Plan Review Details - Permit 10040630
Plan Review Stops For Permit 10040630
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By jwitmer Date 2010-06-08 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2010-06-08 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-12 Cont ID  
Sent By jwitmer Date 2010-05-12 Time 16:01 Rev Time 2.22
Received By jwitmer Date 2010-05-12 Time 16:01 Sent To  
Notes
2010-05-12 16:22:18BUILDING PLAN REVIEW
 PERMIT: 10040630
 ADD: 6312 GEORGIA AVE
 CONT: SHARKEY'S AIR
 TEL: (941)625-2143
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE PAINT MIX BOOTH
 IS TO BE RE-INSTALLED AT THIS LOCATION. THE CITY'S
 RECORDS DO NOT INDICATE ANY PERMITTED SPRAY BOOTH NOR
 FIRE SUPRESSION SYSTEMS.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE FOLLOWING:
  
 F] 416.1 GENERAL. THE PROVISIONS OF THIS SECTION SHALL
 APPLY TO THE CONSTRUCTION, INSTALLATION AND USE OF
 BUILDINGS AND STRUCTURES, OR PARTS THEREOF, FOR THE
 SPRAYING OF FLAMMABLE PAINTS, VARNISHES AND LACQUERS OR
 OTHER FLAMMABLE MATERIALS OR MIXTURES OR COMPOUNDS USED
 FOR PAINTING, VARNISHING, STAINING OR SIMILAR PURPOSES.
 SUCH CONSTRUCTION AND EQUIPMENT SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
  
 F] 416.2 SPRAY ROOMS. SPRAY ROOMS SHALL BE ENCLOSED
 WITH FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING. FLOORS SHALL BE WATERPROOFED
 AND DRAINED IN AN APPROVED MANNER.
  
 F] 416.2.1 SURFACES. THE INTERIOR SURFACES OF SPRAY
 ROOMS SHALL BE SMOOTH AND SHALL BE SO CONSTRUCTED TO
 PERMIT THE FREE PASSAGE OF EXHAUST AIR FROM ALL PARTS
 OF THE INTERIOR AND TO FACILITATE WASHING AND CLEANING,
 AND SHALL BE SO DESIGNED TO CONFINE RESIDUES WITHIN THE
 ROOM. ALUMINUM SHALL NOT BE USED.
  
  
 [F] 416.3 SPRAYING SPACES. SPRAYING SPACES SHALL BE
 VENTILATED WITH AN EXHAUST SYSTEM TO PREVENT THE
 ACCUMULATION OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL . WHERE SUCH
 SPACES ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE
 SPRAY CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD
 OF FLAMMABLE VAPORS.
  
  
 [F] 416.3.1 SURFACES. THE INTERIOR SURFACES OF SPRAYING
 SPACES SHALL BE SMOOTH AND CONTINUOUS WITHOUT EDGES;
 SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE OF
 EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING; AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE SPRAYING SPACE.
 ALUMINUM SHALL NOT BE USED.
  
  
 [F] 416.4 FIRE PROTECTION. AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL
 SPRAY, DIP AND IMMERSING SPACES AND STORAGE ROOMS AND
 SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 9.
  
  
 2) [F] 415.3 FIRE SEPARATION DISTANCE. GROUP H
 OCCUPANCIES SHALL BE LOCATED ON PROPERTY IN ACCORDANCE
 WITH THE OTHER PROVISIONS OF THIS CHAPTER. IN GROUPS
 H-2 AND H-3, NOT LESS THAN 25 PERCENT OF THE PERIMETER
 WALL OF THE OCCUPANCY SHALL BE AN EXTERIOR WALL.
 EXCEPTIONS:
 1. LIQUID USE, DISPENSING AND MIXING ROOMS HAVING A
 FLOOR AREA OF NOT MORE THAN 500 SQUARE FEET (46.5 M2)
 NEED NOT BE LOCATED ON THE OUTER PERIMETER OF THE
 BUILDING WHERE THEY ARE IN ACCORDANCE WITH THE FLORIDA
 FIRE PREVENTION CODE AND NFPA 30.
 2. LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT MORE
 THAN 1,000 SQUARE FEET (93 M2) NEED NOT BE LOCATED ON
 THE OUTER PERIMETER WHERE THEY ARE IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE AND NFPA 30.
 3. SPRAY PAINT BOOTHS THAT COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE NEED NOT BE LOCATED ON THE OUTER
 PERIMETER.
  
  
 3) PLEASE PROVIDE THE AMOUNT OF SPRAYABLE LIQUIDS
 INCLUDING THINNERS AND SOLVENTS. PLEASE SEE FBC-B TABLE
 307.1(1) FOR THE AMOUNTS OF COMBUSTIBLE LIQUIDS PER
 CONTROL AREAS.
  
 F] 307.4 HIGH-HAZARD GROUP H-2. BUILDINGS AND
 STRUCTURES CONTAINING MATERIALS THAT POSE A
 DEFLAGRATION HAZARD OR A HAZARD FROM ACCELERATED
 BURNING SHALL BE CLASSIFIED AS GROUP H-2. SUCH
 MATERIALS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
 CLASS I, II OR IIIA FLAMMABLE OR COMBUSTIBLE LIQUIDS
 WHICH ARE USED OR STORED IN NORMALLY OPEN CONTAINERS OR
 SYSTEMS, OR IN CLOSED CONTAINERS OR SYSTEMS PRESSURIZED
 AT MORE THAN 15 PSI (103.4 KPA) GAGE.
 F] 307.5 HIGH-HAZARD GROUP H-3. BUILDINGS AND
 STRUCTURES CONTAINING MATERIALS THAT READILY SUPPORT
 COMBUSTION OR THAT POSE A PHYSICAL HAZARD SHALL BE
 CLASSIFIED AS GROUP H-3. SUCH MATERIALS SHALL INCLUDE,
 BUT NOT BE LIMITED TO, THE FOLLOWING:
  
 CLASS I, II OR IIIA FLAMMABLE OR COMBUSTIBLE LIQUIDS
 THAT ARE USED OR STORED IN NORMALLY CLOSED CONTAINERS
 OR SYSTEMS PRESSURIZED AT 15 POUNDS PER SQUARE INCH
 GAUGE (103.4 KPA) OR LESS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-23 Cont ID  
Sent By btrobaug Date 2010-06-23 Time 10:52 Rev Time 0.00
Received By btrobaug Date 2010-06-23 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-10 Cont ID  
Sent By btrobaug Date 2010-05-10 Time 15:43 Rev Time 0.00
Received By btrobaug Date 2010-05-10 Time 15:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-14 Cont ID  
Sent By mawillia Date 2010-06-14 Time 14:48 Rev Time 0.00
Received By mawillia Date 2010-06-14 Time 14:41 Sent To  
Notes
2010-06-14 14:47:16*****APPROVED*****
  
  
 SINGLE PLAN SHEET B-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-11 Cont ID  
Sent By mawillia Date 2010-05-11 Time 16:12 Rev Time 0.00
Received By mawillia Date 2010-05-11 Time 15:44 Sent To  
Notes
2010-05-11 22:12:47*****PARTIAL APPROVAL*****
  
 TO BE HELD IN "F" STATUS UNTIL: ALL OTHER PLAN
 EXAMINER(S)' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-25 Cont ID  
Sent By vmolina Date 2010-05-25 Time 11:31 Rev Time 0.00
Received By vmolina Date 2010-05-25 Time 11:30 Sent To  
Notes
2010-05-25 11:35:38C-23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-25 Cont ID  
Sent By vmolina Date 2010-05-12 Time 11:29 Rev Time 0.00
Received By vmolina Date 2010-04-27 Time 10:12 Sent To  
Notes
2010-04-27 10:12:10B 13
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-06-21 Cont ID  
Sent By hmoser Date 2010-06-21 Time 11:04 Rev Time 0.00
Received By hmoser Date 2010-06-21 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-29 Cont ID  
Sent By rregueir Date 2010-04-29 Time 15:27 Rev Time 0.00
Received By rregueir Date 2010-04-29 Time 15:27 Sent To  
Notes
2010-04-29 15:28:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SCOPE OF WORK NOT CLEAR. THE APPLICATION STATES
 ???REINSTALL A PAINT MIX ROOM AT NEW LOCATION,??? BUT I
 WAS UNABLE TO FIND RECORD OF A PAINT MIXING ROOM AT
 THIS ADDRESS. FBC106. PLANS SHOW A NEW PAINT BOOTH.
 PROJECT DESCRIPTION SHOULD BE CONSISTENT WITH PLANS.
  
 2. PROVIDE A SITE PLAN WHICH SHOWS BUILDING IN RELATION
 TO THE LOT LINES; SEE EXHAUST REQUIREMENTS, FBC M501.2,
 FBC M501.2.1.
  
 3. SHOW THE DISTANCE BETWEEN THE EXHAUST AND INTAKE,
 FBC M501.2.1.
  
 4. FBC M607.5, EXHAUST THROUGH A 2 HOUR EXTERIOR WALL
 IS SHOWN. PLEASE ADDRESS.
  
 5. CODE INFORMATION PROVIDES INFORMATION REGARDING
 AMOUNTS OF PAINT PERMITTED WITHIN 6FT OF THE SPRAY
 AREA. PLEASE EXPLAIN, WHERE IS THE SPRAY AREA? WHERE
 WILL THE PAINT BE STORED, AND IN WHAT QUANTITIES, FBC
 M502.8.1? SEE FBC M 502.7, PAINT SPRAY REQUIREMENTS, IF
 THIS IS EXISTING, HOW DO EXISTING EXHAUST AND INTAKE
 OPENINGS AFFECT THE PROPOSED OPENINGS?
  
 6. A 2 HOUR INTERIOR WALL IS SHOWN, IS THIS EXISTING OR
 PROPOSED? FBC 106.
  
 7. A 2 HR FIRE RATED WALL IS SHOWN WITH NO DOOR, IS
 THIS CORRECT? A 24X24 OPENING IS SHOWN, PRESUMABLY FOR
 MAKEUP AIR. A DOOR WOULD INHIBIT THE FLOW OF MAKEUP
 AIR, BUT AN UNPROTECTED DOOR SIZED OPENING WOULD AFFECT
 THE FIRE RESISTANCE OF THE 2 HOUR WALL. PLEASE REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC M502.9.5.4, MAKEUP
 AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2010-05-06 Cont ID  
Sent By eschneid Date 2010-05-06 Time 13:37 Rev Time 0.75
Received By eschneid Date 2010-05-06 Time 13:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved