Plan Review Stops For Permit 10040634 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2010-08-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-08-12 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-08-12 |
Time |
12:03 |
Sent To |
|
|
Notes |
2010-08-12 12:08:46 | ROOF INFORMATION REQUESTED ON PROVISO IS PROVIDED ON | | ROOF PERMIT #10080317. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-06-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-06-10 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-06-10 |
Time |
13:52 |
Sent To |
|
|
Notes |
2010-06-10 14:07:49 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO | | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | LOCATED ON EXPOSURE "C" NOT "B". REVISE THE OPENING | | DESIGN PRESSURES ON SHEET S1 TO REFLECT EXPOSURE "C". | | | | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | A) ROOF TILE TO BE INSTALLED. | | B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE | | INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED | | ADHESIVES. SPECIFY HOW ARE TILES GOING TO BE INSTALLED. | | C) FLAT ROOF TO BE INSTALLED AND, | | * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER | | AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST | | PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE | | REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA | | SUBMITTED. | | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION | | #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T | | MEET THE DESIGN PRESSURES OF SEC. R301. | | D) FRENCH DOOR: FRENCH DOOR NOA 07-0103.02 SUBMITTED | | EXPIRED ON FEBRUARY 24, 2010. NEED TO PROVIDE CURRENT | | NOA. | | | | 3- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT | | APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | 4- ARCHITECT TO SPECIFY ROOF VENTILATION AS REQUIRED BY | | SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | 5- REVISE SHEET A3 TO OMIT WORK ON PORCH ROOF. | | | | 6- SHEET S3: ROOF FRAMING DETAIL #3 AND SECOND FLOOR | | FRAMING DETAIL #2 WERE REVISED AND NOW THEY ARE MISSING | | THE WOOD FRAMING MEMBERS. MISSING THE TOP AND BOTTOM | | PLATES. | | | | 7- REVISE STUCCO THICKNESS ON BUILDING SECTION #1 ON | | SHEET A2 AND NOTE S7 ON SHEET S2. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-06-08 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-06-08 |
Time |
11:14 |
Sent To |
PC |
|
Notes |
2010-06-08 11:32:47 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND | | CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO | | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN | | CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1. | | | | RESPONSE: EXPOSURE WAS REVISED ON SHEET S1, BUT THE | | OPENING DESIGN PRESSURES WERE NOT REVISED TO REFLECT | | EXPOSURE "C". | | | | 2- OWES $2093.06. PERMIT FEE BALANCE. | | | | 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | A) ROOF TILE TO BE INSTALLED. | | | | RESPONSE: NOT SUBMITTED. | | | | B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE | | INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED | | ADHESIVES. SPECIFY HOW ARE TILES GOING TO BE INSTALLED. | | | | RESPONSE: NOT SUBMITTED. | | | | C) FLAT ROOF TO BE INSTALLED AND, | | * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER | | AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST | | PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE | | REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA | | SUBMITTED. | | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION | | #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T | | MEET THE DESIGN PRESSURES OF SEC. R301. | | | | RESPONSE: NOT SUBMITTED. | | | | D) FRENCH DOOR: FRENCH DOOR NOA 07-0103.02 SUBMITTED | | EXPIRED ON FEBRUARY 24, 2010. NEED TO PROVIDE CURRENT | | NOA. | | | | 4- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT | | APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS | | APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH | | THIS SUBMITTAL. | | | | 5- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF | | 2007 FLORIDA RESIDENTIAL CODE. | | | | ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE | | ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED | | ATTIC. | | | | RESPONSE: ARCHITECT'S PLANS DON'T SPECIFY ANY FOAM | | INSULATION AS SHOWN ON RESPONSE LETTER. ALSO, PLANS | | DON'T SPECIFY INSULATION VALUE FOR THE WALLS. AND, | | ENERGY CALCULATIONS WERE NOT REVISED. ARCHITECT TO | | SPECIFY WALL AND CEILING INSULATION ON PLANS AND | | COORDINATE INFORMATION WITH THE ENERGY CALCULATIONS AS | | REQUIRED. | | | | 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS | | FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO | | BE INSTALLED. | | | | RESPONSE: ARCHITECT'S RESPONSE WAS THAT WORK OMITTED | | FROM SCOPE OF WORK, BUT SHEET A3 WAS NOT REVISED TO | | OMIT THIS WORK. | | | | 7- SHEET S3: ROOF FRAMING DETAIL #3 AND SECOND FLOOR | | FRAMING DETAIL #2 WERE REVISED AND NOW THEY ARE MISSING | | THE WOOD FRAMING MEMBERS. MISSING THE TOP AND BOTTOM | | PLATES. | | | | 8- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY THE | | OWNER/AGENT. | | | | RESPONSE: NOT DONE. | | | | B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH | | INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK | | ROOF VENTILATION, ETC. SEE ITEM #5 ABOVE. | | | | RESPONSE: NOT DONE. | | | | 9- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS | | AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS | | REQUIRED BY TABLE R702.1(1). | | | | RESPONSE: REVISE BUILDING SECTION #1 ON SHEET A2 AND | | NOTE S7 ON SHEET S2. | | | | 10- BRING ALL REVISED PLANS TO HISTORIC TO GET THEM | | RE-STAMPED PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-05-18 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-05-18 |
Time |
16:17 |
Sent To |
PC |
|
Notes |
2010-05-18 16:22:44 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO | | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN | | CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1. | | | | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | UP. | | | | 3- PROVIDE COPY OF THE PAID IMPACT FEES RECEIPT. | | | | 4- OWES $2093.06. PERMIT FEE BALANCE. | | | | 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | A) ROOF TILE TO BE INSTALLED. | | | | B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE | | INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED | | ADHESIVES. | | | | C) FLAT ROOF TO BE INSTALLED AND, | | * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER | | AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST | | PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE | | REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA | | SUBMITTED. | | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION | | #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T | | MEET THE DESIGN PRESSURES OF SEC. R301. | | | | D) FRENCH DOOR WITH TRANSOM ABOVE AS SHOWN ON PLANS. | | | | 6- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT | | APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS | | APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH | | THIS SUBMITTAL. | | | | 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF | | 2007 FLORIDA RESIDENTIAL CODE. | | | | ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE | | ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED | | ATTIC. | | | | 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS | | FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO | | BE INSTALLED. | | | | 9- CLEARLY COORDINATE TRUSS CONNECTOR SCHEDULE WITH | | FRAMING PLANS TO VERIFY COMPLIANCE WITH THE DESIGN | | LOADS OF SEC. R301.. FRAMING PLANS DON'T SPECIFY ANY | | CONNECTORS. | | ALSO, COORDINATE TRUSS CONNECTOR SCHEDULE WITH THE | | CONNECTORS SPECIFIED ON DETAILS SHOWN ON SHEET S3. EG: | | DETAIL #2 SPECIFIES SIMPSON HETA24. THIS IS A MASONRY | | EMBEDDED CONNECTOR. NEED TO SPECIFY WOOD TO WOOD | | CONNECTOR. REVISE AS REQUIRED. | | | | 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | BALCONY GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5 | | AND SEC. R312. | | | | 11- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY | | THE OWNER/AGENT. | | | | B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH | | INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK | | ROOF VENTILATION, ETC. SEE ITEM #7 ABOVE. | | | | 12- SHEET A0: | | A) REVISE CITED CODE. CURRENT CODE IS 2007 FLORIDA | | RESIDENTIAL CODE WITH 2009 REVISIONS NOT 2004 CODE. | | | | B) REVISE LEVEL OF ALTERATION. THIS IS NOT A LEVEL ONE | | ALTERATION. SEE CHAPTER 4 OF THE 2007 EXISTING BUILDING | | CODE TO PROPERLY CLASSIFIED ALTERATION LEVEL AND REVISE | | AS REQUIRED. | | | | 13- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS | | AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS | | REQUIRED BY TABLE R702.1(1). | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-04-29 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-04-29 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-04-29 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-06-09 |
|
|
Cont ID |
|
Sent By |
vmolina |
Date |
2010-06-09 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
vmolina |
Date |
2010-06-09 |
Time |
12:33 |
Sent To |
|
|
Notes |
2010-06-09 12:35:05 | REV. IN ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-05-25 |
|
|
Cont ID |
|
Sent By |
vmolina |
Date |
2010-05-24 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
vmolina |
Date |
2010-05-24 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-05-18 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-04-27 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2010-06-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-06-08 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-06-08 |
Time |
10:13 |
Sent To |
|
|
Notes |
2010-06-08 10:15:03 | PR RECEIPT: MU-2010-007762-0000. | | CALLED COUNTY 6/8/10 TO VERIFY THAT IMPACT FEES WERE | | PAID. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-05-18 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-05-18 |
Time |
16:13 |
Sent To |
|
|
Notes |
2010-05-18 16:14:16 | PROVIDE COPY OF PAID RECEIPT. |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
3 |
Status |
N |
Date |
2010-06-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-06-10 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-06-10 |
Time |
13:53 |
Sent To |
|
|
Notes |
2010-06-10 13:54:50 | SCOPE OF WORK WAS REVISED. CONSTRUCTION VALUE WAS | | CHANGED TO $64,000. PORCH ADDITION ROOF WORK WAS | | DELETED FROM THE SCOPE OF WORK. |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
F |
Date |
2010-05-26 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-05-26 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-05-26 |
Time |
15:46 |
Sent To |
|
|
Notes |
2010-05-26 15:48:57 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS | | THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE | | STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH | | THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING | | SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS | | FOUND IN ARTICLE XIV OF THE ZLDR. | | | | 2. REPEAT COMMENT: PLEASE SUBMIT TWO (2) COPIES OF A | | LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTIONS 94-442 | | AND 94-445 OF THE ZLDR. A LANDSCAPE PLAN SHALL BE | | SUBMITTED, EVEN IF THE EXISTING LANDCAPE MEETS ALL | | REQUIREMENTS. WHEN APPLYING FOR THE LANDSCAPE PERMIT, | | PLEASE PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL | | COST OF ALL NEW LANDSCAPE MATERIEALS AND LABOR, BROKEN | | DOWN INTO UNIT COST. | | | | 3. REPEAT COMMENT: THE LANDSCAPE PLAN SHALL INCLUDE ALL | | ITEMS ENUMERATED IN SECTION 94-448 (D). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462, |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2010-05-14 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-05-14 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-05-14 |
Time |
17:17 |
Sent To |
|
|
Notes |
2010-05-14 17:25:17 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDR. | | | | 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | THE ZLDR. WHEN APPLYING FOR THE LANDSCAPE PERMIT, | | PLEASE PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL | | COST OF ALL LANDSCAPE MATERIEALS AND LABOR, BROKEN DOWN | | INTO UNIT COST. | | | | 3. THE LANDSCAPE PLAN SHALL INCLUDE ALL ITEMS | | ENUMERATED IN SECTION 94-448 (D). | | | | 4. IF ANY EXISTING TREES ON SITE WILL NEED TO BE | | REMOVED OR RELOCATED, A TREE ALTERATION PERMIT WILL BE | | REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462, | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-05-18 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-05-18 |
Time |
16:14 |
Sent To |
|
|
Notes |
2010-05-18 16:15:55 | NO DRAWINGS SUBMITTED. PROVIDE COMPLETE DRAWINGS AND | | MANUAL J CALCULATIONS UNDER A SEPARATE PERMIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2010-05-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-05-18 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-05-18 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2010-06-10 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-06-10 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2010-06-10 |
Time |
10:23 |
Sent To |
L |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2010-06-02 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-06-02 |
Time |
19:57 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2010-06-02 |
Time |
19:57 |
Sent To |
L |
|
Notes |
2010-06-02 19:59:07 | PLANNING AND ZONING: **** FAILED **** | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | RE-SUBMITTAL: SHOW LOCATION OF ADDITION ON THE SURVEY | | AND SHOW DIMENSIONS FROM ALL PROPERTY LINES ON BOTH THE | | SURVEY AND SITE PLAN. | | | | 3. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDR. | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | THE ZLDR. | | | | RE-SUBMITTAL: LANDSCAPE COMMENTS ARE STILL OUTSTANDING. | | | | 4. THERE APPEARS TO BE EXISTING VEGETATION (TREES) | | WITHIN THE AREA THAT THE PROPOSED ADDITION IS TO BE | | LOCATED. COORDINATE WITH ROBERT KUSSNER, LANDSCAPE | | PLANNER AT (561) 822-17462, PRIOR TO REMOVING ANY TREES | | ON SITE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-05-14 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-05-14 |
Time |
16:23 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2010-05-14 |
Time |
16:23 |
Sent To |
L |
|
Notes |
2010-05-14 16:26:30 | PLANNING AND ZONING: **** FAILED **** | | | | 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE | | REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS. | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | 3. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDR. | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | THE ZLDR. | | | | 4. THERE APPEARS TO BE EXISTING VEGETATION (TREES) | | WITHIN THE AREA THAT THE PROPOSED ADDITION IS TO BE | | LOCATED. COORDINATE WITH ROBERT KUSSNER, LANDSCAPE | | PLANNER AT (561) 822-17462, PRIOR TO REMOVING ANY TREES | | ON SITE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|