Plan Review Details - Permit 10040384
Plan Review Stops For Permit 10040384
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-05-26 Cont ID  
Sent By jgomez Date 2010-05-26 Time 13:24 Rev Time 0.00
Received By jgomez Date 2010-05-26 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-05-26 Cont ID  
Sent By jgomez Date 2010-05-26 Time 12:41 Rev Time 0.00
Received By jgomez Date 2010-05-26 Time 12:37 Sent To  
Notes
2010-05-26 12:59:28RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ROOF CALCULATIONS SUBMITTED:
  
 A) ENGINEER TO PROVIDE ACTUAL RAS 117 CALCULATIONS.
 FASTENING OPTION #1 ON PAGE 5 OF NOA 08-0924.14
 SUBMITTED IS GOOD ONLY FOR -60PSF. IT CAN'T BE USED FOR
 ALL ROOF ZONES AS SPECIFIED BY THE ENGINEER. PERIMETER
 AND CORNER AREAS REQUIRE HIGHER DESIGN PRESSURES.
  
 B) PROVIDE ACTUAL CALCULATIONS FOR COMPONENTS AND
 CLADDING. INFORMATION SUBMITTED IS INCORRECT.
 CALCULATED DESIGN PRESSURES ARE NOT FOR EXPOSURE "C".
 REVISE AS REQUIRED.
  
 C) CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL CODE
 WITH 2009 REVISIONS. ENGINEER TO REFER TO ASCE 7-05 NOT
 ASCE 7-02.
  
 D) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE AND FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002(2). MISSING THE
 ENGINEER'S ADDRESS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By jgomez Date 2010-04-19 Time 10:16 Rev Time 0.00
Received By jgomez Date 2010-04-19 Time 10:15 Sent To  
Notes
2010-04-19 10:31:30RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS ( 2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF MULE-HIDE PRODUCTS CO. INC NOA 08-0924.14
 SUBMITTED.
  
 2- CLARIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. IS IT AN INSULATED SYSTEM AS SHOWN ON PAGE 5
 SUBMITTED. OR IS IT A NON-INSULATED SYSTEM AS SHOWN ON
 PAGE 34 SUBMITTED.
 ***NOTE: NON-INSULATED SYSTEM ON PAGE 34 CAN'T NOT BE
 USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. 301 OF 2007 FLORIDA RESIDENTIAL CODE.
 AND, GENERAL LIMITATION #9 DOESN'T ALLOW NAIL
 ENHANCING. SEE LAST PAGE OF NOA SUBMITTED.
  
 3- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-19 Cont ID  
Sent By jgomez Date 2010-04-19 Time 10:15 Rev Time 0.00
Received By jgomez Date 2010-04-19 Time 10:15 Sent To  
Notes
***NONE***