/AGENT.
  
 B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH
 INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK
 ROOF VENTILATION, ETC. SEE ITEM #7 ABOVE.
  
 12- SHEET A0:
 A) REVISE CITED CODE. CURRENT CODE IS 2007 FLORIDA
 RESIDENTIAL CODE WITH 2009 REVISIONS NOT 2004 CODE.
  
 B) REVISE LEVEL OF ALTERATION. THIS IS NOT A LEVEL ONE
 ALTERATION. SEE CHAPTER 4 OF THE 2007 EXISTING BUILDING
 CODE TO PROPERLY CLASSIFIED ALTERATION LEVEL AND REVISE
 AS REQUIRED.
  
 13- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS
 AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS
 REQUIRED BY TABLE R702.1(1).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-29 Cont ID  
Sent By btrobaug Date 2010-04-29 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2010-04-29 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-09 Cont ID  
Sent By vmolina Date 2010-06-09 Time 12:33 Rev Time 0.00
Received By vmolina Date 2010-06-09 Time 12:33 Sent To  
Notes
2010-06-09 12:35:05REV. IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-25 Cont ID  
Sent By vmolina Date 2010-05-24 Time 13:20 Rev Time 0.00
Received By vmolina Date 2010-05-24 Time 13:20 Sent To  
Notes
2010-05-24 13:26:30R-22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-18 Cont ID  
Sent By jgomez Date 2010-05-18 Time 16:17 Rev Time 0.00
Received By jgomez Date 2010-04-27 Time 09:58 Sent To  
Notes
2010-04-27 09:58:37R 23
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By jgomez Date 2010-06-08 Time 10:13 Rev Time 0.00
Received By jgomez Date 2010-06-08 Time 10:13 Sent To  
Notes
2010-06-08 10:15:03PR RECEIPT: MU-2010-007762-0000.
 CALLED COUNTY 6/8/10 TO VERIFY THAT IMPACT FEES WERE
 PAID.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By jgomez Date 2010-05-18 Time 16:13 Rev Time 0.00
Received By jgomez Date 2010-05-18 Time 16:13 Sent To  
Notes
2010-05-18 16:14:16PROVIDE COPY OF PAID RECEIPT.

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2010-06-10 Cont ID  
Sent By jgomez Date 2010-06-10 Time 13:53 Rev Time 0.00
Received By jgomez Date 2010-06-10 Time 13:53 Sent To  
Notes
2010-06-10 13:54:50SCOPE OF WORK WAS REVISED. CONSTRUCTION VALUE WAS
 CHANGED TO $64,000. PORCH ADDITION ROOF WORK WAS
 DELETED FROM THE SCOPE OF WORK.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-05-26 Cont ID  
Sent By rkussner Date 2010-05-26 Time 15:46 Rev Time 0.00
Received By rkussner Date 2010-05-26 Time 15:46 Sent To  
Notes
2010-05-26 15:48:57***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS
 THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE
 STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH
 THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING
 SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS
 FOUND IN ARTICLE XIV OF THE ZLDR.
  
 2. REPEAT COMMENT: PLEASE SUBMIT TWO (2) COPIES OF A
 LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTIONS 94-442
 AND 94-445 OF THE ZLDR. A LANDSCAPE PLAN SHALL BE
 SUBMITTED, EVEN IF THE EXISTING LANDCAPE MEETS ALL
 REQUIREMENTS. WHEN APPLYING FOR THE LANDSCAPE PERMIT,
 PLEASE PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL
 COST OF ALL NEW LANDSCAPE MATERIEALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 3. REPEAT COMMENT: THE LANDSCAPE PLAN SHALL INCLUDE ALL
 ITEMS ENUMERATED IN SECTION 94-448 (D).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-05-14 Cont ID  
Sent By rkussner Date 2010-05-14 Time 17:17 Rev Time 0.00
Received By rkussner Date 2010-05-14 Time 17:17 Sent To  
Notes
2010-05-14 17:25:17***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. WHEN APPLYING FOR THE LANDSCAPE PERMIT,
 PLEASE PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL
 COST OF ALL LANDSCAPE MATERIEALS AND LABOR, BROKEN DOWN
 INTO UNIT COST.
  
 3. THE LANDSCAPE PLAN SHALL INCLUDE ALL ITEMS
 ENUMERATED IN SECTION 94-448 (D).
  
 4. IF ANY EXISTING TREES ON SITE WILL NEED TO BE
 REMOVED OR RELOCATED, A TREE ALTERATION PERMIT WILL BE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-05-18 Cont ID  
Sent By jgomez Date 2010-05-18 Time 16:16 Rev Time 0.00
Received By jgomez Date 2010-05-18 Time 16:14 Sent To  
Notes
2010-05-18 16:15:55NO DRAWINGS SUBMITTED. PROVIDE COMPLETE DRAWINGS AND
 MANUAL J CALCULATIONS UNDER A SEPARATE PERMIT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-18 Cont ID  
Sent By jgomez Date 2010-05-18 Time 16:17 Rev Time 0.00
Received By jgomez Date 2010-05-18 Time 16:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-06-10 Cont ID  
Sent By lfranco Date 2010-06-10 Time 10:23 Rev Time 0.00
Received By lfranco Date 2010-06-10 Time 10:23 Sent To L
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-06-02 Cont ID  
Sent By lfranco Date 2010-06-02 Time 19:57 Rev Time 0.50
Received By lfranco Date 2010-06-02 Time 19:57 Sent To L
Notes
2010-06-02 19:59:07PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 RE-SUBMITTAL: SHOW LOCATION OF ADDITION ON THE SURVEY
 AND SHOW DIMENSIONS FROM ALL PROPERTY LINES ON BOTH THE
 SURVEY AND SITE PLAN.
  
 3. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 RE-SUBMITTAL: LANDSCAPE COMMENTS ARE STILL OUTSTANDING.
  
 4. THERE APPEARS TO BE EXISTING VEGETATION (TREES)
 WITHIN THE AREA THAT THE PROPOSED ADDITION IS TO BE
 LOCATED. COORDINATE WITH ROBERT KUSSNER, LANDSCAPE
 PLANNER AT (561) 822-17462, PRIOR TO REMOVING ANY TREES
 ON SITE.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-05-14 Cont ID  
Sent By lfranco Date 2010-05-14 Time 16:23 Rev Time 0.50
Received By lfranco Date 2010-05-14 Time 16:23 Sent To L
Notes
2010-05-14 16:26:30PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 4. THERE APPEARS TO BE EXISTING VEGETATION (TREES)
 WITHIN THE AREA THAT THE PROPOSED ADDITION IS TO BE
 LOCATED. COORDINATE WITH ROBERT KUSSNER, LANDSCAPE
 PLANNER AT (561) 822-17462, PRIOR TO REMOVING ANY TREES
 ON SITE.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  