Plan Review Details - Permit 10040490
Plan Review Stops For Permit 10040490
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-16 Cont ID  
Sent By mawillia Date 2010-06-16 Time 14:16 Rev Time 0.00
Received By mawillia Date 2010-06-16 Time 13:09 Sent To  
Notes
2010-06-16 14:15:58*****APPROVED****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED. THE FIRE ALARM PLAN (FA-1 AND FA-1) WAS
 FIRE-STAMPED ACCORDINGLY; READY FOR PERMIT ISSUANCE.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2010-05-10 Time 12:00 Rev Time 0.00
Received By mawillia Date 2010-05-07 Time 14:25 Sent To  
Notes
2010-05-10 20:41:49*****DENIED*****
  
  
 1. THE SPECIFICATIONS PACKAGE INCLUDES INFORMATION FOR
 SINGLE-ENDED REFLECTED TYPE BEAM SMOKE DETECTORS
 INSTEAD OF HEAT DETECTORS AS LISTED IN THE FIRE ALARM
 PLAN.
  
 2. ON SHEET FA-2, THE FLOOR PLAN / FIRE ALARM SYSTEM
 LAYOUT IS TOO SMALL. ENLARGE THE DRAWING TO CLEARLY AND
 DISTINCTLY SHOW/LIST THE DEVICES AND THEIR
 CORRESPONDING ADDRESSES.
  
 3. THE PLAN INDICATES THAT SMOKE DETECTORS ARE
 INSTALLED IN THE SLEEPING ROOMS. PLEASE FAMILIARIZE
 YOURSELF AND BE ADVISED OF THE SMOKE ALARM REQUIREMENTS
 AS PER 32.2.3.4.3 OF 2006 NFPA 101 - LIFE SAFETY CODE -
 FLORIDA 2007 EDITION. ATTENTION: IN LIEU OF SMOKE
 ALARMS, FIRE ALARM SYSTEM SMOKE DETECTORS IN ACCORDANCE
 WITH NFPA 72 SHALL BE PERMITTED IF SO ARRANGED TO
 FUNCTION IN THE SAME MANNER AS SMOKE ALARMS.
  
 4. IN NEW CONSTRUCTION AND/OR CONVERSIONS, WHERE TWO OR
 MORE ALARMS ARE INSTALLED WITHIN A DWELLING UNIT, SUITE
 OF ROOMS, OR SIMILAR AREA, SHALL BE ARRANGED SO THAT
 THE OPERATION OF ANY SMOKE ALARM SHALL CAUSE ALL ALARMS
 WITHIN THESE LOCATIONS TO SOUND. SMOKE ALARMS SHALL
 RECEIVE THEIR OPERATING POWER FROM THE BUILDING
 ELECTRICAL SYSTEM.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-08 Time 08:20 Rev Time 0.00
Received By vmolina Date 2010-06-08 Time 08:20 Sent To  
Notes
2010-06-08 08:21:07IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-07 Cont ID  
Sent By mawillia Date 2010-05-10 Time 08:17 Rev Time 0.00
Received By mawillia Date 2010-04-21 Time 11:53 Sent To  
Notes
2010-04-21 11:53:23*****ROUTED TO FIRE BOX*****