Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-09-21 Cont ID  
Sent By mcarsill Date 2010-09-21 Time 14:27 Rev Time 0.00
Received By mcarsill Date 2010-09-21 Time 14:09 Sent To  
Notes
2010-09-21 14:27:46355 EDMORE ROAD
 PERMIT NUMBER 10040488
 FIRE ALARM SYSTEM INSTALLATION
  
  
 1. AFTER SEVERAL MEETINGS AND TELEPHONE CALLS, THE
 PLANS CONSIST OF SHEET FA-1 AND FA-2. THE FIRE ALARM
 INSTALLATION CONSISTS OF THE INSTALLATION OF MANUAL
 PULL STATIONS, CEILING HORN STROBES, AND STROBE LIGHTS.
  
 2. PER SECTION 32.2.3.4.1 "A MANUAL FIRE ALARM SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH 9.6." (FLORIDA
 FIRE PREVENTION CODE, LIFE SAFETY CODE, 101, 2006
 EDITION)
  
 3. PER SECTION 32.2.3.4.2 "OCCUPANT NOTIFICATION SHALL
 BE PROVIDED AUTOMATICALLY, WITHOUT DELAY, IN ACCORDANCE
 WITH 9.6.3" (FLORIDA FIRE PREVENTION CODE, LIFE SAFETY
 CODE, 101, 2006 EDITION)
  
 4. NOT PART OF THIS PLAN: "APPROVED SMOKE ALARMS SHALL
 BE PROVIDED IN ACCORDANCE WITH 9.6.2.9" (FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.1)
  
 5. "SMOKE ALARM SHALL BE INSTALLED ON ALL LEVELS,
 INCLUDING BASEMENTS, BUT EXCLUDING CRAWL SPACES AND
 UNFINISHED ATTICS" (FLORIDA FIRE PREVENTION CODE, LIFE
 SAFETY CODE, 101, 2006 EDITION, SECTION 32.2.3.4.3.2)
  
 6. "ADDITIONAL SMOKE ALARMS SHALL BE INSTALLED IN ALL
 LIVING AREAS, AS DEFINED IN 3.3.17.5" (FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.3)
  
 7. "EACH SLEEPING ROOM SHALL BE PROVIDED WITH AN
 APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.9"
 (FLORIDA FIRE PREVENTION CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.4)
  
 8) THE FIRE ALARM SYSTEM INSTALLATION TO BE TESTED WITH
 REPRESENTATIVES OF THIS OFFICE.
  
 9) FIRE ALARM INSTALLATION SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-06-16 Cont ID  
Sent By mawillia Date 2010-06-16 Time 15:48 Rev Time 0.00
Received By mawillia Date 2010-06-16 Time 14:42 Sent To  
Notes
2010-06-16 15:48:16*****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS 7 PLAN REVIEW
 COMMENTS STILL NEEDS TO BE ADDRESSED:
  
 1. THE PROJECT SCOPE OF WORK DESCRIBED ON THE
 APPLICATION DOES NOT CORRESPOND WITH THE SUBMITTED FIRE
 ALARM PLAN. PLEASE BE ADVISED THAT THE DESCRIBED WORK
 ON THE APPLICATION WILL BE REFLECTED ON THE PERMIT
 CARD.
  
 3. MANUAL PULL STATION 4 (M4) NOT SHOWN IN THE FIRE
 ALARM RISER. ADDITIONALLY ONLY 3 SUCH DEVICES ARE
 LISTED IN THE BATTERY CALCULATIONS.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-10 Cont ID  
Sent By mawillia Date 2010-05-10 Time 16:43 Rev Time 0.00
Received By mawillia Date 2010-05-10 Time 15:56 Sent To  
Notes
2010-05-10 21:58:18*****DENIED*****
  
  
 1. THE PROJECT SCOPE OF WORK DESCRIBED ON THE
 APPLICATION DOES NOT CORRESPOND WITH THE SUBMITTED FIRE
 ALARM PLAN.
  
 2. THE SPECIFICATIONS PACKAGE INCLUDES INFORMATION FOR
 SINGLE-ENDED REFLECTED TYPE BEAM SMOKE DETECTORS
 INSTEAD OF HEAT DETECTORS AS LISTED IN THE FIRE ALARM
 PLAN.
  
 3. MANUAL PULL STATION 4 (M4) NOT SHOWN IN THE FIRE
 ALARM RISER. ADDITIONALLY ONLY 3 SUCH DEVICES ARE
 LISTED IN THE BATTERY CALCULATIONS.
  
 4. SMOKE DETECTOR D2 IS IDENTIFIED IN THE FIRE ALARM
 RISER AS A HEAT DETECTOR.
  
 5. UNABLE TO LOCATE THE REMOTE ANNUNCIATOR (ANN-80) ON
 THE FA-2 SHEET.
  
 6. THE PLAN INDICATES THAT SMOKE DETECTORS ARE
 INSTALLED IN THE SLEEPING ROOMS. PLEASE FAMILIARIZE
 YOURSELF AND BE ADVISED OF THE SMOKE ALARM REQUIREMENTS
 AS PER 32.2.3.4.3 OF 2006 NFPA 101 - LIFE SAFETY CODE -
 FLORIDA 2007 EDITION. ATTENTION: IN LIEU OF SMOKE
 ALARMS, FIRE ALARM SYSTEM SMOKE DETECTORS IN ACCORDANCE
 WITH NFPA 72 SHALL BE PERMITTED IF SO ARRANGED TO
 FUNCTION IN THE SAME MANNER AS SMOKE ALARMS.
  
 7. IN NEW CONSTRUCTION AND/OR CONVERSIONS, WHERE TWO OR
 MORE ALARMS ARE INSTALLED WITHIN A DWELLING UNIT, SUITE
 OF ROOMS, OR SIMILAR AREA, SHALL BE ARRANGED SO THAT
 THE OPERATION OF ANY SMOKE ALARM SHALL CAUSE ALL ALARMS
 WITHIN THESE LOCATIONS TO SOUND. SMOKE ALARMS SHALL
 RECEIVE THEIR OPERATING POWER FROM THE BUILDING
 ELECTRICAL SYSTEM.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-09-14 Cont ID  
Sent By shill Date 2010-09-14 Time 14:43 Rev Time 0.00
Received By shill Date 2010-09-14 Time 14:42 Sent To  
Notes
2010-09-14 14:43:57TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-29 Cont ID  
Sent By vmolina Date 2010-06-29 Time 09:30 Rev Time 0.00
Received By vmolina Date 2010-06-29 Time 09:30 Sent To  
Notes
2010-06-29 09:31:06IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-08 Time 08:23 Rev Time 0.00
Received By vmolina Date 2010-06-08 Time 08:22 Sent To  
Notes
2010-06-08 08:23:14IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-11 Cont ID  
Sent By mawillia Date 2010-05-11 Time 08:15 Rev Time 0.00
Received By mawillia Date 2010-04-21 Time 11:51 Sent To  
Notes
2010-04-21 11:52:25*****ROUTED TO FIRE BOX*****